TECHNICAL INFORMATION

pulse valves
for dust collector systems

1 8 9 10
TECHNICAL INFORMATION 1) Compressed air jet
ON PULSE VALVES 2
2) Clean air exhaust
11
3) Filter housing
ASCO Numatics has a comprehensive 4) Filter bag
range of pulse valves for the dust control 12
5) Dirty air intake
market with accessories to sense the pres-
13 6) Dust collector hopper
sure drop across the fabric and to control
the pulse sequence. 7) Dust lock
3 14
Since the valve performance has great 8) Secondary air
influence on the cleaning efficiency of the 4 15 9) Supply air
generated air pulse, this aspect in particular 10) Pressure switch
is highlighted in this section. 11) Dust collector valve
5
12) (Auxiliary) air control pipe
Diaphragm Pulse valves 6
13) Valve block
The construction of the ASCO 2-way dia- 14) Solid state sequential controller
phragm pulse valves is based on the proven 7 15) Filter cage (shown without filter bag)
fact that fast opening and closing of the
valve is of great importance for effective
cleaning of the filter fabric and economical in the filter is reached when the air veloc- neath the piston instead of over a wall as in
air consumption. ity becomes sonic (344 m/s); this situation the conventional pulse valve. This creates
By keeping the weight of the moving parts in occurs at the critical pressure drop. For air less of a restriction to the flow (fig. 2). An-
the valves as low as possible, the response this condition is reached when the abso- other advantage is that the venturi shape of
times are, thanks to the low inertia, very lute downstream pressure is 52,8% of the the valve outlet increases air speed.
short and result in opening times between absolute upstream pressure. In addition to the flow, the peak pressure
8 and 14 milliseconds. The diaphragm The standard valve bodies have threaded is positively influenced. Laboratory tests
assembly used in the ASCO pulse valves pipe connections according to ISO 228/1. show a 20% improvement.
is a low mass construction compared to The valves are either integral solenoid pilot
what is normal practice in this industry. At operated or remote pilot operated. Fully immersed piston valves
the same time the strength and endurance Solenoid pilot controlled types are standard
of the used nylon reinforced Neoprene equipped with epoxy moulded spade plug Due to the Pressure Equipment Direc-
or Hytrel sheet-material diaphragms are connection coils. Stainless steel waterproof tive 97/23/EC, which contains pressure
extremely good. enclosures (IP 67) and ATEX (CENELEC), equipment operating above 0.5 bar and
The main diaphragm is clamped between IECEx, NEMA explosionproof solenoids manufactured or traded within the Euro-
valve bonnet and body in a special patented are available as an option. Other options pean Union, filter builders more and more
way which forces the diaphragm to seal available are NPT or ISO 7/1 pipe threads, prefer to buy complete assembled pressure
the valve seat without the use of strong brass bodies for mining applications (spar- header tanks.
closing springs, thus preventing the flutter kless) and epoxy coating for corrosive Besides this regulation also other factors
phenomenon which is very common in other environments. enable true “one stop shopping":
high flow diaphragm pulse valves. - One supplier supplies and guarantees
Flluttering of the diaphragm during opening Piston Pulse valves the complete system
- Simplified stocking and purchasing
Availability, design and specifications are subject to change without notice. All rights reserved.
and closing of the valve will affect the valve
performance dramatically and increases air The main requirements of pulse valves for process
consumption. the dust collection market are low cost, - Tank system with full-immersed valve
superior operating characteristics, long life has an increased flow performance
and ease of installation & maintenance.
In order to improve the present offer, a new To meet these market demands, a revolu-
piston concept, the power pulse valve was tionairy Power Pulse Tank System with fully
developed to meet these market require- immersed valves has been introduced,
ments. based on the proven Power Pulse valve
An integral component in producing this new technology. In the case of the full-immersed
flow concept is a unique one-piece patented valves, the air enters the valve from all
Hytrel piston/diaphragm construction. This directions (see fig. 3).
fig. 1 combination allows the flow to travel under-

The high flow, angle type aluminium bodied


valves in combination with the special main
diaphragm assemblies give the unique
operating characteristics required for this
application.
X003GB-2009/R8

