Professional Documents
Culture Documents
April 12 and 13
Kansas City, MO
Minutes
Subcommittee members
Jason Bray John Hukey
Robert Jenkins David Scott
Michael Hernandez Matthew Sheehan
Visitors
Oscar R. Antommatlei Claude E. Jaycox
Kevin Wolf
Minutes of the Kansas City Convention, 2015
4. Announcements:
Chairman Cornell discussed convention goals. Purpose of convention was to focus on Primary
TAC comments that need committee discussion. Goal is to have Public Comment this summer and
handle Public Comments in Denver, if needed. Final goal: Will publish by end of 2015.
Chairman Cornell acknowledged D. Gustafson who will receive Honorary Membership this
convention. Chairman also acknowledged 301 Committee members J. Gajda and T. Greene who
will be inducted as Fellows of the Institute this convention.
6.2 Item 3, Ref 174, negative by Carino, Becker, and Malits. Becker changed his vote to Abstain.
There was a motion made by Toon and seconded by Ferraro to find Carino persuasive and to
accept a substantive change. The motion passed by a vote of 23-0-2.
2.3.3.1 During reshoring and backshoring, comply with 1.8.1. If RESPONSE TO TAC
submittal in 2.1.3.1.d is specified, do not allow any structural Accepted.
member to be loaded with combined dead and construction loads in Editorial.
excess of loads indicated in the submitted reshoring and backshoring
procedure in 2.1.3.1.d.
If the reshoring and backshoring procedure described in 2.1.3.1.d is
submitted, do not allow structural members to be loaded with
combined dead and construction loads in excess of loads indicated
in the accepted procedure.
Minutes of the Kansas City Convention, 2015
6.3 Item 3, Ref 172, negative by Lobo. There was a motion made by Toon and seconded by Carino
to find the voter persuasive and to accept a substantive change. The motion passed by a vote of
23-0-2.
2.3.2.6 Unless otherwise specified, if shores and OPTIONAL RESPONSE TO TAC
other supports are arranged to allow removal of Specify the minimum in-place Accepted.
form-facing material without allowing structural compressive strength for Substantive Change.
slab or member to deflect, form-facing material removal of forms supporting the
and its horizontal supporting members are weight of concrete if different
allowed to be removed before in-place concrete from fc’. Refer to ACI 347 and
reaches f'c. ACI 347.2R for guidance on
items to consider.
Unless otherwise specified, form-facing
Specify if non-load-carrying
material and horizontal facing support members
form-facing material is not
may be removed before in-place concrete
permitted to be removed at an
reaches specified compressive strength if shores
earlier age than the load-carrying
and other supports are designed to allow facing
portion of the formwork.
removal without deflection of supported slab or
member.
6.4 Item 3, Ref 170, negative by Carreira There was a motion made by Toon and seconded by
Malits to find the voter persuasive and to accept a substantive change. The motion passed by a
vote of 25-0-0.
2.3.2.43 Do not damage concrete during removal of RESPONSE TO TAC
vertical formwork for columns, walls, and sides of Accepted.
beams. Perform needed repair and finishing Substantive Change.
operations required on vertical surfaces that day. If
forms are removed before end of specified curing
period, provide curing and protection in accordance
with Section 5.
6.5 Item 3, Ref 150, negative by Becker and Hanskat. There was a motion made by Toon and
seconded by Malits to find the voter persuasive and change response to TAC. The motion
passed by a vote of 25-0-0.
2.2.2.5.a Unless otherwise OPTIONAL RESPONSE TO TAC
specified, submit details and Specify locations or allowable Not Accepted.
locations of construction spacings for construction joints. Substantive Change.
joints in accordance with the Specify or allow alternative
Construction joints are at times left to the
following requirements: locations for formed construction
Contractor without specific “details”.
joints if necessary to facilitate
Alternate locations may require different
formwork removal or accelerate
details than the AE considered. There is no
construction, provided that the
harm in leaving “details” in for
alternative joint locations do not
construction joints. If specified in Contract
adversely affect the strength of the
Documents, they will simply duplicate the
structure.
provided details and confirm product
details.
