MEDIUM VOLTAGE SEPARABLE


CONNECTORS AND BUSHINGS
CATALOGUE 2020
NEXANS NETWORK SOLUTIONS DIV. EUROMOLD

COMPANY PRESENTATION

EUROMOLD International standards Laboratory accreditation


Euromold is the leading All our products meet the Since June 2000, Euromold’s
European specialised designer, International standards like independent ELAB laboratory
manufacturer and distributor of CENELEC HD 629.1, CENELEC obtained the BELAC accreditation
prefabricated cable accessories EN 50180, IEC 60137, no.144-TEST conform with
for medium voltage energy IEC 60502-4… or country the European standards for
distribution. Euromold provides a specifications. Official certificates, laboratories ISO 17025 for
complete range of accessories for CESI, KEMA, ATEX… prove the electrical testing of low and
underground cables: premoulded conformity of our products. medium voltage cable accessories
EPDM rubber connectors for Long duration tests of existing or according to the international
cables and epoxy bushings for new products are continuously standards EN 50393, IEC 60502-
transformers and switchgear, as performed in our test fields. 4, IEC 61442 and HD 629.
well as a large range of cold-
shrinkable terminations and joints
from 12 to 42 kV.
Euromold is also the manufacturer
of electrical components for the
high voltage accessories of the
Nexans group.

ISO 9001 Certificate


Since 1992, Euromold’s
commitment to quality is
demonstrated by its ISO 9001
certification.

While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility
can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or
modify the characteristics of its products described in this catalogue as standards and technology evolve.
SEPARABLE CONNECTORS AND BUSHINGS
INTERFACE D

TABLE OF CONTENTS INTERFACE D1 & D2


676LRA - tee connector Dimensions according to European
670AR-2 - equipment bushing CENELEC EN 50180 and 50181
Accessories (in mm).
Possible arrangements

In mm.

02/2020
CONNECTING POSSIBILITIES

BUSHINGS / CONNECTION CONNECTORS /


ACCESSORIES ACCESSORIES

Equipment
interface dead-ending
of equipment
(K)606DR-TPS
Dead-end receptacle

(K)670AR-2
Equipment bushing

(K)675BE 676SA (K)680CP


Bushing extender Stud Connecting plug

(K)672T1
Equipment bushing
connector standing
away from equipment
one cable to
equipment
(K)672TBC
In-air bushing

676SN
(K)680CP in-line junction Stud + nut
Connecting plug

tap-off
(K)676RTPA
Reducing tap plug 1250/250 A
(K)676LRA(/G)
Tee connector
dead-ending
(K)676BIPA
Basic insulating plug of connector

cable
(K)606SOP isolation
Stand-off plu g

cable
606GP earthing
Earthing plu g

09/2017
676LRA INTERFACE D
TEE CONNECTOR

APPLICATION TECHNICAL
Separable tee connector designed CHARACTERISTICS
to connect polymeric insulated • A thick conductive EPDM jacket
cable to equipment (transformers, provides a total safe to touch
switchgear, motors...). screen.
Also connects cable to cable, • Each separable connector is
using the appropriate mating tested for AC withstand and
part. partial discharge prior to leaving
the factory.

DESIGN 250 mm
212 mm
Separable connector
comprising: 6/10 (12) kV
1. Conductive EPDM insert. 6.35/11 (12) kV
2. Conductive EPDM jacket. 8.7/15 (17.5) kV
3. Insulating EPDM layer 12/20 (24) kV
moulded between the insert 4 9 12.7/22 (24) kV
5 6 8
and the jacket.
4. Type D - 1250 A interface 1

as described by CENELEC
Up to 24 kV - 1250 A
2
EN 50180 and 50181. 355 mm 3
5. Conductor contact.
6. Basic insulating plug
10
(with VD point).
7. Cable reducer.
8. Conductive rubber cap.
9. Threaded stud.
7
10. Earthing lead.

The screen break design


enables cable outer sheath
testing without removing or
dismantling the connector.

SPECIFICATIONS AND
STANDARDS
The separable connector 676LRA
meets the requirements of
CENELEC HD 629.1.

