Professional Documents
Culture Documents
Xb12ul02406rnbnnnr PDF
Xb12ul02406rnbnnnr PDF
MEDC Series
These listed strobes have been designed for use in Certifications and Compliances:
potentially explosive atmospheres and harsh environmental
• UL Listed for USA and Canada
conditions. The enclosures are suitable for use offshore or
– Hazardous locations for USA and Canada
onshore, where a lightweight product combined with
Class I, Div. 2, Groups A, B, C, D*
corrosion resistance is required. UL 1971 compliant version available
The housing is manufactured from a U.V. stable, glass – Ordinary locations: Visual Signal Device
reinforced polyester, with the lens manufactured from a • NEMA 4X and 6, IP66 & 67
U.V. stable polycarbonate. Stainless steel screws are used, • Certified temperature
ensuring a totally corrosion-free product. –67°F to +158°F
The strobes contain supervisory diode and four wire leads –55°C to +70°C
for fire alarm applications. This strobe is also available UL
1971 (ADA) Listed for hearing impaired applications. Typical Industries:
Units can be painted to customer specification and supplied • Utility gas plants
with identification labels. • Wastewater treatment plants
• Mining
Applications: • Petroleum refineries
2S
1188 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds
1196-1197.qxp 5/30/2011 11:39 AM Page 1196
MEDC Series
Weight 15.5lb/7.0kg
Options Body & lens color, lens guard, certification,
voltages 24V DC, 110–254V AC
1196 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds
1198-1199.qxp 5/30/2011 11:39 AM Page 1199
MEDC Series
Specification—XB12 DC AC 50/60Hz
Certification: UL Listed for USA and Canada Voltage 24 110 240
– Hazardous locations: XB12
Class I, Div. 2, Groups C, D Tube Energy 21 21 21
Class I, Zone 1 & 2, AExd IIB T4/T5 (joules)
UL Listing No. E187894
– Ordinary locations: Visual Signal Device Peak Current
UL Listing No. S8128 Consumption 1400 350 185
ATEX approved: (mA)
Exd IIB T4/T5 Effective
Cert. No. 99 ATEX 2196 355 355 355
Intensity (Cd)
Materials: Body: Glass reinforced polyester Peak Intensity (Cd) 123691 123691 123691
Lens: Toughened Glass
Cover Screws + Backstrap: Power Consumption
(Watts) 33.6 38.5 44.4
Stainless steel 316
The Cd figures are for a clear lens @ 1Hz flash rate.
Finish: Natural black or painted to customer
specification For Colored Lenses
Weight: 15.5 lb/7.0kg Color Red Blue Amber Green Yellow
Certified Temperature: –67°F to +158°F (–55°C to +70°C) Multiplying
0.15 0.12 0.51 0.49 0.86
hazardous locations Factor
–67°F to +131°F (–55°C to +55°C) The photometric data has been verified by BSI. A report is available
ordinary locations
if required.
Ingress Protection: NEMA 4X and 6, IP66 & 67
Terminals: 6 off suitable for up to 10 AWG conductor
size
Labels: Duty/tag label optional
Entries: 2 × 1/ 2" NPT, 20mm
2S
Ordering Requirements
The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box.
www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1199