3
Minutes of the Kansas City Convention, 2015
6.6 Item 3, Ref 177, negatives by Carino, Lobo, Krauser, and McCall. There was a motion made by
Toon and seconded by Lobo to find the voters persuasive and change response to TAC. The
motion passed by a vote of 25-0-0.
2.3.3.5 In multistory buildings, OPTIONAL RESPONSE TO TAC
place reshoring or backshoring over Refer to ACI 347.2 Not Accepted.
a sufficient number of stories to for further guidance Substantive Change.
distribute weight of newly placed
Content in document can be used by the A/E to
concrete, forms, and construction
understand required submittals and better specify
live loads in accordance with
expectations regarding reshoring, but this is not the
reshoring and backshoring
place for an educational reference. No trigger
procedure in 2.1.3.1.d.
language exists to use the option.
6.8 Item 5, Ref 242 and Ref 245, negatives by Becker. There was a motion made by Prenger and
seconded by Whisonant to find the voter persuasive and to accept a substantive change and
change response to TAC. The motion passed by a vote of 22-0-0.
4.2.2.2 Slump—Unless otherwise OPTIONAL RESPONSE TO TAC
specified select a target slump or slump Specify slump or slump flow if it is not Not Accepted.
flow at the point of delivery discharge permissible for Contractor to select these Substantive Change.
from the transportation unit of concrete values.
Point of delivery is used
mixtures for each application. Selected
throughout 301. This
target slump shall not exceed 9 inches.
does not need to be
Selected target slump flow shall not
changed to be
exceed 30 in. Concrete shall not show
inconsistent with all
visible signs of segregation. The target
other places it is used.
slump or slump flow value shall be
enforced for the duration of Project.
Determine the slump by ASTM
C143/C143M. Slump tolerances shall
meet the requirements of ACI 117.
Determine slump flow by ASTM
C1611/C1611M. Slump flow
tolerances shall meet the requirements
of ASTM C94/C94M.
4
Minutes of the Kansas City Convention, 2015
6.9 Item 5, Ref 247, negative by Carino. There was a motion made by Prenger and seconded by
Toon to find the voter persuasive and to accept a substantive change. The motion passed by a
vote of 22-0-0.
4.2.2.5.a Minimum temperature—If the average of the OPTIONAL RESPONSE TO TAC
highest and lowest ambient temperature from midnight to Not Accepted.
These requirements have
midnight is expected to be less than 40°F for more than Committee 301 feels
been excerpted from ACI
three successive days, deliver concrete to meet the that only these
306.1. For projects in cold
following minimum temperatures immediately after provisions of 301 are
climates, such as in
placement unless otherwise specified: to be replaced if the
northern winters, or in
A/E prefers to use
(a) 55°F for sections with least dimension less than 12 situations where it is
306.1
in.; prudent to require
Contractor to follow
(b) 50°F for sections with least dimension 12 to 36 in.; Editorial change to add
specific procedures to
“unless otherwise
(c) 45°F for sections with least dimension 36 to 72 in. achieve the limits of
specified” trigger
and 4.2.2.5.a, the temperature
language.
limits for cold weather may
(d) 40°F for sections with least dimension greater than
be deleted and ACI 306.1
72 in. can be referred to in its
The temperature of concrete as placed shall not exceed entirety. Options provided
these values by more than 20°F. These minimum in ACI 306.1 must then be
temperature requirements may be terminated if exercised. Also, Refer to
temperatures above 50°F occur during more than half of the Optional Requirements
any 24-hour duration. Checklist for 5.3.6.1.
6.11 Item 5, Ref 256, negative by Carino. There was a motion made by Prenger and seconded by
Chrzanowski to find the voter persuasive and to accept a substantive change. The motion passed
by a vote of 22-0-0.
RESPONSE TO TAC
Table 4.2.2.7.b.1—Total air content for concrete exposed to cycles of freezing and thawing
Editorial – ACI Staff to
determine appropriate
Target Total air content, percent *†
footnote symbols.
Nominal maximum
aggregate size, in.‡ Exposure Class F1 Exposure Classes F2 and F3 Removed Note 3 to be
consistent with ACI 318-
3/8 6.0 7.5
14.