Separable Voltage Current Conductor sizes (mm2)


connector Um Ir
type (kV) (A) min. max.
676LRA/G 12 1250 50 630
K676LRA/G 24 1250 35 630
02/2020

4
KIT CONTENTS The kit also comprises lubricant, wipers,
installation instructions and crimp chart.
The complete (K)676LRA tee
connector kit comprises the
following components:

(K)676LRA/G-W-X
connector kit

Connector housing Threaded Conductor Basic insulating Cable reducer


(K)650BLR/G stud + nut contact plug + 611CA-W
676SN TBC-X rubber cap
(K)676BIPA

TABLE W
ORDERING INSTRUCTIONS
Select the part number Ordering Dia. over core insulation (mm)
which gives the best centring to the part number min. max.
cable core insulation diameter. 676LRA/G-15-X 16.0 22.0
Add a 'K' for use up to 24 kV. 676LRA/G-19-X 20.0 26.5
676LRA/G-22-X 23.5 31.0
676LRA/G-27-X 28.5 37.5
676LRA/G-32-X 34.0 42.5
676LRA/G-37-X 39.0 48.5
676LRA/G-43-X 45.5 56.0

TABLE X

Aluminium conductor Copper conductor


Conductor sizes
EXAMPLE: (mm2) DIN Deep DIN
The copper wire screened cable hexagonal indent hexagonal
is 24 kV, 630 mm2 stranded 35 35(K)M-12-2 35KM-12-1 35(K)M-11-2
50 50(K)M-12-2 50(K)M-12-1 50(K)M-11-2
aluminium with a diameter over
70 70(K)M-12-2 70(K)M-12-1 70(K)M-11-2
core insulation of 44.0 mm.
95 95(K)M-12-2 95(K)M-12-1 95(K)M-11-2
Order a K676LRA/G-37- 120 120(K)M-12-2 120(K)M-12-1 120(K)M-11-2
630KM-12-1 tee connector kit. 150 150(K)M-12-2 150(K)M-12-1 150(K)M-11-2
185 185(K)M-12-2 185(K)M-12-1 185(K)M-11-2
240 240(K)M-12-2 240(K)M-12-1 240(K)M-11-2
300 300(K)M-12-2 300(K)M-12-1 300(K)M-11-2
400 400(K)M-12-2 400(K)M-12-1 400(K)M-11-2
500 500(K)M-12-2 500(K)M-12-1 500(K)M-11-2
630 – 630(K)M-12-1 630(K)M-11-2

For use with For use with Alupe or For use in potentially For use with For outdoor Components can be
copper tape C 33-226 cables. explosive atmospheres other cable types. applications. ordered individually.
screened cables. Please contact our (for 12 kV max.). Please contact our Order: +MWS.
Order: Kit MT. representative. Order: -/ATEX. representative.

5
670AR-2 INTERFACE D
EQUIPMENT BUSHING

APPLICATION TECHNICAL
For use in equipment insulated CHARACTERISTICS
with oil fluid, typically for Each bushing is tested for
transformers, switchgear, AC withstand and partial
capacitors... discharge prior to leaving
the factory.

SPECIFICATIONS AND
STANDARDS 6/10 (12) kV
The bolted type equipment
bushings 670AR-2 are moulded
6,35/11 (12) kV
epoxy insulated parts and meet
130
8,7/15 (17,5) kV
the requirements of CENELEC EN
12/20 (24) kV
50180 and IEC 60137. 36
12,7/22 (24) kV
10

325
Up to 24 kV - 1250 A

ORDERING INSTRUCTIONS 140


To order the equipment bushing, Dia.
32
Minimum oil level:
specify the type. -12 kV: 40 mm
The bushings can be supplied with -24 kV: 50 mm

an earth jumper (/J) or an earth


plate (/GS). This earth connection 40
must be specified when ordering.
M16
E.g. K670AR-2/GS. Dia. 70
Dia. 100
Dia. 150

In mm.

