To use enter the cable Outside Diameter and Conduit Inside Diameter

NEC Chapter 9 Table 1 p70-617

Number of Conductors All Conductor Types (Max cable cross sectional area)
1 53%
2 31%
Over 2 40%

SINGLE CABLE

Cable Info Conduit Info Used Spare

OD ID
75 114 43.28% 56.72% OK

TWO CABLES

Cable Info Conduit Info Used Spare

OD ID
55 200 15.13% 84.88% OK
55

THREE CABLES

Cable Info Conduit Info Used Spare

OD ID
50 150 33.33% 66.67% OK
50
50
Schedule 40 Conduit - UL Listed
Conforms to NEMA TC 2 UL 651
Trade Average Approximate Minimum Approximate

Trade Size Outside Diameter Outside Diameter Inside Diameter Inside Diameter Wall Thickness Weight
(inches) (inches) (mm) (inches) (mm) (lbs/100')
1/2 0.84 21.336 0.6 15.24 0.109 16
3/4 1.05 26.67 0.8 20.32 0.113 22
1 1.315 33.401 1.03 26.162 0.133 32
1 1/4 1.66 42.164 1.36 34.544 0.14 46
1 1/2 1.9 48.26 1.59 40.386 0.145 54
2 2.375 60.325 2.04 51.816 0.154 73
2 1/2 2.875 73.025 2.44 61.976 0.203 120
3 3.5 88.9 3.03 76.962 0.216 170
3 1/2 4 101.6 3.51 89.154 0.226 200
4 4.5 114.3 3.99 101.346 0.237 230
5 5.563 141.3002 5.01 127.254 0.258 320
6 6.625 168.275 6.02 152.908 0.28 412