You are on page 1of 8

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/3274179

A current-based solution for transformer differential protection - Part I:


Problem statement

Article  in  IEEE Transactions on Power Delivery · November 2001


DOI: 10.1109/61.956726 · Source: IEEE Xplore

CITATIONS READS
100 5,730

4 authors, including:

Armando Guzman
Schweitzer Engineering Laboratories, Inc.
80 PUBLICATIONS   1,188 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Transformer Protection View project

All content following this page was uploaded by Armando Guzman on 13 June 2016.

The user has requested enhancement of the downloaded file.


IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 4, OCTOBER 2001 485

A Current-Based Solution for Transformer


Differential Protection—Part I: Problem Statement
Armando Guzmán, Member, IEEE, Stan Zocholl, Life Fellow, IEEE, Gabriel Benmouyal, Member, IEEE, and
Héctor J. Altuve, Senior Member, IEEE

Abstract—This paper analyzes the problem of transformer


differential protection. First, we review the concept of trans-
former differential protection. We then analyze magnetizing
inrush, overexcitation, and current transformer (CT) saturation
phenomena as possible causes of relay misoperation. Finally, we
summarize the existing methods for discriminating internal faults
from inrush and overexcitation conditions. In Part II of the paper,
we propose a new approach for transformer differential protection
and describe the relay that is based on this approach.
Index Terms—Differential protection, power transformer pro-
tection, protective relaying.
Fig. 1. Typical differential relay connection diagram.

I. INTRODUCTION
block, Sharp and Glassburn introduced the idea of harmonic

T HREE characteristics generally provide means for


detecting transformer internal faults [1]. These char-
acteristics include an increase in phase currents, an increase
blocking instead of restraining [9].
Many modern transformer differential relays use either
harmonic restraint or blocking methods. These methods en-
in the differential current, and gas formation caused by the sure relay security for a very high percentage of inrush and
fault arc. When transformer internal faults occur, immediate overexcitation cases. However, these methods do not work in
disconnection of the faulted transformer is necessary to avoid cases with very low harmonic content in the operating current.
extensive damage and/or preserve power system stability and Common harmonic restraint or blocking, introduced by Einval
power quality. Three types of protection are normally used to and Linders [10], increases relay security for inrush, but could
detect these faults: overcurrent protection for phase currents, delay operation for internal faults combined with inrush in the
differential protection for differential currents, and gas accu- nonfaulted phases.
mulator or rate-of-pressure-rise protection for arcing faults. Transformer overexcitation may also cause differential relay
This analysis will focus primarily on differential protection. misoperation. Einval and Linders proposed the use of an ad-
Transformer differential relays are prone to misoperation in the ditional fifth-harmonic restraint to prevent such misoperations
presence of transformer inrush currents, which result from tran- [10]. Others have proposed several methods based on wave
sients in transformer magnetic flux. The first solution to this shape recognition to distinguish faults from inrush and have ap-
problem was to introduce an intentional time delay in the dif- plied these methods in transformer relays [11]–[14]. However,
ferential relay [2], [3]. Another proposal was to desensitize the these techniques do not identify transformer overexcitation
relay for a given time, to override the inrush condition [3], [4]. conditions.
Others suggested adding a voltage signal to restrain [2] or to su- This paper analyzes the problem of transformer differential
pervise the differential relay [5]. protection. We discuss magnetizing inrush, overexcitation, and
Researchers quickly recognized that the harmonic content of CT saturation phenomena as possible causes of relay misoper-
the differential current provided information that helped differ- ation. We then summarize the existing methods for discrimi-
entiate faults from inrush conditions. Kennedy and Hayward nating internal faults from inrush and overexcitation conditions.
proposed a differential relay with only harmonic restraint for bus In Part II of the paper, we propose a new approach for trans-
protection [6]. Hayward [7] and Matthews [8] further developed former differential protection and describe the relay that is based
this method by adding percentage differential restraint for trans- on this approach.
former protection. These early relays used all the harmonics to
restrain. With a relay that used only the second harmonic to
II. TRANSFORMER DIFFERENTIAL PROTECTION