Equipment Voltage Current


bushing Um Ir
type (kV) (A)
670AR-2 12 1250
K670AR-2 24 1250

02/2020

6
FIXINGS FOR EQUIPMENT BUSHINGS
670AR-2/GS BUSHING 670AR-2/J BUSHING

bushing interface

fixing studs

fixing flange

NF C 52-053
claw clamp F DIN 42 538
stud clamp

equipment

sealing gasket

equipment
connection

earth jumper
earth plate

BUSHING CLAMPING KIT BUSHING CLAMPING KIT


To order the bushing clamping kit, To order the bushing clamping kit
according to NFC 52-053 with DIN style fixing flange, simply
standards, simply specify: KBC - specify: KBC - RING CLAMP 3.
NFC 52-053 /400 SERIES. Contents: - 1 x fixing flange
Ø150 mm
Contents: - 4 x claw clamp NF
- 6 x stud clamp
- 1 x sealing gasket.
F DIN 42 538
- 1 x sealing gasket.

FIXING DIMENSIONS FIXING DIMENSIONS


STANDARDS NF C 52-053
French standards.

M10 or M12
M12

Min. 55 Min. 60
Max. 25 Max. 30

4 fixing
studs Dia. 105
6 fixing
studs
Dia. 105 7
Dia. 171 Dia. 171

In mm.
ACCESSORIES

APPLICATION TECHNICAL 6/10 (12) kV


For use with connectors and CHARACTERISTICS 6.35/11 (12) kV
bushings with an interface D as All these products, except the 8.7/15 (17.5) kV
described by CENELEC EN 50180 earthing plug, are tested for 12/20 (24) kV
and 50181. AC withstand and partial 12.7/22 (24) kV
discharge prior to leaving
the factory.
Up to 24 kV

606DR-TPS ORDERING INSTRUCTIONS


DEAD-END RECEPTACLE Order
Fits over a bushing with a type 606DR-TPS for 12 kV or
D interface to provide 'dead-end' K606DR-TPS for 24 kV
facility. applications.
Contains a capacitive test point The dead-end receptacle can
for checking circuit conditions. be supplied with an earth lead.
Order: -/G.
E.g. 606DR-TPS/G.

606SOP ORDERING INSTRUCTIONS


STAND-OFF PLUG Order
Is designed to support and 'dead- 606SOP for 12 kV or
end' connectors with a type D K606SOP for 24 kV
interface when removed from applications.
equipment.

606GP ORDERING INSTRUCTIONS


EARTHING PLUG Order
Is designed to support and earth 606GP for 12 or 24 kV
connectors with a type D interface applications.
when removed from equipment.

02/2020

8
675BE ORDERING
BUSHING EXTENDER INSTRUCTIONS
Provides an extension piece to Order
allow cables to stand away from 675BE for 12 kV or
equipment. K675BE for 24 kV
Is used in conjunction with the applications.
680CP connecting plug.

676BIPA ORDERING INSTRUCTIONS


BASIC INSULATING PLUG Order
Acts as a tightening nut for the 676BIPA for 12 kV or
676LRA/G tee connector kits. K676BIPA for 24 kV
The plug contains a voltage applications.
detection point.
The conductive rubber protection
cap is included.

680CP ORDERING INSTRUCTIONS


CONNECTING PLUG Order
For connecting two or more 680CP for 12 kV or
connectors with a type D interface K680CP for 24 kV
together, thus creating a separable applications.
cable joint or a multiple cable Order: -/ATEX for use in
connection to equipment. potentially explosive atmospheres
(for 12 kV max.).

676RTPA ORDERING INSTRUCTIONS


REDUCING TAP PLUG Order
Provides a type A interface to 676RTPA for 12 kV or
connectors with a type D interface. K676RTPA for 24 kV
A 'C' spanner, 600SW, is used to applications.
tighten the reducing tap plug onto Order 600SW for the 'C'
its mating part. spanner.