This higher flow is expressed in a very high


Kv factor for each valve (fig. 1).
The maximum flow through the blow pipe(s) fig. 2 fig. 3

All leaflets are available on: www.asconumatics.eu


X003-58
TECHNICAL INFORMATION SECTION
In the adapter the flow is optimal guided by turer, the tank type and the size of the pipe ● Opening time to 50% Pp [ms]:
the patented venturi concept, resulting in a connection. Below the heading of the graph This is the elapsed time from zero until
higher peak pressure. the following data is provided: 50% of the peak pressure has been
The sine wave is the electrical signal and reached. The quicker the opening time,
Accessories for pulse valve further two pressure signals are shown. the higher the acceleration of air for
control The upper signal shows the pressure in the better cleaning.
supply tank and the lower signal shows the ● Closing time from 50% Pp [ms]:

Pulse valves are vital parts in dust col- pressure of the shock wave generated by the This is the elapsed time from 50% of the
lector systems but only one of the many pulse valve which is registrated at the peak pressure measured on the down
components necessary to build a complete end of the blow pipe. stream slope until the valve is completely
system. closed.

MANUFACTURER : ASCO CONTROLS

TANK TYPE : E355AN04


Electrical PIPE SIZE : 1"
signal

Tank volume : 24 dm3

Tank pressure : 6 barg

Compressed air Electrical pulse length : 60 msec.


tank pressure Total pulse length : 81 msec.

Peak pressure : 4.6 barg

Opening time - 50% pp : 1.9 msec.

Closing time - 50% pp : 6.5 msec.


Blow pipe filter
Pressure drop tank : 1.9 bard.
pressure
Performance ratio : 76.7%

Volume per pulse : 45.2Ndm3


fig. 4

Additional accessories available from DEFINITIONS ● Pressure drop tank [bar]:


ASCO Numatics are solenoid pilot valves This is the difference between the tank
for remote control, both as single valve or ● Tank volume [dm3]: pressure before and after the shot.
grouped in pilot boxes for large filter units, This is the amount of air volume stored in With this value it is possible to calculate
electronic timers to control the solenoid the supply tank. (Tank volume depends the air consumption of the valve per pulse
operators and pressure switches to sense on valve size). (volume per pulse).
the air tank pressure or the pressure dif- ● Performance ratio [%]:
● Tank pressure [barg]:

ferential across the filters. The pilot valve This is the air pressure in the supply tank This is the ratio between tank pres-
boxes can house 2 up to 12 solenoid which is given in gauge pressure. sure and peak pressure multiplied by
valves protected by a dust and waterproof This is also the pressure to which the 100%.
aluminium enclosure (IEC 144, IP 65) ● Volume per pulse [Ndm ]:
3
Availability, design and specifications are subject to change without notice. All rights reserved.

valve is subjected.
and are available with a heating device ● Max. allowable pressure (PS)[barg]:
This is the amount of air at atmospheric
for low ambient temperature conditions pressure passing through the valve for
The line or system pressure to which
(down to -40°C). a given pulse time.
the equipment may be subjected without
To fulfill the timer function in the filter The greater the volume per pulse the
being damaged.
cleaning process, ASCO has a solid state better the filter bags are cleaned and
● Electrical pulse length [ms]:
sequential controller with adjustable im- more bags could be cleaned per valve.
pulses and interval signals to control the This is the energized time of the valve.
solenoid operators. (The wave length of a 50 Hz alternating
Using figures for comparison and
current is 20ms for a full wave). selection
● Total pulse length [ms]:
INTERPRETATION OF THE FIGURES
This is the time from the moment the valve To compare graphs of different valve makes
The data sheet of ASCO pulse valves is opens until the valve is fully closed. and/or types of pulse valves the following is
● Peak pressure [barg]:
divided into two parts; the left side shows essential: it is preferable to have the graphs
the graphical presentation of the test data This is the maximum pressure which is made by identical electronic measurement
and on the right all the numeric data can measured at the end of the blow pipe equipment since a slight difference in sen-
be found (fig. 4). usually scaled at the end of the first slope sitivity and accuracy of the components can
The graph shows the following information: of the graph (after the valve has opened make a fair difference in the results.
The x-axis represents the elapsed time and completely).This creates the shock wave The other basic test conditions and set
X003GB-2009/R8

the y-axis represents the electrical and the down the filter bags for cleaning. up must be equal too. The most impor-
pressure signals. tant parameters which have to be exactly
The table states the name of the manufac- identical are:

