www.hilti.com Profis Anchor 2.7.

1
Company: JPT Page: 1
Specifier: Project: Jade Hills - RSKU
Address: Sub-Project I Pos. No.: Lifting Hook Alt -4
Phone I Fax: | Date: 28/11/2016
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 200-R + HIT-V-F (8.8) M10
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,opti = 90 mm (hef,limit = 120 mm)
Material: 8.8
Evaluation Service Report: ETA 12/0084
Issued I Valid: 15/4/2015 | 15/4/2020
Proof: Engineering judgement SOFA BOND - based on ETAG BOND testing
Stand-off installation: eb = 0 mm (no stand-off); t = 14 mm
Anchor plate: lx x ly x t = 580 mm x 160 mm x 14 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: uncracked concrete, C25/30, fc = 30.00 N/mm2; h = 150 mm, Temp. short/long: 30/30 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: JPT Page: 2
Specifier: Project: Jade Hills - RSKU
Address: Sub-Project I Pos. No.: Lifting Hook Alt -4
Phone I Fax: | Date: 28/11/2016
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 2 Compression 3 4
1 0.358 3.125 0.000 -3.125
2 0.358 3.125 0.000 -3.125 x
3 0.358 3.125 0.000 -3.125 5 6 7 8
Tension
4 0.358 3.125 0.000 -3.125
5 6.705 3.125 0.000 -3.125
6 6.705 3.125 0.000 -3.125
7 6.705 3.125 0.000 -3.125
8 6.705 3.125 0.000 -3.125
max. concrete compressive strain: 0.13 [‰]
max. concrete compressive stress: 4.00 [N/mm2]
resulting tension force in (x/y)=(0/-45): 28.250 [kN]
resulting compression force in (x/y)=(0/72): 28.250 [kN]

3 Tension load (EOTA TR 029, Section 5.2.2)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 6.705 30.667 22 OK
Combined pullout-concrete cone failure** 28.250 62.780 45 OK
Concrete Breakout Strength** 28.250 64.431 44 OK
Splitting failure** 28.250 71.168 40 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
46.000 1.500 30.667 6.705

3.2 Combined pullout-concrete cone failure


Ap,N [mm2] A0p,N [mm2] 2
t Rk,ucr,25 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm]
229400 72900 15.00 270 135 75
2 0
yc t Rk,ucr [N/mm ] k y g,Np y g,Np
1.020 15.30 3.200 1.214 1.064
ec1,N [mm] y ec1,Np ec2,N [mm] y ec2,Np y s,Np y re,Np
0 1.000 45 0.750 0.867 1.000
N0Rk,p [kN] NRk,p [kN] gM,p NRd,p [kN] NSd [kN]
43.271 94.170 1.500 62.780 28.250

3.3 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm]
229400 72900 135 270
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 45 0.750 0.867 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
10.100 47.233 1.500 64.431 28.250

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: JPT Page: 3
Specifier: Project: Jade Hills - RSKU
Address: Sub-Project I Pos. No.: Lifting Hook Alt -4
Phone I Fax: | Date: 28/11/2016
E-Mail:

3.4 Splitting failure


Ac,N [mm2] A0c,N [mm2] ccr,sp [mm] scr,sp [mm] y h,sp
247544 82944 144 288 1.160
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1
0 1.000 45 0.762 0.856 1.000 10.100
N0Rk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
47.233 1.500 71.168 28.250

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: JPT Page: 4
Specifier: Project: Jade Hills - RSKU
Address: Sub-Project I Pos. No.: Lifting Hook Alt -4
Phone I Fax: | Date: 28/11/2016
E-Mail:

4 Shear load (EOTA TR 029, Section 5.2.3)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 3.125 18.400 17 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 25.000 167.351 15 OK
Concrete edge failure in direction y-** 25.000 31.884 79 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
23.000 1.250 18.400 3.125

4.2 Pryout Strength (Bond Strength controls)


Ap,N [mm2] A0p,N [mm2] 2
t Rk,ucr,25 [N/mm ] ccr,Np [mm] scr,Np [mm] cmin [mm]
229400 72900 15.00 135 270 75
2 0
yc t Rk,ucr [N/mm ] k4 k-factor y g,Np y g,Np
1.020 15.30 3.200 2.000 1.214 1.064
y s,Np ec1,V [mm] y ec1,Np ec2,V [mm] y ec2,Np y re,Np
0.867 0 1.000 0 1.000 1.000
N0Rk,p [kN] NRk,p [kN] gM,c,p VRd,cp [kN] VSd [kN]
43.271 125.514 1.500 167.351 25.000

4.3 Concrete edge failure in direction y-


lf [mm] dnom [mm] k1 a b
90 10.0 2.400 0.110 0.067
c1 [mm] Ac,V [mm2] A0c,V [mm2]
75 81563 25313
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V
1.000 1.000 1.000 0 1.000 1.000
V0Rk,c [kN] gM,c VRd,c [kN] VSd [kN]
14.843 1.500 31.884 25.000

5 Combined tension and shear loads (EOTA TR 029, Section 5.2.4)

bN bV a Utilization bN,V [%] Status


0.450 0.784 1.500 100 OK

baN + baV ≤ 1

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: JPT Page: 5
Specifier: Project: Jade Hills - RSKU
Address: Sub-Project I Pos. No.: Lifting Hook Alt -4
Phone I Fax: | Date: 28/11/2016
E-Mail:

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 4.966 [kN] dN = 0.070 [mm]
VSk = 4.630 [kN] dV = 0.278 [mm]
dNV = 0.287 [mm]
Long term loading:
NSk = 4.966 [kN] dN = 0.088 [mm]
VSk = 4.630 [kN] dV = 0.370 [mm]
dNV = 0.381 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Bore hole cleaning must be performed according to instructions for use (blow 4 times with the hand pump, brush 4 times, blow again 4 times
with the hand pump).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• An SLS-check is not performed for SOFA and has to be provided by the user!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: JPT Page: 6
Specifier: Project: Jade Hills - RSKU
Address: Sub-Project I Pos. No.: Lifting Hook Alt -4
Phone I Fax: | Date: 28/11/2016
E-Mail:

8 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200-R + HIT-V-F (8.8) M10
Profile: no profile Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 14 mm Hole depth in the base material: 90 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 120 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Dispenser including cassette and mixer
• Properly sized drill bit • Proper diameter wire brush • Seismic/Filling set
• Torque wrench

290 290

30
1 2 3 4

80
100

80
5 6 7 8 30

40 100 300 100 40

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 -250 50 150 2324 175 2065 5 -250 -50 150 2324 75 2165
2 -150 50 250 2224 175 2065 6 -150 -50 250 2224 75 2165
3 150 50 550 1924 175 2065 7 150 -50 550 1924 75 2165
4 250 50 650 1824 175 2065 8 250 -50 650 1824 75 2165
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: JPT Page: 7
Specifier: Project: Jade Hills - RSKU
Address: Sub-Project I Pos. No.: Lifting Hook Alt -4
Phone I Fax: | Date: 28/11/2016
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

You might also like