Manuscript received January 19, 2000. Percentage restraint differential protective relays [3] have
A. Guzmán, S. Zocholl, and G. Benmouyal are with Schweitzer Engineering been in service for many years. Fig. 1 shows a typical differen-
Laboratories, Pullman, WA, USA. tial relay connection diagram. Differential elements compare
H. J. Altuve is with Universidad Autónoma de Nuevo León, Monterrey, N.L.,
México. an operating current with a restraining current. The operating
Publisher Item Identifier S 0885-8977(01)08528-4. current (also called differential current), , can be obtained
0885–8977/01$10.00 © 2001 IEEE
486 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 4, OCTOBER 2001

CT saturation is only one of the causes of false operating


current in differential relays. In the case of power transformer
applications, other possible sources of error are the following:
• Mismatch between the CT ratios and the power trans-
former ratio
• Variable ratio of the power transformer caused by a tap
changer
• Phase shift between the power transformer primary and
secondary currents for delta-wye connections
• Magnetizing inrush currents created by transformer tran-
sients because of energization, voltage recovery after the
clearance of an external fault, or energization of a parallel
transformer
Fig. 2. Differential relay with dual slope characteristic. • High exciting currents caused by transformer
overexcitation.
from the phasor sum of the currents entering the protected The relay percentage restraint characteristic typically solves
element: the first two problems. A proper connection of the CTs or emula-
tion of such a connection in a digital relay (auxiliary CTs histor-
(1) ically provided this function) addresses the phase shift problem.
A very complex problem is that of discriminating internal fault
is proportional to the fault current for internal faults and currents from the false differential currents caused by magne-
approaches zero for any other operating (ideal) conditions. tizing inrush and transformer overexcitation.
There are different alternatives for obtaining the restraining
current, . The most common ones include the following:
III. MAGNETIZING INRUSH, OVEREXCITATION, AND CT
(2) SATURATION
Inrush or overexcitation conditions of a power transformer
(3) produce false differential currents that could cause relay misop-
eration. Both conditions produce distorted currents because
(4) they are related to transformer core saturation. The distorted
waveforms provide information that helps to discriminate
where is a compensation factor, usually taken as 1 or 0.5. inrush and overexcitation conditions from internal faults. How-
Equations (3) and (4) offer the advantage of being applicable ever, this discrimination can be complicated by other sources
to differential relays with more than two restraint elements. of distortion such as CT saturation, nonlinear fault resistance,
The differential relay generates a tripping signal if the oper- or system resonant conditions.
ating current, , is greater than a percentage of the restraining
current, : A. Inrush Currents

(5) Magnetizing inrush occurs in a transformer whenever the


polarity and magnitude of the residual flux do not agree with
Fig. 2 shows a typical differential relay operating character- the polarity and magnitude of the ideal instantaneous value of
istic. This characteristic consists of a straight line having a slope steady-state flux [15]. Transformer energization is a typical
equal to and a horizontal straight line defining the relay cause of inrush currents, but any transient in the transformer
minimum pickup current, . The relay operating region is circuit may generate these currents. Other causes include
located above the slope characteristic [equation (5)], and the re- voltage recovery after the clearance of an external fault or the
straining region is below the slope characteristic. energization of a transformer in parallel with a transformer
Differential relays perform well for external faults, as long that is already in service. The magnitudes and waveforms of
as the CTs reproduce the primary currents correctly. When one inrush currents depend on a multitude of factors, and are almost
of the CTs saturates, or if both CTs saturate at different levels, impossible to predict [16]. The following summarizes the main
false operating current appears in the differential relay and characteristics of inrush currents:
could cause relay misoperation. Some differential relays use • Generally contain dc offset, odd harmonics, and even har-
the harmonics caused by CT saturation for added restraint and monics [15], [16].
to avoid misoperations (6). In addition, the slope characteristic • Typically composed of unipolar or bipolar pulses, sepa-
of the percentage differential relay provides further security rated by intervals of very low current values [15], [16].
for external faults with CT saturation. A variable-percentage • Peak values of unipolar inrush current pulses decrease
or dual-slope characteristic, originally proposed by Sharp very slowly. Time constant is typically much greater
and Glassburn, further increases relay security for heavy CT than that of the exponentially decaying dc offset of fault
saturation. Fig. 2 shows this characteristic as a dotted line. currents.
GUZMÁN et al.: A CURRENT-BASED SOLUTION FOR TRANSFORMER DIFFERENTIAL PROTECTION—PART I: PROBLEM STATEMENT 487