KIT MT ORDERING INSTRUCTIONS


EARTHING KIT FOR COPPER Order
TAPE SCREENED CABLES Kit MT for 12 kV or 24 kV
Contains a tinned copper braid applications.
(25 mm² - L = 500 mm), a tinned
copper wire for cleating and water
sealing mastic.
9
POSSIBLE ARRANGEMENTS

676LRA/G 676LRA/G-P2
Single cable arrangement. Dual cable arrangement.
Order 676LRA/G for 12 kV or Order 676LRA/G-P2 for 12 kV
K676LRA/G for 24 kV or K676LRA/G-P2 for 24 kV
applications. applications.

250 470

basic connecting basic


insulating plug insulating
plug plug

106 106 225

676LRA/G-P3 676LRA/G-P4
Triple cable arrangement. Single cable arrangement with
Order 676LRA/G-P3 for 12 kV tap-off.
or K676LRA/G-P3 for 24 kV Order 676LRA/G-P4 for 12 kV
applications. or K676LRA/G-P4 for 24 kV
applications.

695 460

connecting connecting basic tap-off


plug plug insulating plug
plug

type A
separable
connector

106 225 225 106 235 In mm.

02/2020

10
676LRA/G-P5 676LRA/G-P6
Dual cable arrangement with tap- Connector standing away from
off. equipment.
Order 676LRA/G-P5 for 12 kV Order 676LRA/G-P6 for 12 kV
or K676LRA/G-P5 for 24 kV or K676LRA/G-P6 for 24 kV
applications. applications.
690 470

connecting tap-off connecting basic


plug plug plug insulating
plug
bushing
extender
type A
separable
connector

106 225 235 331

676LRA/G-L1 676LRA/G-L3
Dead-ending. 3-way connection.
Order 676LRA/G-L1 for 12 kV Order 676LRA/G-L3 for 12 kV
or K676LRA/G-L1 for 24 kV or K676LRA/G-L3 for 24 kV
applications. applications.
285 730

basic basic basic connecting connecting basic


insulating insulating insulating plug plug insulating
plug plug plug plug

676LRA/G-L2 676LRA/G-L4
2-way connection. 4-way connection.
Order 676LRA/G-L2 for 12 kV Order 676LRA/G-L4 for 12 kV
or K676LRA/G-L2 for 24 kV or K676LRA/G-L4 for 24 kV
applications. applications.
505 955

basic connecting basic basic connecting connecting connecting basic


insulating plug insulating insulating plug plug plug insulating
plug plug plug plug

11

In mm.
676LRA/G-L5 676LRA/G-L6
2-way connection with tap-off. 3-way connection with two
Order 676LRA/G-L5 for 12 kV tap-offs.
or K676LRA/G-L5 for 24 kV Order 676LRA/G-L6 for 12 kV
applications. or K676LRA/G-L6 for 24 kV
applications.
500 710

basic tap-off tap-off tap-off


insulating plug plug plug
plug

type A type A type A


separable separable separable
connector connector connector

676LRA/G-L7
3-way connection with one tap-off.
Order 676LRA/G-L7 for 12 kV
or K676LRA/G-L7 for 24 kV
applications.

725

basic connecting tap-off


insulating plug
plu g plug
plug

type A
separable
connector

676LRA/G-L8
4-way connection with two 935
tap-offs.
Order 676LRA/G-L8 for 12 kV
or K676LRA/G-L8 for 24 kV
applications. tap-off connecting tap-off
plug plug plug

type A type A
separable separable
connector connector

In mm.
12

02/2020
676LRA/G-L9
4-way connection with one tap-off.
Order 676LRA/G-L9 for 12 kV
or K676LRA/G-L9 for 24 kV
applications.

945

basic connecting connecting tap-off


insulating plug plug plug
plug

type A
separable
connector

CONNECTOR ON STAND- CONNECTOR ON EARTHING


OFF PLUG PLUG
Order 606SOP for 12 kV or Order 606GP for 12 kV and
K606SOP for 24 kV applications. 24 kV applications.

basic basic
insulating insulating
stand-off earthing
plug plug
plug plug

In mm.

13
NOTES

02/2020

14
15
16

02/2020
Nexans Network Solutions N.V. - Div. Euromold
Zuid III, Industrielaan 12, B-9320 Erembodegem
Tel.: +32(0)53 85 02 11 • sales.euromold@nexans.com • www.euromold.be