1/2 5.5 7
3/4 5 6
1 4.5 6
2§ 4 5
3§ 3.5 4.5
*
Tolerance on air content as delivered shall be ± 1.5 percent.
†
For fc’ > 5000 psi reducing air content by 1.0 percentage point is acceptable.
‡
Refer to ASTM C33/C33M for tolerance on oversize for various nominal maximum size designations.
6.12 Item 5, Ref 264, negative by Robinson was withdrawn and will be taken as new business.
5
Minutes of the Kansas City Convention, 2015
6.13 Item 5, Ref 278, negative by Krauser was discussed and tabled.
6.14 Item 5, Ref 279 (related to Ref 280), negative by Carino. There was a motion made by Prenger
and seconded by Chrzanowski to find the voter persuasive and making a change to TAC
response. The motion passed by a vote of 23-0-0.
RESPONSE TO TAC
Accepted.
Editorial see Ref 280.
6.15 Item 5, Ref 281, negative by Carino and McCall was tabled.
6
Minutes of the Kansas City Convention, 2015
6.16 Item 10, Ref 472, negative by Lobo. There was a motion made by Krauser and seconded by
Becker to find the voter persuasive and to change response to TAC. The motion passed by a
vote of 23-0-0.
9.2.2 Grout mixtures for bonded tendons— RESPONSE TO TAC
Unless otherwise specified, use a grout materials, Not Accepted.
admixtures and testing that conform to the Substantive Change.
requirements of PTI M55.1with the following (Primary Change from Ref 4
exception: water soluble chloride ion content of included)
grout shall not exceed 0.06 percent measured by Original wording is consistent
mass of chloride ion to by mass of cement when with the chloride limits for
tested in accordance with ASTM concrete in Section 4.2 and does
C1218/C1218M. not change the intent of ACI 318.
6.19 Item 8, Ref 445, negative by Carino and Lobo. There was a motion made by Gajda and
seconded by Robinson to find the voter persuasive and to accept a substantive change. The
motion passed by a vote of 23-0-0.
7.2.2.1 Density—Proportion lightweight concrete MANDATORY RESPONSE TO TAC
to meet the specified equilibrium density Specify equilibrium density Accepted.
specified in the Contract Documents. Unless for lightweight concrete. Substantive Change.
otherwise specified, . C calculate the
approximate equilibrium density of mixture from OPTIONAL
measured or calculated ovendry density in Specify alternative method of
accordance with ASTM C567/C567M, unless determining equilibrium
another method is specified to determine density if other than
equilibrium density. calculated method in ASTM
Correlate equilibrium density with fresh density C567/C567M.
of concrete. Fresh density will be used as the
basis for acceptance during construction.
6.20 Item 8, Ref 446, negative by McCall. There was a motion made by Gajda and seconded by
Robinson to find the voter non-persuasive because his comment is unrelated to the TAC
comment. The motion passed by a vote of 19-1-2.
6.21 Item 8, Ref 447, negative by Carino and McCall. There was a motion made by Gajda and
seconded by Toon to find the voter persuasive and to change response to TAC. The motion
passed by a vote of 23-0-0.
7.3.1.2 Air content—Air content of lightweight RESPONSE TO TAC
concrete will be determined in accordance with Not Accepted.
ASTM C173/C173M Determine air content of Substantive Change.
lightweight concrete in accordance with ASTM Keep original wording. We are not
C173/C173M.
requiring the contractor to
determine the air content. The
article informed the contractor that
the air would be measured.
7
Minutes of the Kansas City Convention, 2015
6.22 Item 9, Ref 452, negative by Lobo and Malisch. There was a motion made by Gajda and
seconded by Toon to find the voter persuasive and to accept a substantive change. The motion
passed by a vote of 23-0-0.
8.1.4 Submittals— RESPONSE TO TAC
Not Accepted.
(j) description of format and frequency of If we omit this phrase, who
providing temperature data to does the temperature data get
Architect/Engineer; sent to?
Substantive Change.