TABLE I
HARMONIC CONTENT OF THE CURRENT SIGNAL SHOWN IN FIG. 3

Fig. 3. Exciting current of an overexcited transformer; overvoltage of


150 percent applied to a 5 KVA, 230/115 V single-phase transformer. Table I shows the most significant harmonics of the current
signal depicted in Fig. 3. Harmonics are expressed as a per-
• Second-harmonic content starts with a low value and in- centage of the fundamental component. The third harmonic is
creases as the inrush current decreases. the most suitable for detecting overexcitation conditions, but ei-
• Relay currents are delta currents (a delta winding is en- ther the delta connection of the CTs or the delta connection com-
countered in either the power- or current-transformer con- pensation of the differential relay filters out this harmonic. The
nections, or is simulated in the relay), which means that fifth harmonic, however, is still a reliable quantity for detecting
currents of adjacent windings are subtracted, and: overexcitation conditions.
DC components are subtracted Einval and Linders [10] were first to propose using the fifth
Fundamental components are added at 60 harmonic to restrain the transformer differential relay. They rec-
Second harmonics are added at 120 ommended setting this restraint function at 35 percent of fifth
Third harmonics are added at 180 (they cancel out), harmonic with respect to the fundamental. This ensures secu-
and so forth. rity for overvoltage conditions less than 140 percent. For greater
overvoltages, which could destroy the transformer in a few sec-
Sonnemann et al. initially claimed that the second-harmonic
onds, it is desirable to have the differential relay fast tripping
content of the inrush current was never less than 16–17 percent
added to that of the transformer overexcitation relay.
of the fundamental [15]. However, transformer energization
with reduced voltages may generate inrush currents with C. CT Saturation
second-harmonic content less than 10 percent, as will be
discussed in Part II of this paper. The effect of CT saturation on transformer differential pro-
tection is double-edged. For external faults, the resulting false
B. Transformer Overexcitation differential current may produce relay misoperation. In some
cases, the percentage restraint in the relay addresses this false
The magnetic flux inside the transformer core is directly differential current. For internal faults, the harmonics resulting
proportional to the applied voltage and inversely proportional from CT saturation could delay the operation of differential re-
to the system frequency. Overvoltage and/or underfrequency lays having harmonic restraint or blocking.
conditions can produce flux levels that saturate the transformer The main characteristics of CT saturation are the following:
core. These abnormal operating conditions can exist in any part
• CTs reproduce faithfully the primary current for a given
of the power system, so any transformer may be exposed to
time after fault inception [18]. The time to CT saturation
overexcitation.
depends on several factors, but is typically one cycle or
Transformer overexcitation causes transformer heating and
longer.
increases exciting current, noise, and vibration. A severely
• The worst CT saturation is produced by the dc component
overexcited transformer should be disconnected to avoid
of the primary current. During this dc saturation period,
transformer damage. Because it is difficult, with differential
the second-ary current may contain dc offset and odd and
protection, to control the amount of overexcitation that a trans-
even harmonics [7], [19].
former can tolerate, transformer differential protection tripping
When the dc offset dies out, the CT has only ac saturation,
for an overexcitation condition is not desirable. Use separate
characterized by the presence of odd harmonics in the secondary
transformer overexcitation protection, instead, and the differen-
current [6], [7], [20]. Fig. 4 shows a typical secondary current
tial element should not trip for these conditions. One alternative
waveform for computer-simulated ac CT saturation. This figure
is a V/Hz relay that responds to the voltage/frequency ratio.
also depicts the harmonic content of this current. The figure
Overexcitation of a power transformer is a typical case of ac
confirms the presence of odd harmonics and the absence of even
saturation of the core that produces odd harmonics in the ex-
harmonics in the secondary current.
citing current. Fig. 3 shows the exciting current recorded during
a real test of a 5 kVA, 230/115 V, single-phase laboratory trans-
former [17]. The current corresponds to an overvoltage con- IV. METHODS FOR DISCRIMINATING INTERNAL FAULTS FROM
INRUSH AND OVEREXCITATION CONDITIONS
dition of 150 percent at nominal frequency. For comparison
purposes, the peak value of the transformer nominal current is Early transformer differential relay designs used time delay
61.5 A, and the peak value of the exciting current is 57.3 A. [2], [3] or a temporary desensitization of the relay [3], [4] to
488 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 4, OCTOBER 2001

