You are on page 1of 7

Selection of arrester

Simplified selection procedure


For a detailed Selection Guide, please The selection is carried out in two major
refer to ABB publications PTHVP/A steps:
2300E and PTHVP/A 2310E. • Matching the electrical characteristics
The catalogues list the available of the arresters to the system’s electri-
standard arresters from ABB of por- cal demands
celain-housed arresters type EXLIM • Matching the mechanical characte-
ristics of the arresters to the system’s
and silicone polymer-housed arresters,
mechanical and environmental require-
type PEXLIM.
ments.
The final selection is reflected in the arres-
ter type designation.

Vocabulary

Um Maximum system voltage k Earth fault factor

Uc Continuous operating voltage Ups Switching impulse protective level

Ur Rated voltage Upl Lightning impulse protective level

TOV Temporary overvoltage Uws Switching impulse withstand level

T TOV strength factor Uwl Lightning impulse withstand level

ABB Surge Arresters — Buyer’s Guide Edition 4, 2003-10 C-1


Selection of arrester

Flowchart for simplified selection


of surge arresters

C-2 Edition 4, 2003-10 ABB Surge Arresters — Buyer’s Guide


Selection of arrester

Matching the electrical characteristics


Arrester rated voltage (Ur) System Fault System Min. Rated
For each system voltage, the tables ”Gua- Earthing Dura- Voltage Voltage, Ur
tion Um (kV) (kV)
ranteed protective data” show a range of
Effective ≤1s ≤ 100 ≥ 0.8 x Um
Ur and maximum continuous operating
Effective ≤1s ≥ 123 ≥ 0.72 x Um
voltages Uc, all of which are capable of
Non-effective ≤ 10 s ≤ 170 ≥ 0.91 x Um
withstanding the actual continuous ope- ≥ 0.93 x Um
rating voltage (Uca) with sufficient margin. (EXLIM T)
Hence, the selection of Ur is only a func- Non-effective ≤2h ≤ 170 ≥ 1.11 x Um
tion of the applied temporary overvolta- Non-effective >2h ≤ 170 ≥ 1.25 x Um
ges, TOV, (Utov), taking into account their Table 1.
amplitudes and duration. The table gives a minimum value of the arrester
TOV are long-duration, mostly power- rated voltage (Ur). In each case, choose the next
higher standard rating as given in the catalogue.
frequency (p.f.) or nearly p.f. voltages,
with or without harmonics, generated
Note: Do not select a lower value of
by system events. The arresters must
Ur than obtained as above unless the
withstand the heat energy generated by
parameters are known more exactly;
them.
otherwise the arrester may be over-
Most commonly, a single or two-phase
stressed by TOV.
earth fault leads to a TOV in the healthy
phase(s) and also in the neutral of Y-
connected transformers. Its amplitude Energy capability & line
is determined by the system earthing discharge class
conditions and its duration by the fault- IEC classifies arresters by their nominal
clearance time. discharge current. For 10 and 20 kA arres-
If the earth-fault factor, (k) = Utov/Uca, ters, they are also classified by energy capa-
is 1.4 or less, the system is considered bility expressed as line discharge class (2
to be effectively earthed. Generally, this to 5) verified in a long duration current test
implies a solid connection of the neutral to and a switching surge operating duty test.
the earth grid. All other forms of earthing In the latter, the arrester is subjected to two
via an impedance or a non-earthing of the impulses of a given amplitude and dura-
neutral is considered as non-effective with tion after which it must be thermally stable
k = 1.73 against Uc. The ”class” figure roughly gives
For effectively earthed systems, the fault- the expected energy absorbed in
clearance time is generally under 1 s but it kJ/kV (Ur) per impulse. As seen in Table 2,
can vary widely among different systems. the ABB arresters are tested for a much
The catalogues list the values of TOV higher energy absorption capability.
capability for 1 and 10 s duration after
a prior energy stress (as a conservative Arrester Line Energy Normal
Type discharge capability application
approach). For other durations or for spe- class (2 impulses) range (Um)
cific TOV conditions, follow the procedure kJ/kV (Ur)
hereunder: EXLIM R 2 5.0 ≤ 170 kV
PEXLIM R 2 5.1 ≤ 170 kV
• Consider each TOV separately. EXLIM Q 3 7.8 170 - 420 kV
• From the TOV curves, read off the TOV PEXLIM Q 3 7.8 170 - 420 kV
strength factor (T) for the time cor- EXLIM P 4 10.8 362 - 550 kV
PEXLIM P 4 12 362 - 550 kV
responding to the fault-clearance time. HS PEXLIM P 4 10.5 362 - 550 kV
• Utov/T gives the min. value of Ur for EXLIM T 5 15.4 420 - 800 kV
withstanding this TOV. Choose the next HS PEXLIM T 5 15.4 420 - 800 kV

higher standard rating. Table 2.


• The final choice of Ur will be the hig- Energy capability of ABB arresters: The normal
hest of the Ur values obtained from the application range is only a guide. Arresters for
higher class may be required depending on the
above calculations for each TOV. specific parameters.

