FOSTER WHEELER USA - FIRED HEATER DIVISION

DAMPER & ACTUATOR DATA SHEET

Client: IOCL Heater Tag No.: 030-F-001, 030-F-002 Doc. No.: 1196-DPR-430
Location: Paradip Req No.: 1196REQ-430
Job No.:5-16-1196 Originator: JAK Date: April 6, 2009
Unit: Delayed Coker Heater Revision: 0 Date:

DAMPER DATA
1 TAG NUMBER
2 QUANITITY 4 4 12 2
Hot Flue Gas Cells #1 &
3 SERVICE #3
Hot Flue Gas Cell #2 Hot Air Cold Air Bypass
ORIENTATION Horizontal Duct Horizontal Duct Horizontal Duct Vertical Duct
1350(h) x 2180(v) Note 1288(h) x 2180(v) Note 650(h) x 1200(v) Note
4 SIZE 1. 1. 1.
1530 OD Duct Note 1

5 Blade/ Shaft Material A240 TP 304SS A240 TP 304SS CS CS


75mm 1260°C LI 75mm 1260°C LI
6 Refractory Castable 977kg/m3 Castable 977kg/m4
N/A N/A
6 Operating Temp. (°C) 313 313 244 11
7 Design Temp. (°C) 369 369 300 67
8 Operating Flow kg/hr 33,839 16,919 15,963 95,777
9 Design Flow kg/hr 38,915 19,457 18,357 110,144
10 Leakage Rate 0.50% 0.50% 0.50% 0.50%
11 Actuator / manual Actuator Actuator Actuator Actuator
12 Mode of Operation Control / T.S.O.Note 2 Control / T.S.O.Note 2 Control / T.S.O.Note 3 Control / T.S.O.Note 4

ACTUATOR DATA
5 ACTUATOR TYPE PNEU. PNEU. PNEU. PNEU.
6 ROT. TO OPEN See drawing See drawing See drawing See drawing
7 ACTION (Dbl Act. vs Spring) By Vendor By Vendor By Vendor By Vendor
8 FORCE (LBS) By Vendor By Vendor By Vendor By Vendor
9 TORQUE (FT/LBS) By Vendor By Vendor By Vendor By Vendor
10 OD DAMPER SHAFT See drawing See drawing See drawing See drawing
11
12 HAND WHEEL YES YES YES
13 W/ LOCK DEVISE YES YES YES
14 AIR FAIL (SIGNAL) LAST LAST LAST CLOSED
15 AIR FAIL (SUPPLY) LAST LAST LAST CLOSED
16 MATERIAL
17
18 MANUFACTURER By Vendor By Vendor By Vendor By Vendor
19 MODEL No. By Vendor By Vendor By Vendor By Vendor
20
21 AREA CLASS CLASS I DIV 2 GROUP C& D
22
23 TYPE PNEUMATIC PNEUMATIC PNEUMATIC PNEUMATIC
24 INPUT SIGNAL 4-20 MA 24VDC Compatible with Foundation Field Bus/HART
25 OUTPUT SIGNAL 4-20 MA 24VDC Compatible with Foundation Field Bus/HART
26 AIR SUPPLY MIN/NORM/MAX 4.0 kg/cm2 min/7.0 kg/cm2 normal/10.5 kg/cm2 max
27 CONNECTION Mfg. Std Mfg. Std Mfg. Std Mfg. Std
28 CONDUIT Mfg. Std Mfg. Std Mfg. Std Mfg. Std
29 AIR TUBING Stainless Steel Stainless Steel Stainless Steel Stainless Steel
30 POSITION IND YES YES YES YES
31 MOUNTING KIT If Req'd If Req'd If Req'd If Req'd
32 AIR FILTER & REG YES YES YES YES
33 GAUGES YES YES YES YES
34 3 WAY SOL VALVE YES YES YES YES
35 LIMIT SWITCHES YES YES YES YES
36 AIR RESERVIOR If Req'd If Req'd If Req'd If Req'd
37 I/P CONVERTER YES YES YES YES
Form 1196-DPR
FOSTER WHEELER USA - FIRED HEATER DIVISION
DAMPER & ACTUATOR DATA SHEET

Client: IOCL Heater Tag No.: 030-F-001, 030-F-002 Doc. No.: 1196-DPR-430
Location: Paradip Req No.: 1196REQ-430
Job No.:5-16-1196 Originator: JAK Date: April 6, 2009
Unit: Delayed Coker Heater Revision: 0 Date:

Note 1: Dimensions are to outside of steel casing


Note 2: Normal operation is control/balancing of hot flue gas exiting from three parallel heater cells. During maintenance, one heater cell at a time will be
isolated and that damper will be in TSO mode. Normal upstream pressure during TSO will be atmospheric and downstream pressure will be -203 mm H20.
Note 3: Normal operation is control/balancing of hot air for three radiant cells. During maintenance, one cell at a time will be isolated and that Damper will
be in TSO Mode. Normal upstream pressure during TSO will be 229 mm H2O, down stream pressure will be atmospheric

Note 4: Normal operation is closed in TSO Mode. During Air Preheater maintenance the damper is fully open at 95,777 kg/hr. The low flow control case is
TBD by APH Vendor.