Einval and Linders [10] designed a three-phase differential


relay with second- and fifth-harmonic restraint. This design
complemented the idea of using only the second harmonic
to identify inrush currents (originally proposed by Sharp and
Glassburn [9]), by using the fifth harmonic to avoid misopera-
tions for transformer overexcitation conditions.
The relay [10] includes air-gap auxiliary current transformers
that produce voltage secondary signals and filter out the dc
components of the input currents. A maximum voltage detector
produces the percentage differential restraint voltage, so the
restraint quantity is of the form shown in (4). The relay forms
an additional restraint voltage by summing the second- and
fifth-harmonic components of a voltage proportional to the
operating current. The basic operation equation for one phase
can be expressed according to the following:
Fig. 4. Typical secondary current for symmetrical CT saturation and its
harmonic content. (8)

Einval and Linders first introduced the concept of common


override the inrush current. An additional voltage signal to re-
harmonic restraint in this relay. The harmonic restraint quan-
strain [2] or to supervise (block) [5] the differential relay has
tity is proportional to the sum of the second- and fifth-harmonic
also been proposed. These proposals increased operating speed
components of the three relay elements. The relay operation
at the cost of higher complexity. Recent methods use voltage
equation is of the following form:
information to provide transformer protection [21]–[24]. It is
recognized, however, that while an integrated digital substation
protection system provides voltage information, this is not the (9)
case for a stand-alone differential relay. Adding voltage signals
to such a relay requires potential transformers that are normally
Sharp and Glassburn [9] were first to propose harmonic
not available in the installation.
blocking. They designed a relay consisting of a percentage
The current-based methods for discriminating internal faults
differential unit, DU, and a harmonic blocking unit, HBU.
from inrush and overexcitation conditions fall into two groups:
Differential relay tripping requires operation of both DU and
those using harmonics to restrain or block [6]–[10] and those
HBU units.
based on wave-shape identification [11]–[14].
In the harmonic blocking unit the fundamental component
and higher harmonics of the operating current are passed to two
A. Harmonic-Based Methods
parallel circuits, rectified, and applied to the operating and re-
The harmonic content of the differential current can be used to straint coils of a polarized relay unit. The circuit supplying the
restrain or to block the relay, providing a means to differentiate operating coil of the polarized relay unit includes a notch-type
between internal faults and inrush or overexcitation conditions. parallel filter tuned to 120 Hz. The circuit supplying the restraint
The technical literature on this topic has not clearly identified coil of the polarized relay contains a low-pass filter combined
the differences between restraint and blocking. with a notch filter tuned to 60 Hz. The series combination of
The first harmonic-restrained differential relays used all har- both filters passes the second harmonic and rejects the funda-
monics to provide the restraint function [6]–[8]. The resulting mental component and remaining harmonics of the operating
high level of harmonic restraint provided security for inrush current. As a result, the polarized relay compares an operating
conditions at the expense of operating speed for internal faults signal formed by the fundamental component, plus the third and
with CT saturation. higher order harmonics of the operating current, with a restraint
Kennedy and Hayward [6] designed a differential relay with signal that is proportional to the second harmonic of the oper-
only harmonic restraint for bus protection. The operating equa- ating current. The operating condition of the harmonic blocking
tion can be expressed as: unit, HBU, can be expressed as follows:

