Professional Documents
Culture Documents
Interchangeability
The ICX cutout is designed to be electrically and mechanically inter-
changeable with the S&C type “XS”, A.B. Chance type “C”, and Cooper
type “L” cutouts. Fuseholder caps are also interchangeable with the
S&C design. Testing has confirmed the performance of the ICX fuse-
holder and fuse support with S&C and Chance.
15 kV ICX
polymer concrete ICX with ECD
-2-
Options Construction Details
Silicone Rubber Fuse Tube Construction
Silicone rubber has been used for more than 25 years as an The ICX cutouts utilize two different types of fuse tubes: a
outdoor insulation material and has become the fastest moisture-proof fuse tube or a high-strength glass fuse tube.
growing choice for polymeric material for medium and high The moisture proof fuse tube is standard on all 100 A
voltage outdoor insulation. Silicone was selected for its designs and is notated by the letter "M" in the 8th digit of
superior performance, durability, and insulation properties. the style number (refer to Ordering Instructions on pages
It has the unique ability to maintain its hydrophobicity and 6-7). The moisture-proof tube reduces swelling that can
offers greater stability against heat and ultraviolet radiation create problems with interruption.
compared to other polymers. In addition, silicone cutouts
are 30% - 50% lighter than porcelain units. Silicone insula- The 200 A design utilizes a high-strength glass fuse tube
tors are available in all ratings up to 180 kV BIL. and is notated by the letter "A" in the 8th digit of the style
number (refer to Ordering Instructions on pages 6-7). This
Polymer Concrete fuse tube is composed of a horn fiber liner surrounded by
ABB has been using polymer concrete for more than 10 a glass filament wound outer shell. The durable tube with-
years. It is available in the 110 and 125 kV BIL ratings. stands the rigors of high fault current interruptions. In
Polymer concrete provides a safe, shatter-proof design with addition, the tube is applied with electrostatic powder paint
molded-in rods to prevent moisture penetration. Polymer to provide protection against the effects of ultraviolet rays.
concrete is cold weather friendly since it resists damage from
freeze/thaw cycles. This makes it an excellent replacement Voltage Levels
for porcelain in colder climates. It is a field-proven material Single voltage rated cutouts can be applied on any single or
that provides excellent electrical properties and dielectric three-phase system where the line-to-line voltage does not
strengths, as well as superior mechanical durability. exceed the cutout rating. Dual voltage rated cutouts are suit-
able on single-phase circuits where maximum line-to-ground
ICX with ECD voltage does not exceed the value shown to the right of the
The ICX is available with an Emission Control Device slash (for example, does not exceed 27 kV in 15/27 kV).
(ECD). The ECD prevents forest fires and provides added ICX cutouts may be used on three-phase circuits that are
operator and environment protection. The unlatching oper- solidly grounded and the maximum line-to-line voltage
ation of the dropout is unique in the ECD, as it automati- does not exceed the value shown to the left of the slash (for
cally resets to the service position upon closing the dropout example, does not exceed 7.8 kV in 7.8/15 kV).
carrier.
Each frame size has fault interrupting ratings at more than
Kick-out Spring one voltage level. An extensive testing program was per-
All ICX fuse tubes are available with an optional kick-out formed to develop these multi-voltage capabilities. As a
spring. The spring assists the drop-out operation by increas- result of this program, the voltage rating of some ICX
ing the kick-out force on the tube. cutouts may be increased by changing the fuseholder.
15 kV ICX
silicone
27 kV Silicone ICX
(180 kV BIL)
-3-
Unit Dimensions
7.75
[197]
C 4.12-5.12
[105-130]
1.56
[40]
FR
D
17-20 DEG
1.00
[25]
-4-
Bracket Dimensions
.312 .375
[8] [10]
7.8 7.8
[198] [198]
1.6 1.6
[40] [40]
2.6 2.6
[67] [67]
.38
[10]
7.8 9.1
[198] 12.8 [231]
[325]
1.5
[38]
5.4
[137]
6.9 2.2
[175] [56]
-5-
Ordering Instructions
ICX 15 kV
X 1
ICX 27 kV
DIGIT 2
Insulator BIL
2 = 125 kV BIL
4 = 150 kV BIL
600 mm creep
(silicone only)
DIGIT 4 DIGIT 6 DIGIT 11
5 = 150 kV BIL Terminal Connectors Special Options Additional Options
8 = 180 kV BIL N = No terminal N = None K = Kickout spring
750 mm creep on fuse tube
(silicone only) C = Clamshell F = Wildlife guard
9 = 200 kV BIL S = Seacoast design
1130 mm creep E = Eyebolt Y = Combo box silicone
(silicone only)
-6-
ICX 38 kV, 150 or 180 kV BIL
DIGIT 2
Insulator BIL
4 = 150 kV BIL DIGIT 4 DIGIT 6 DIGIT 11
600mm creep Terminal Connectors Special Options Additional Options
(silicone only)
N = No terminal N = None K = Kickout spring
5 = 150 kV BIL on fuse tube
C = Clamshell F = Wildlife guard
8 = 180 kV BIL S = Seacoast design
750mm creep E = Eyebolt Y = Combo box silicone
(silicone only)
X 7
-7-
Optional Cutout Parts
Replacement Fuseholders
Voltage Current Interrupting
Rating BIL Rating Rating Corresponding
Style Number (kV) (kV) (A) (kAIC) Cap Type Cutout*
7194C60G01MP 15 110 100 10 Solid AM11
7194C60G02MP 15 110 100 16 Link Extender LM11
7194C60G03 7.8/15 110 200 12 Link Extender PA21
7194C60G04 15 110 300 - Solid Disconnect Blade CA31
7194C60G05MP 27 125 or 150 100 8 Solid AM12
7194C60G06MP 27 125 or 150 100 12 Link Extender MM12
7194C60G07 15/27 125 or 150 200 10 Solid BA22
7194C60G08 27 125 or 150 300 - Solid Disconnect Blade DA32
7194C60G08 38 150 300 - Solid Disconnect Blade DA32
7194C60G11MP 27 170 100 12 Link Extender MM13
7194C60G12MP 38 170 300 - Solid Disconnect Blade EA33
7194C60G19 15 110 200 10 Link Extender KA21
7194C60G26 27 125 or 150 200 12 Link Extender VA22
* Used with ICX cutouts having the following characters in digit positions 7-10 of the ABB cutout style number.
Brackets
ABB Inc.
406 Banner Ave.
Greensboro, NC 27401
Tel: +1-336-275-7310