All leaflets are available on: www.asconumatics.eu


X003-59
TECHNICAL INFORMATION SECTION
Tank volume and pressure
● 7. The number of valves on the tank ing response times of the valve increase
8. The capacity of the compressor with the length and size of the tubing of
Electrical pulse length/Total pulse
● the pilot valve (the opening response
length The most common method to determine time is the time elapsed after the begin of
the tank volume is to experiment at which the electrical signal and the moment the
Fittings from supply tank to valve and

minimum tank volume at a certain pulse valve starts to open, the closing response
from valve to the blow pipe
time you achieve a square shock wave and time is the time elapsed after the end of
the best cleaning effect. the electrical signal until the valve is fully
Size of the blow pipe and the number

closed). The best way to estimate the
and location of the blow pipe holes
To make a rough calculation of the capacity electrical pulse length is to experiment
of the supply tank, the below mentioned since there is no other practical method.
● Location and position of the pressure
method can be used: An electrical pulse time of 60 ms (for direct
transducer(s)
operated valves) in most cases is sufficient
(distance from the valve and radial or
To maintain sonic flow conditions in the for correct operation that is: achieve maxi-
axial mounted on the air stream)
blow pipe(s) it is necessary to choose the mum opening of the valve and reach the
Since there are so many parameters to take product of the tank volume and the absolute best possible peak pressure
into account, the most reliable method to tank pressure (= gauge pressure +1 bar) at
compare the test results is when they are least twice the required volume per pulse, ● Total pulse length:
made under the same test conditions, so this will also allow a maximum pressure The total pulse length depends on the
with the same equipment. tank pressure. electrical pulse length as described ear-
2.Vp lier and the opening and closing times.
Besides the performance and price level In a formula: Vt ≥ —— Together they are responsible for the air
of the pulse valve, several other important Pu consumption or volume per pulse of the
parameters are essential, such as: valve.
Vt = Tank volume [dm3]
Vp = Volume per pulse [Ndm3] Peak pressure:
● Installation dimensions ●
Pu = Absolute upstream pressure [bara] The peak pressure is an important
(Absolute tank pressure) figure to improve cleaning efficiency at
● Minimum and maximum operation
pressure minimum air consumption.
● Tank pressure:
The tank pressure is usually set at 0,5 It depends in the first place on the tank
Service life time

to 8 barg and depends on the type and pressure but also on the construction of
construction of the filter units. the valve; a short opening time provides
Internal and external leakage

high peak pressures. Of course the valve
The system is often connected to an must also have sufficient flow capacity
Installation possibility of silencers in
existing line pressure of 6 or 8 bar and

vent port(s) (Kv) to allow pressure build up in the


reduced to the required pressure. blow pipe.
Calculation and determination of the
For direct pulse valve systems the tank Opening time:
parameters ●

pressure usually is 0,5 to 3 barg. The opening time of the pulse valve must
First we have to divide the different param- be as short as possible to achieve best
For reverse air-jet systems the pressure performance.
eters into those we can fix or influence and
mostly is 6 to 8 barg. To achieve quick opening times, air must
those which are depending on the settings
be exhausted very quickly to allow line
of the equipment.
Availability, design and specifications are subject to change without notice. All rights reserved.
The tank pressure is also proportional pressure to act against the bottomside of
responsible for the height of the peak the diaphragm, opening the main orifice.
Note that the calculation examples
pressure. Keeping the moving parts as light as
are based on sonic flow conditions
(air flow velocity = 344 m/s) without possible (low inertia) will result in short
● Electrical pulse length: opening times.
friction losses and under isothermal
The electrical pulse length is usually
conditions.
set at 40 to 200 ms and is also mainly ● Closing time:
responsible for the total pulse length and It is preferable that the closing time of
● Tank volume:
thus the amount of air passing through the valve is as short as possible, since a
The determination of the tank volume
the valve. long closing time of the valve increases
depends on several conditions:
1. The required volume air per pulse to air consumption.
A minimum electrical pulse length is The extra flow air has a negligible contri-
clean the dust filter(s) (depends on type,
required to operate the pulse valve bution to the cleaning effect of the total
size and construction of the filter unit)
correctly and depends on the type, con- air pulse and is therefore not efficient.
2. The tank pressure and the desired
struction and size of the valve. The tank
peak pressure
pressure can also influence the required Pressure drop tank:
3. The size of the valve (Kv value) ●