6.23 Item 9, Ref 449 and 453, negative by Malisch. There was a motion made by Gajda and seconded
by Chrzanowski to find the voters non-persuasive because the checklist is to advise the A/E to specify an
alternate and to advise on the options for alternates. It is not commentary. Advice is not readily found in
other reference documents such as ACI 207. The motion passed by a vote of 19-2-2.
6.25 Item 13, Ref 541, negative by Carino. There was a motion made by DeCarlo and seconded by
Toon to find the voter persuasive and to accept a substantive change. The motion passed by a
vote of 24-0-0.
12.3.3.1 Reveals shall be located within ACI RESPONSE TO TAC
117 tolerances for cast in place concrete. Accepted.
Substantive Change
6.26 Item 13, Ref 544, negative by Carino was withdrawn and item will be taken up as new business.
6.27 Item 13, Ref 545, negative by Carino. There was a motion made by DeCarlo and seconded by
Toon to find the voter persuasive and to accept a substantive change and change response to
TAC. The motion passed by a vote of 25-0-0.
12.3.16.1 Concrete strength at time of erection shall RESPONSE TO TAC
be in accordance with accepted Lifting and Bracing Not Accepted.
Design Drawings. Substantive Change
The default is to provide Lifting
and Bracing Design Drawings.
No Optional Checklist is
required.
6.28 Item 3, Ref 149, negative by Becker and Carino. There was a motion made by Toon and
seconded by Becker to find the voters persuasive and to change response to TAC. The motion
passed by a vote of 24-0-1.
2.2.2.4 Unless otherwise specified, OPTIONAL RESPONSE TO TAC
limit deflection of facing materials for Specify more stringent Not Accepted.
concrete surfaces exposed to view to limitations on deflection Substantive Change.
1/240 of center-to-center spacing of of facing materials if
“Exposed to view” will be taken as new
facing supports. For architectural needed
business as will “Normal Use”.
concrete,refer to 6.2.2.1.a.
8
Minutes of the Kansas City Convention, 2015
6.30 Item 5, Ref 281, negative by Carino and McCall. There was a motion made by Prenger and
seconded by Chrzanowski to find the voter persuasive and to accept a substantive change. The
motion passed by a vote of 25-0-0.
4.3.1.2 Concrete produced by volumetric OPTIONAL RESPONSE TO TAC
batching and continuous mixing—If When Specify if the use of Accepted.
Concrete is made produced by volumetric volumetric batching and Substantive Change.
batching and continuous mixing is acceptable, it continuous mixing is
shall conform to ASTM C685/C685M and permitted.
satisfy the requirements of this Specification.
6.31 Item 5, Ref 284, negative by Gajda withdrew his negative and the topic will be taken up as new
business in the next cycle.
6.32 Item 6, Ref 288 and 289, negative by Malisch was withdrawn. Editorials by Lobo and Carino
were accepted and there was a change made to response to TAC on Ref 289.
SECTION 5—HANDLING, PLACING, RESPONSE TO TAC
AND CONSTRUCTING Not Accepted.
The committee prefers the existing
wording. Will take up proposed changes
as new business in next cycle.
5.1.1 Scope—This section covers the RESPONSE TO TAC
construction production of cast-in-place Not Accepted.
structural concrete. Included are methods and
The committee prefers the existing
procedures for obtaining quality concrete
wording. Will take up proposed changes
through proper handling, placing, finishing,
as new business in next cycle.
curing, and repair of surface defects.
Editorial change.
6.33 Item 6, Ref 293 and 312, negative by Carino and McCall. McCall withdrew his negatives. There
was a motion made by Prenger and seconded by Lobo to find the Carino persuasive and to
accept a substantive change. The motion passed by a vote of 22-0-0.
5.1.2.1.d Drawings and data— Shop drawings of p RESPONSE TO TAC
Placing, handling, and construction— Description of Accepted.
proposed methods. Substantive Change.
RESPONSE TO TAC
Accepted.
Substantive Changes.
See Ref 293.
6.34 Item 6, Ref 295, negative by McCall. There was a motion made by Prenger and seconded by
Lobo to find the voter persuasive and change response to TAC. The motion passed by a vote of
23-0-0.