ABB Surge Arresters — Buyer’s Guide Edition 4, 2003-10 C-3


Selection of arrester

Matching the electrical characteristics


Though the energy capability is mentioned Note! ANSI standards refer to Uwl as BIL
in a different manner in ANSI, the normal and Uws as BSL.
range of application as above applies
even for ANSI systems. Margins are normally excellent due
For specific and special cases, e.g. to the low Upl, Ups and also that most
capacitor banks, it may be necessary to equipment at present have a high Uwl and
calculate the energy capability as shown Uws. However, depending on the electrical
in the IEC 60099-5 and other guides, e.g. distance between the arrester and the
publication PTHVP/A 2312en. protected equipment, the Upl margin is
reduced and thus arresters fail to protect
Protection levels (Upl and Ups) equipment that is not in the close vicinity
For insulation co-ordination purposes, of the arresters (i.e. within their protection
consider the lightning impulse protection zone). The flexible erection alternatives
level (Upl) at 10 kA for Um ≤ 362 kV and for PEXLIM arresters may be of benefit in
at 20 kA for higher voltages. Similarly, the reducing the distance effects. Additional
switching impulse protection levels (Ups) line-entrance arresters may help too. For
for co-ordination purposes range from 0.5 more detailed information regarding this,
kA (for Um ≤ 170 kV) to 2 kA (for Um ≥ 362 please refer to publications PTHVP/A
kV). The values can be read-off from the 2310E and PTHVP/A 2120en.
catalogue tables or easily computed from
Table 3. In the latter case, they must be Note! The ”distance effect” reduction
rounded upwards. does not apply to Ups margin since the
front-time of a switching surge impulse
Arrester Nom. Upl/Ur Upl/Ur Ups/Ur is longer.
Type Dis- at at
charge 10 20
current kAp kAp It is recommended that the protection
(In) margins (after taking into account the
EXLIM R 10 2.590 2.060 at 0.5 kAp ”distance effect”) should be of the order of
PEXLIM R 10 2.590 2.060 at 0.5 kAp 20% or more to account for uncertainties
EXLIM Q 10 2.350 1.981 at 1.0 kAp and possible reduction in the withstand
PEXLIM Q 10 2.350 1.981 at 1.0 kAp
values of the protected equipment with
EXLIM P 20 2.275 2.5 2.020 at 2.0 kAp
age.
PEXLIM P 20 2.275 2.5 2.020 at 2.0 kAp
Should the selected arrester type not
HS PEXLIM P 20 2.275 2.5 2.020 at 2.0kAp
EXLIM T 20 2.200 2.4 1.976 at 2.0 kAp
give the desired protection margins, the
selection should be changed to an arres-
Table 3.
Upl and Ups ratios for ABB arresters ter of a higher line discharge class, which
automatically leads to lower Upl.
Protection margins
Protection margins (in %), calculated at Note! Do NOT use a lower-than selected
co-ordinating impulse currents as per (Ur) to attempt improve the margins, as
Table 3, are defined as follows: this may lead to unacceptably low TOV
• Margin for lightning impulses = capability.
((Uwl/Upl)-1) x 100, where Uwl is the
external insulation withstand of the As an additional assistance in selection,
equipment against lightning impulses. please refer to the simplified flow chart at
• Margin for switching impulses = ((Uws/ the beginning of this chapter.
Ups)-1) x 100 where Uws is the exter-
nal insulation withstand of the equip-
ment for switching impulses.

C-4 Edition 4, 2003-10 ABB Surge Arresters — Buyer’s Guide


Selection of arrester

Matching the mechanical characteristics


The varistor column must be suitably to reduce the static loading. Suspending
housed to withstand long-term effects of PEXLIM arresters further reduces the
the system loading and the environmental static terminal loading and allows PEXLIM
stresses. arresters to also be chosen for higher
voltages without mechanical problems.
External creepage distance For short arresters, the mechanical
IEC 60815 defines the minimum creepage strength of PEXLIM approximately equals
distances for different environmental that for EXLIM. For longer arresters, the
conditions. Select the housing to give the lower mechanical strength of PEXLIM arres-
desired creepage - the same as for the ters can be compensated by using suspen-
other equipment in the same location. If ded or under-hung erection or by special
the creepage demand exceeds 31 mm/kV, bracing for upright erection. For details,
please refer to ABB for a special design. refer to publication PTHVP/A 2120en.

Mechanical test of sili-


cone-housed arrester
PEXLIM P.