(6) (10)

where represents the fundamental component of the oper- Typically, digital transformer differential relays use second-
ating current; , are the higher harmonics; and are and fifth-harmonic blocking logic. Fig. 5(a) shows a logic
constant coefficients. diagram of a differential element having second- and fifth-
Hayward [7] and Matthews [8] enhanced this method by harmonic blocking. A tripping signal requires fulfillment of
adding percentage differential restraint for transformer protec- (5), without fulfillment of the following blocking conditions:
tion. The differential relay operating condition is:
(11)
(7) (12)
GUZMÁN et al.: A CURRENT-BASED SOLUTION FOR TRANSFORMER DIFFERENTIAL PROTECTION—PART I: PROBLEM STATEMENT 489

scheme and is the preferred alternative in present-day digital re-


lays. Fig. 7 shows a logic diagram of the common harmonic
blocking method.
A method that provides a compromise in reliability between
the independent and common harmonic blocking methods
described earlier forms a composite signal that contains
information on the harmonics of the operating currents of all
relay elements. Comparison of this composite signal with the
operating current determines relay operation.
The composite signal, , may be of the following form:

(13)

may contain all or only part of the harmonics of the op-


erating current. Another possibility is to calculate the harmonics
RMS value for each relay element, :

(14)

The composite signal, , may then be calculated as some


Fig. 5. Two approaches to a differential element. type of an average value, using (15) or (16).

(15)

(16)

The relay blocking condition is the following:

(17)
Fig. 6. Three-phase differential relay with independent harmonic blocking or
restraint. Common harmonic blocking logic provides high security but
sacrifices some dependability. Energization of a faulted trans-
Fig. 5(b) depicts the logic diagram of a differential element former could result in harmonics from the inrush currents of
using second- and fifth-harmonic restraint. the nonfaulted phases, and these harmonics could delay relay
Fig. 6 shows the three-phase versions of the transformer dif- operation.
ferential relay with independent harmonic blocking or restraint.
The relay is composed of three differential elements of the types B. Wave Shape Recognition Methods
shown in Fig. 5. In both cases a tripping signal results when any Other methods for discriminating internal faults from inrush
one of the relay elements asserts. conditions are based on direct recognition of the wave shape
Note that in the harmonic restraint element [see Fig. 5(b)], distortion of the differential current.
the operating current, , should overcome the combined ef- Identification of the separation of differential current peaks
fects of the restraining current, , and the harmonics of the represents a major group of wave shape recognition methods.
operating current. On the other hand, in the harmonic blocking Bertula [25] designed an early percentage differential relay in
element the operating current is independently compared with which the contacts vibrated for inrush current (because of the
the restraint current and the harmonics. Table II summarizes low current intervals) and remained firmly closed for symmet-
the results of a qualitative comparison of the harmonic restraint rical currents corresponding to internal faults. Rockefeller [13]
(using all harmonics) and blocking methods for transformer dif- proposed blocking relay operation if successive peaks of the dif-
ferential protection. ferential current fail to occur at about 7.5–10 ms.
The comparison results given in Table II suggest the use of the A well-known principle [11], [26] recognizes the length of
blocking method, if security for inrush can be guaranteed. How- the time intervals during which the differential current is near
ever, it is not always possible to guarantee security for inrush, zero. Fig. 8 depicts the basic concept behind this low current
as Part II of this paper explains. Therefore, harmonic restraint detection method.
is an alternative method for providing relay security for inrush The differential current is compared with positive and nega-
currents having low harmonic content. tive thresholds having equal magnitudes. This comparison helps
Another alternative is to use common harmonic restraint or to determine the duration of the intervals during which the ab-
blocking. This method is simple to implement in a blocking solute value of the current is less than the absolute value of the
490 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 4, OCTOBER 2001