5.1.2.1.f Pre-placement requirements—List of RESPONSE TO TAC
concrete pre-placement activities. Not Accepted.
Editorial
5.1.2.1.g Pre-placement meeting - Agenda for The term preplacement
concrete preplacement meeting to be held before indicates that we are referring to
start of placement activities. concrete.
9
Minutes of the Kansas City Convention, 2015
6.35 Item 6, Ref 296, negative by Carino (related to Provision 2.1.3.2). There was a motion made by
Prenger and seconded by Malisch to find the voter persuasive and to accept a substantive
change and change response to TAC. The motion passed by a vote of 23-0-0.
5.1.2.2 If required, submit information OPTIONAL RESPONSE TO TAC
specified in 5.1.2.2.a through 5.1.2.2.g. Not Accepted.
Specify the information Substantive Change.
in 5.1.2.2.a to 5.1.2.2.g The committee prefers the existing
that is to be submitted. wording. Will take up proposed
changes as new business in next cycle.
6.36 Item 6, Ref 300 (related to ref 361), negative by Carino. There was a motion made by Prenger
and seconded by Chrzanowski to find the voter persuasive and to accept a substantive change.
The motion passed by a vote of 22-0-1.
5.1.2.3 If alternatives are proposed, comply RESPONSE TO TAC
with 5.1.2.3.a through 5.1.2.3.f. Not Accepted.
The committee feels this is not an
5.1.2.3.f. If sawed joints are to be installed improvement to the document and prefers
using methods that are different from those the existing language. Will take up
specified in 5.3.5 submit request of the “alternatives” as New
proposed methods. Business.
(Substantive Change related to Ref 361)
5.3.5 Sawed joints—Where sawcut joints are OPTIONAL RESPONSE TO TAC
required start cutting as soon as concrete has Specify where saw- Accepted.
gained sufficient strength to prevent cut joints are Substantive Change.
dislodgment of coarse aggregate particles. Do required. Specify if (shown in Ref 300)
not saw cut reinforcement. an alternative saw-
Unless otherwise specified, saw a continuous cut depth is
slot to a depth one fourth the thickness of the required.
slab but not less than 1 in.
If an alternative method, timing, or depth is
proposed for saw cutting, submit procedure
and plans.
6.37 Item 6, Ref 302, negative by Carino. There was a motion made by Prenger and seconded by
Toon to find the voter persuasive and to accept a substantive change and change response to
TAC. The motion passed by a vote of 23-0-0.
5.1.2.3.a Construction joints—Submit information RESPONSE TO TAC
on proposed location and treatment of Not Accepted.
construction joints not indicated in Contract This is consistent with ACI 318.
Documents. Substantive Change to clarify intent.
5.1.2.3.cd Contraction or expansion joints—If Take out from list of "alternatives."
contraction or expansion joints other than those
indicated in Contract Documents are proposed,
submit locations.
5.1.2.4 Joints not shown in Contract Documents
5.1.2.4.a Submit information on proposed location
and treatment of construction joints not indicated
in Contract Documents.
5.1.2.4.b If movement joints other than those
indicated in Contract Documents are proposed,
submit locations.
10
Minutes of the Kansas City Convention, 2015
6.38 Item 6, Ref 309, negative by Carino and Lobo. Lobo withdrew his negative. There was a motion
made by Prenger and seconded by Toon to find Carino persuasive and to accept a substantive
change and change response to TAC. The motion passed by a vote of 22-0-2.
5.2.1.5 Evaporation retardants — Use l Liquid RESPONSE TO TAC
applied evaporation retardants that shall form a Not Accepted.
continuous monomolecular film and reduce This is the Products/Materials Section.
moisture loss from fresh concrete surface. 5.3.6.2 goes into how and when these
products should be used.
Substantive change.
6.39 Item 6, Ref 310, negative by Carino. There was a motion made by Prenger and seconded by
Lobo to find the voter persuasive and to accept a substantive change. The motion passed by a
vote of 24-0-0.
5.2.1.5 7Bonding material—For bonding material, use an RESPONSE TO TAC
acceptable Accepted bonding agent applied in Not Accepted.
accordance with the manufacturer’s requirements or use Will take up as New
portland cement grout of the same proportions as the Business in next cycle.
mortar in the concrete.