electrical pulse length. The pressure drop in the supply tank


4. The size of the blow pipe and the size
and number of the blow holes is the result of the amount of air which
For remote controlled pulse valves, the
X003GB-2009/R8

5. The number of pulses per time unit has passed through the valve after one
length and size of the tubing is of great pulse and depends on the following
6. The duration of the electrical pulse
influence too because opening and clos- parameters:
and the total pulse time

All leaflets are available on: www.asconumatics.eu


X003-60
TECHNICAL INFORMATION SECTION
a. Kv value of the valve In a formula: Kv = Flow factor [m3/h]
b. Electrical pulse time and total pulse 2,1 = Dimension factor (3,97.0,528)
length
c. Tank volume and tank pressure Pd = Differential pressure [bar] Instead of using the volume per pulse
d. KV value blowpipe you can also use the volume per second
To calculate the volume per pulse at value Vs, this is more accurate since
As stated before, to maintain sonic flow a certain valve and at a certain pulse opening and closing effects of the valve
in the blow pipe(s) it is necessary to limit length, the equation mentioned below have been eliminated.
the pressure drop to maximum 50% of can be used. You have to take into ac-
the absolute tank pressure. count that the calculated value is only
In a given installation it is the easiest the amount of air which is supplied by
way to reduce the electrical pulse time the tank. Vs = Volume per second [dm3/s]
if the pressure drop is too high. The air that will clean the dust filter
● Performance ratio: depends on several other things e.g. ● Average volume per s:
The performance ratio is a figure to the distance from the blow holes to the The average volume per second at a
compare pulse valves under the same filters and the use and shape of venturies certain upstream pressure (tank pres-
test conditions. which will draw secondary air into the sure) can be calculated by taking the
The size of the percentage depends on filter increasing the amount of cleaning quotient of the volume per pulse and
the Kv value of the valve and the opening air. the total pulse length.
time, both are responsible for the peak
pressure. In a formula:


C = Flow factor [dm3/s.bar]

0,528 = Critical pressure ratio to obtain
Pr = Performance ratio Avs = Average volume per s [Nm3/s]
sonic or choked flow
Pp = Peak pressure Tpl = Total pulse length [ms] This figure indicates the flow capacity
Pt = Tank pressure Pu = absolute upstream pressure in relation with the opening and closing
[bar] times of the valve. In other words, a valve
Volume per pulse: C = 3,97.Kv with a high flow capacity has a relatively

The volume per pulse can be determined C = 3,39.Cv high Avs value.
as follows:
multiply the tank volume by the differ- Kv value:
● However, long closing and/or opening
ential of the tank pressure before and With the same equation we can calculate times will reduce the Avs value, espe-
after the shot; this is the (atmospheric) the required Kv value: cially at shorter total pulse length.
amount of air which has passed through
On the other hand, short opening and
the valve.
closing times can compensate a lower
flow capacity.

TEST SET-UP
220V/50Hz
230V/50Hz
8 Blowpipe 4
Availability, design and specifications are subject to change without notice. All rights reserved.

PT

Air supply PT

7 1 2 3
5
PI
Water supply

LI

Drain

Equipment used: 1) Digital memo oscilloscope 5) Demodulator/carrier/transmitter/amplifier


X003GB-2009/R8

2) Busconverter parallel 6) Pressure transducer


3) Digital plotter 7) Pressure indicator
4) Pressure transducer 8) Adjustable time triggering device

All leaflets are available on: www.asconumatics.eu


X003-61