TABLE II
COMPARISON OF INDEPENDENT HARMONIC RESTRAINT AND INDEPENDENT BLOCKING METHODS

This signal is the sum of the dc and amplified fundamental com-


ponents of the rectified differential current.
Another group of methods makes use of the recognition of
dc offset or asymmetry in the differential current. Some early
relays [12], [29], [30] used the saturation of an intermediate
Fig. 7. Common harmonic blocking method. transformer by the dc offset of the differential current as a
blocking method. A transient additional restraint based on
the dc component was an enhancement to a well-known
harmonic-restraint transformer differential relay [8]. Michelson
[31] proposed comparing the amplitudes of the positive and
negative semicycles of the differential current with given
thresholds in two different polarized elements. Both elements
must pick up to produce a trip. Rockefeller [13] suggested
extension of this idea to a digital relay. Another alternative [32]
is to use the difference of the absolute values of the positive and
negative semicycles of the differential current for restraint. The
amplitude of the negative semicycle of the differential current
may also be used as the relay operating quantity [32]. The
negative semicycle is that semicycle having opposite polarity
with respect to the dc component. More recently, Wilkinson
[14] proposed making separate percentage-differential compar-
isons on both semicycles of the differential current. Tripping
occurs if an operation condition similar to (7) is true for both
Fig. 8. Differential relay blocking based on recognizing the duration time of semicycles.
low current intervals.
V. CONCLUSION
threshold. The time intervals are then electronically compared 1) Most transformer differential relays use the harmonics of
with a threshold value equal to one-quarter cycle. For inrush the operating current to distinguish internal faults from
currents [Fig. 8(a)], the low current intervals, , are greater magnetizing inrush or overexcitation conditions. The har-
than one-quarter cycle, and the relay is blocked. For internal monics can be used to restrain or to block relay operation.
faults [Fig. 8(b)], the low current intervals, , are less than Harmonic restraint and blocking methods ensure relay se-
one-quarter cycle, and the relay operates. curity for a very high percentage of inrush and overexci-
Use of rectified differential current components provides an tation cases. However, these methods fail for cases with
indirect way to identify the presence of low current intervals. very low harmonic content in the operating current.
Hegazy [27] proposed comparing the second harmonic of the 2) Common harmonic restraint or blocking increases differ-
rectified differential current with a given threshold to generate ential relay security, but could delay relay operation for
a tripping signal. Dmitrenko [28] proposed issuing a tripping internal faults combined with inrush currents in the non-
signal if the polarity of a summing signal remains unchanged. faulted phases.
GUZMÁN et al.: A CURRENT-BASED SOLUTION FOR TRANSFORMER DIFFERENTIAL PROTECTION—PART I: PROBLEM STATEMENT 491