Substantive change.
6.40 Item 6, Ref 313, negative by McCall. There was a motion made by Prenger and seconded by
Toon to find the voter persuasive and to change response to TAC. The motion passed by a vote
of 23-0-0.
5.3.1.3 Before placing concrete in forms, complete RESPONSE TO TAC
the following: Not Accepted.
Substantive Change.
(a) comply with formwork requirements specified in
The requirement is to have the
Section 2;
formwork surface to be free of
(b) remove snow, ice, frost, standing water, and water. It is not always better for
other foreign materials from surfaces against the formwork to be at SSD;
which concrete will be placed, and from saturated plywood does not
reinforcement and embedded items and perform well.
(c) comply with reinforcement placement
requirements specified in Section 3.
6.41 Item 6, Ref 317, negative by Malisch. There was a motion made by Prenger and seconded by
Greene to find the voter non-persuasive because the best indication of the moisture content of
the concrete surface is that the surface appears to be dry. Moist concrete typically has a sheen
that provides an indication that the surface of the concrete is not dry. The surface of concrete
needs to be kept moist regardless of the reason that it is drying. The motion passed by a vote of
19-1-3.
6.42 Item 6, Ref 318, negative by Lobo. There was a motion made by Prenger and seconded by Lobo
to find the voter persuasive and to accept a substantive change. The motion passed by a vote of
22-0-1.
5.3.2.1.a Wet weather—Do not place concrete while RESPONSE TO TAC
rain, sleet, or snow is falling unless protection is Accepted.
provided and if required, acceptance of protection is Substantive Change.
obtained. Do not allow rain water precipitation to
increase mixing water or to damage concrete surface.
6.43 Ballot Item 2 did not pass and was withdrawn. Section 1 responses to TAC will be reballoted.
11
Minutes of the Kansas City Convention, 2015
6.44 Item 4, Ref 184 and 185, negative by McCall. McCall changed negatives to editorial.
6.45 Item 4, Ref 190, negatives by Carino and Krauser. There was a motion made by Turner and
seconded by Toon to find the voters persuasive and to accept a substantive change. The motion
passed by a vote of 18-0-3.
3.2.1.2.a Zinc-coated (galvanized) reinforcing bars OPTIONAL RESPONSE TO TAC
shall conform to ASTM A767/A767M and other MANDATORY Not Accepted.
requirements, in Contract Documents and other For zinc-coated reinforcing The committee intends that
requirements as specified in Contract Documents. bars conforming to ASTM all zinc coated (galvanized)
Coating damage incurred during shipment, A767/A767M, specify bars conform to the
handling, and placing of zinc-coated (galvanized) coating class, whether standard. The provision
reinforcing bars shall be repaired in accordance galvanizing is to be would require compliance
with ASTM A780. Damaged areas shall not exceed performed before or after only where zinc-coated
2 percent of surface area in each linear foot of each fabrication, and indicate (galvanized) bars are
bar or bar shall not be used. The 2 percent limit on which bars require special included in the design.
maximum allowed damaged coating area shall finished bend diameters (Substantive change- (see
include previously repaired areas damaged before (usually smaller sizes used Ref 204)
shipment as required by ASTM A767/A767M. for stirrup and ties).
6.46 Item 4, Ref 192, negative by Carino and Krauser. There was a motion made by Turner and
seconded by Toon to find the voter persuasive and to accept a substantive change. The motion
passed by a vote of 21-0-1.
3.2.1.2.b Epoxy-coated reinforcing bars shall conform to OPTIONAL RESPONSE TO TAC
ASTM A775/A775M or ASTM A934/A934M as specified MANDATORY Not Accepted.
in Contract Documents. Coatings shall be applied in plants Specify ASTM The committee intends
that are certified in accordance with Concrete Reinforcing specification to which that all epoxy coated
Steel Institute (CRSI) Epoxy Coating Plant Certification epoxy-coated reinforcing bars conform to the
Program or an equivalent program acceptable to bars are to conform. standard.