PEXLIM arresters, having a highly Arrester Cantilever strength (Nm) MPDSL - Maximum
hydrophobic housing, are better suited type
MPDSL PSSL DPSSL permissible dynamic
for extremely polluted areas than EXLIM EXLIM R-C 7 500 3 000 n.a.
service load.
arresters and a lower creepage may be EXLIM Q-D 18 000 7 200 n.a.
justified in many cases. EXLIM Q-E 7 500 3 000 n.a. PSSL - Permissible
EXLIM P-G 18 000 7 200 n.a. static service load
Mechanical strength EXLIM T-B 18 000 7 200 n.a. (for PEXLIM arresters
The maximum useable static and permis- PEXLIM R-Y 1 600 n.a. 1 000 this is a declared
PEXLIM Q-X 4 000 n.a. 2 500
sible cantilever loading is shown in the rele- value based on cyclic
PEXLIM P-X 4 000 n.a. 2 500
vant catalogues and summarised in Table 4. HS PEXLIM P 28 000 n.a. 19 000 loading).
Since arresters do not carry any large HS PEXLIM T 28 000 n.a. 19 000
continuous current, they should be Table 4. DPSSL - Declared
provided with lighter leads and clamps Permissible strength loading for ABB arresters permissible static
service load.

ABB Surge Arresters — Buyer’s Guide Edition 4, 2003-10 C-5


Selection of arrester

Simplified selection procedure


Neutral-ground arresters Special applications
For neutral-ground arresters the recom- Please consult your nearest ABB repre-
mended rated voltage is approximately sentative for help in selection of arresters
the maximum system voltage divided by for special applications such as protection
√3. The recommended neutral-ground of shunt or series capacitor banks, cables
arresters in the relevant sections are and cable-aerial junctions, rotating machi-
calculated for unearthed systems with nes, traction systems, overhead lines,
relatively long fault duration. The electrical HVDC etc. or for non-standard arrester
characteristics are identical to standard ratings.
catalogue arresters with the correspon-
ding rated voltage. For such arresters, Ordering data for arresters
Uc is zero and they are not subject to The following information, at a minimum,
any voltage stress during normal service is required with your order:
conditions. The neutral-ground arresters • Quantity and type designation
should preferably be of the same type as • Rated voltage
the phase-ground arresters. For resonant- • Type of line terminal
earthed systems with long radial lines • Type of earth terminal
special considerations must be taken. A • Type of surge counter, if any
higher rated voltage (20% to 40%) than • Type of insulating base, if any.
listed may be necessary. (Insulating base is required if surge counter
and/or leakage current measurements
Type designation are desired. One base is required for
The type designation itself gives detailed each arrester).
information of the arrester and its applica-
tion. See the figure below. As standard,
the arresters are meant for upright vertical Ordering example
erection. For under-hung erection, when Below is a typical example of an order
desired, the type designation is completed with three PEXLIM arresters and its
by letter ”H” after system voltage (Um). accessories.
For other angular erection, please inform
us at order. 3 pcs. PEXLIM Q192-XV245
For non-standard arresters, the type Rated voltage 192 kV
designation will have additional letters for Line terminal type 1HSA 410 000-L
example: Earth terminal type 1HSA 420 000-A
E Non-standard electrical data
M Non-standard mechanical data 3 pcs. Insulating base type 1HSA 430 000-A
P Parallel metal-oxide columns

For under-hung
3 pcs. Surge counter type EXCOUNT-A
arresters, letter ”H”
to be added here.
Internal
code Um
Note! We recommend that the order
Block-type Ur
form, in section T-1, be filled-in and
PEXLIM Q192-XV245 (H) (L) attached to your order to ensure
inclusion of all the important parameters
Arrester family Pollution level according to For transmission line
IEC 60815. Neutral-ground surge arresters, letter and commercial conditions.
arresters have an ”N” here. ”L” to be added here.

C-6 Edition 4, 2003-10 ABB Surge Arresters — Buyer’s Guide


Selection of arrester

Simple selection example


Substation data:
Maximum system voltage: 145 kV
Arrester location: Phase-ground
System earthing: Effective
System fault clearance time: 1s
Creepage distance: 3 000 mm

1 Ur0 = 0.72xUm (according to table 1) 10% to 15% after taking distance effect
= 0.72x145 = 104.4 kVrms. Select the into account and depending on the
next higher standard Ur (see ”Guaran- chosen impulse steepness and ampli-
teed protective data”), i.e. 108 kVrms. tude. Thus, it is very important that the
arrester is installed as close as possible
2 According to table 2, a common to the protected object.
choice selection for 145 kVrms would
be a line discharge class 2 arrester, i.e. 4 If the margin is considered insufficient,
PEXLIM R. This arrester has a Upl/Ur choose a class 3 arrester, e.g. PEXLIM Q
of 2.59, i.e. Upl of 280 kVpeak at 10 kA with the same rated voltage 108 kV.
(according to table 3). With a Uwl of
550 kVpeak this would give a protective 5 With a required creepage distance of
margin of (550/280-1)x100 = 96 %. 3 000 mm, i.e. 20.7 mm/kV, YH145
(XH145 for PEXLIM Q) housing should
3 This margin appears to be excellent be selected.
but it must be noted that depending on
distance effect and possible insulation 6 The type designation of the selected
ageing, the margin is reduced to only arrester will then be:
PEXLIM R108-YH145
(or PEXLIM Q108-XH145)

ABB Surge Arresters — Buyer’s Guide Edition 4, 2003-10 C-7

You might also like