3) Wave shape recognition techniques represent another [26] A. Giuliante and G. Clough, “Advances in the design of differential pro-
alternative for discriminating internal faults from inrush tection for power transformers,” in 1991 Georgia Tech. Protective Re-
laying Conference, Atlanta, GA, May 1–3, 1991, pp. 1–12.
conditions. However, these techniques fail to identify [27] M. Hegazy, “New principle for using full-wave rectifiers in differential
transformer overexcitation conditions. protection of transformers,” IEE Proceedings, vol. 116, pp. 425–428,
Mar. 1969.
[28] A. M. Dmitrenko, “The use of currentless pauses for detuning differ-
REFERENCES ential protection from transient imbalance currents” (in Russian), Elek-
trichestvo, no. 1, pp. 55–58, Jan. 1979.
[1] E. A. Klingshirn, H. R. Moore, and E. C. Wentz, “Detection of faults
in power transformers,” AIEE Transactions, pt. III, vol. 76, pp. 87–95, [29] D. Robertson, Ed., Power System Protection Reference Manual—Rey-
rolle Protection. London: Oriel Press Ltd., 1982.
Apr. 1957.
[2] I. T. Monseth and P. H. Robinson, Relay Systems: Theory and Applica- [30] R. K. Edgeley and F. L. Hamilton, “The application of transductors as
relays in protective gear,” IEE Proceedings, pt. II, vol. 99, p. 297, 1952.
tions. New York: McGraw Hill Co., 1935.
[3] R. E. Cordray, “Percentage differential transformer protection,” Elec- [31] E. L. Michelson, “Rectifier relay for transformer protection,” AIEE
trical Engineering, vol. 50, pp. 361–363, May 1931. Transactions, vol. 64, pp. 252–254, May 1945.
[32] E. V. Podgornyi and E. M. Ulianitskii, “A comparison of principles for
[4] , “Preventing false operation of differential relays,” Electrical
World, pp. 160–161, July 25, 1931. detuning differential relays from transformer inrush currents” (in Rus-
sian), Elektrichestvo, no. 10, pp. 26–32, Oct. 1969.
[5] E. L. Harder and W. E. Marter, “Principles and practices of relaying in
the United States,” AIEE Transactions, pt. II, vol. 67, pp. 1005–1023,
1948.
[6] L. F. Kennedy and C. D. Hayward, “Harmonic-current-restrained relays
for differential protection,” AIEE Transactions, vol. 57, pp. 262–266, Armando Guzmán received the B.S.E.E. degree with honors from Guadala-
May 1938. jara Autonomous University (UAG), Mexico, in 1979. He received a diploma
[7] C. D. Hayward, “Harmonic-current-restrained relays for transformer in fiber-optics engineering from Monterrey Institute of Technology and Ad-
differential protection,” AIEE Transactions, vol. 60, pp. 377–382, 1941. vanced Studies (ITESM), Mexico, in 1990. He served as regional supervisor of
[8] C. A. Mathews, “An improved transformer differential relay,” AIEE the Protection Department in the Western Transmission Region of the Federal
Transactions, pt. III, vol. 73, pp. 645–650, June 1954. Electricity Commission (the electrical utility company of Mexico) for 13 years.
[9] R. L. Sharp and W. E. Glassburn, “A transformer differential relay with He lectured at UAG in power system protection. Since 1993, he has been with
second-harmonic restraint,” AIEE Transactions, pt. III, vol. 77, pp. Schweitzer Engineering Laboratories, Pullman, WA, where he is presently a re-
913–918, Dec. 1958. search engineer. He holds several patents in power system protection. He is a
[10] C. H. Einval and J. R. Linders, “A three-phase differential relay for Member of IEEE and has authored and coauthored several technical papers.
transformer protection,” IEEE Trans. PAS, vol. PAS-94, no. 6, pp.
1971–1980, Nov./Dec. 1975.
[11] A. M. Dmitrenko, “Semiconductor pulse-duration differential restraint
relay” (in Russian), Izvestiya Vysshikh Uchebnykh Zavedenii, Elek- Stanley (Stan) Zocholl received the B.S. and M.S. degrees in electrical engi-
tromekhanika, no. 3, pp. 335–339, Mar. 1970. neering from Drexel University. He is an IEEE Life Fellow and a member of the
[12] G. I. Atabekov, The Relay Protection of High-Voltage Net- Power Engineering Society and the Industrial Application Society. He is also a
works. London: Pergamon Press Ltd., 1960. member of the Power System Relaying Committee and past chair of the Relay
[13] G. D. Rockefeller, “Fault protection with a digital computer,” IEEE Input Sources Subcommittee. He joined Schweitzer Engineering Laboratories
Trans. PAS, vol. PAS-98, pp. 438–464, Apr. 1969. in 1991 in the position of Distinguished Engineer. He was with ABB Power