Architect/Engineer. Coating damage incurred during The provision would
shipment, storage, handling, and placing of epoxy-coated require compliance
reinforcing bars shall be repaired. Repair damaged coating only where epoxy-
areas with patching material conforming to in accordance coated bars are
with ASTM A775/A775M or ASTM A934/934M as included in the design.
applicable and in accordance with material manufacturer’s
written recommendations. Damaged coating area shall not Substantive Change
exceed 2 percent of surface area in each linear foot of each (Substantive change-
bar or bar shall not be used. The 2 percent limit on damaged see Ref 204)
coating area shall include repaired areas damaged before
shipment as required by ASTM A775/A775M or
A934/A934M as applicable. Fading of coating color shall
not be cause for rejection of epoxy coated reinforcing bars.
6.45 Item 4, Ref 204 and Ref 205, negatives by Carino. There was a motion made by Turner and
seconded by Toon to find the voter persuasive and accept a substantive change. The motion
passed by a vote of 22-0-1.
12
Minutes of the Kansas City Convention, 2015
6.47 Item 4, Ref 195, negative by Carino. There was a motion made by Turner and seconded by
Toon to find the voter persuasive and to accept a substantive change and change resonse to
TAC. The motion passed by a vote of 22-0-0.
3.2.1.2.d Mechanical splices for coated RESPONSE TO TAC
reinforcement shall have compatible Not Accepted.
coatings, in accordance with to The requirement for
manufacturer’s instructions. galvanized is for
Splices for galvanized reinforcement galvanized OR coated
shall be galvanized or coated with couplers, while the
dielectric material. Splices used with requirement for coated
epoxy-coated or dual-coated reinforcement is for only
reinforcement shall be coated with coated couplers
dielectric material.
Substantive Change.
6.48 Item 5, Ref 198, negative by Carino and McCall. There was a motion made by Turner and
seconded by Toon to find the voter persuasive and to accept a substantive change. The motion
passed by a vote of 22-0-0.
13
Minutes of the Kansas City Convention, 2015
6.51 Item 4, Ref 203, (related to 3.2.1.7a and 3.2.1.7.b) negative by McCall was tabled.
6.52 Item 4, Ref 213, negative by Carino, Malits, and McCall. McCall withdrew his negative. There
was a motion made by Turner and seconded by Toon to find Carino and Malits persuasive and
to accept a substantive change. The motion passed by a vote of 21-0-0.
3.3.2.3 Concrete cover—Unless otherwise OPTIONAL RESPONSE TO TAC
specified, concrete cover for reinforcement Specify the cover for headed shear Accepted.
shall conform to Table 3.3.2.3. 3.3.2.3.1, stud reinforcement and headed Substantive Change.
3.3.2.3.2, and 3.3.2.3.3. Concrete cover reinforcing bars. Refer to ACI 318.
tolerances shall comply with ACI 117. Specify cover requirements for
Position tie wire ends away from exposed corrosive atmosphere, other severe
concrete surfaces. exposures, or fire protection. Refer to
ACI 318.
3.3.2.3.1 Nonprestressed cast-in-place concrete members shall have specified concrete cover for reinforcement at least that given in Table 3.3.2.3.1
Table 3.3.2.3.1 Specified c Concrete cover for cast-in-place nonprestressed concrete members
3.3.2.3.2 Cast-in-place prestressed concrete members shall have specified concrete cover for reinforcement, ducts, and end fittings at least that given in
Table 3.3.2.3.2
Table 3.3.2.3.2 Specified c Concrete cover for cast-in-place nonprestressed concrete members
14
Minutes of the Kansas City Convention, 2015
3.3.2.3.3 Precast nonprestressed or prestressed concrete members manufactured under plant conditions shall have specified concrete cover for
reinforcement, ducts, and end fittings at least that given in Table 3.3.2.3.3
Table 3.3.2.3.3 Specified c Concrete cover for precast nonprestressed or prestressed concrete members manufactured under plant conditions
3.3.2.3.4 For bundled bars, specified concrete cover shall be at least the smaller of (a) and (b):
(a) The equivalent diameter of the bundle
(b) 2 in. and for concrete cast against and permanently in contact with ground, the specified cover shall be 3 in.