[14] S. B. Wilkinson, “Transformer differential relay,” U.S. Patent No T&D Company Allentown (formerly ITE, Gould, BBC) since 1947, where he
5 627 712, May 6, 1997. held various engineering positions including Director of Protection Technology.
[15] W. K. Sonnemann, C. L. Wagner, and G. D. Rockefeller, “Magnetizing His biography appears in Who’s Who in America. He holds over a dozen patents
inrush phenomena in transformer banks,” AIEE Transactions, pt. III, vol. associated with power system protection using solid state and microprocessor
77, pp. 884–892, Oct. 1958. technology and is the author of numerous IEEE and protective relay conference
[16] J. Berdy, W. Kaufman, and K. Winick, “A dissertation on power trans- papers. He received the Best Paper Award of the 1988 Petroleum and Chem-
former excitation and inrush characteristics,” in Symposium on Trans- ical Industry Conference and the Power System Relaying Committee’s Distin-
former Excitation and Inrush Characteristics and Their Relationship to guished Service Award in 1991.
Transformer Protective Relaying, Houston, TX, Aug. 5, 1976.
[17] S. E. Zocholl, A. Guzmán, and D. Hou, “Transformer modeling as
applied to differential protection,” in 22nd Annual Western Protective
Relay Conference, Spokane, WA, Oct. 24–26, 1995.
[18] IEEE Power Engineering Society, “Transient response of current trans- Gabriel Benmouyal received the B.A.Sc. degree in electrical engineering and
formers,” IEEE Special Publication 76 CH 1130-4 PWR, Jan. 1976. the M.A.Sc. degree in control engineering from Ecole Polytechnique, Univer-
[19] E. C. Wentz and W. K. Sonnemann, “Current transformers and relays sité de Montréal, Canada in 1968 and 1970, respectively. In 1969, he joined
for high-speed differential protection with particular reference to offset Hydro-Québec as an instrumentation and control specialist. He worked on dif-
transient currents,” AIEE Transactions, vol. 59, pp. 481–488, Aug. 1940. ferent projects in the field of substation control systems and dispatching centers.
[20] J. E. Waldron and S. E. Zocholl, “Design considerations for a new In 1978, he joined IREQ, where his main field of activity was the application
solid-state transformer differential relay with harmonic restraint,” in of microprocessors and digital techniques to substation and generating-station
Fifth Annual Western Protective Relay Conference, Sacramento, CA, control and protection systems. In 1997, he joined Schweitzer Engineering Lab-
Oct. 15–18, 1978. oratories in the position of Research Engineer. He is a registered professional
[21] J. A. Sykes, “A new technique for high speed transformer fault pro- engineer in the Province of Québec, is an IEEE Member, and has served on the
tection suitable for digital computer implementation,” in Power Engi- Power System Relaying Committee since May 1989.
neering Society Summer Meeting, 1972, IEEE Paper no. C72 429-9.
[22] J. S. Thorp and A. G. Phadke, “A microprocessor based, voltage-re-
strained, three-phase transformer differential relay,” in Proceedings of
the Southeastern Symposium on System Theory, Apr. 1982, pp. 312–316. Héctor J. Altuve received the B.S.E.E. degree from Central University of Las
[23] , “A new computer based, flux restrained, current differential relay Villas (UCLV), Cuba, in 1969 and the Ph.D. degree from Kiev Polytechnic In-
for power transformer protection,” IEEE Trans. PAS, vol. PAS-102, no. stitute, USSR, in 1981. He served as a professor in the School of Electrical
11, pp. 3624–3629, Nov. 1983. Engineering at UCLV from 1969 to 1993. Since 1993, he has been a professor
[24] K. Inagaki, M. Higaki, Y. Matsui, K. Kurita, M. Suzuki, K. Yoshida, in the Ph.D. program of the Mechanical and Electrical Engineering School at
and T. Maeda, “Digital protection method for power transformers based Autonomous University of Nuevo Leon, in Monterrey, Mexico. He is a member
on an equivalent circuit composed of inverse inductance,” IEEE Trans. of the Mexican National Research System, a Senior Member of IEEE, and a
Power Delivery, vol. 3, no. 4, pp. 1501–1510, Oct. 1998. PES Distinguished Lecturer. He has authored and coauthored many technical
[25] G. Bertula, “Enhanced transformer protection through inrush-proof ratio papers. He is presently the Schweitzer visiting professor at Washington State
differential relays,” Brown Boveri Review, vol. 32, pp. 129–133, 1945. University.

View publication stats

You might also like