3.3.2.3.5 For headed shear stud reinforcement, concrete cover for the heads and base rails shall be the same as for surrounding reinforcement
unless otherwise specified by Architect/Engineer.
6.53 Item 4, Ref 214, negative by McCall. There was a motion made by Turner and seconded by
Toon to find the voter persuasive and to accept a substantive change. The motion passed by a
vote of 21-0-0.
15
Minutes of the Kansas City Convention, 2015
6.55 Item 4, Ref 222, negative by McCall. There was a motion made by Turner and seconded by
Toon to find the voter persuasive and to accept a substantive change and change response to
TAC. The motion passed by a vote of 20-0-0.
RESPONSE TO TAC
Table 3.3.2.8—Minimum specified Specified diameter Part 1- Accepted.
of bend Substantive Editorial Change. The table now
agrees with ACI 318-14 Tables 25.3.1 & 25.3.2
Minimum inside Inside Change “Inside bend diameter” to “Inside
Bar size diameter of bend”
bend diameter
6.56 Item 4, Ref 226, negative by Malisch. There was a motion made by Turner and seconded by
Toon to find the voter persuasive and change response to TAC. The motion passed by a vote of
19-0-0.
3.3.2.9 Field cutting reinforcement—Field RESPONSE TO TAC
cut after acceptance by Architect/ Not Accepted.
Engineer. Do not flame-cut epoxy-coated The committee intends to prohibit cutting of
reinforcement or zinc and epoxy dual- reinforcement on the job site unless called for
coated reinforcement. in the CDs or a request is made during
construction. This is intended to reduce the
3.1.2.1.f Field cutting of reinforcement – occurrence of cutting misplaced
Submit request for field cut including reinforcement without notice.
location and type of bar to be cut and Substantive Change.
reason field cut is required.
6.57 Item 4, Ref 227, negative by Malisch. There was a motion made by Turner and seconded by
Toon to find the voter persuasive and to accept a substantive change. The motion passed by a
vote of 17-0-0.
3.3.2.10 Reinforcement through expansion joint—Do Optional: OPTIONAL RESPONSE TO TAC
not continue reinforcement or other embedded metal Specify dowels that are Not Accepted.
items bonded to concrete through expansion joints, to be bonded on one side Editorial
16
Minutes of the Kansas City Convention, 2015
except dowels, that are specified to be bonded on one of an expansion joint. The committee intends to
side of a joint. allow unbounded dowels
If specified, dowels may continue through expansion across expansion joints as a
joints if unbonded on one side of the joint. default condition.
6.58 Item 3, Ref 138, negative by Malisch was changed to editorial and changed response to TAC.
2.1.3.2.c Submit manufacturer’s data RESPONSE TO TAC
sheet on form ties. Not Accepted.
2.1.3.2.d Submit manufacturer’s data The committee prefers the term data sheet for these
sheet on expansion joint materials. submittals.
2.1.3.2.e Submit manufacturer’s data
Data Sheet and Product Data were discussed at length
sheet on waterstop materials and
and the committee at large voted to accept the change
splices.
with the rationale that for these items a data sheet
which assumes to convey technical details is critical vs.
the generic product data which was assumed to be sales
materials in the experience of the group.
17
Minutes of the Kansas City Convention, 2015
9. Announcements:
Chairman Cornell made announcements. Matt Senecal is coordinating respective Codes in North
America and coordinate ACI documents. Code cycle will change to 6 years in the future.
10.2 Item 14, Ref 554, negative by Carino. There was a motion made by Wittry and seconded by
Carino to find the voter persuasive and to accept a substantive change. The motion passed by a
vote of 26-0-0.
13.1.4.4.c Test grout compressive strength in RESPONSE TO TAC
accordance with ASTM C109/C109M ASTM Accepted.
C1107/C1107M for sand-cement and non-shrink Substantive Change.
grout and ASTM C881/C881M for epoxy grout..
Strength of grout is satisfactory if 28-day
compressive strength is equal to or exceeds
specified grout strength.
10.3 Item 7, Ref 384, negative by McCall was changed to editorial on the capitalization of “Work”
and “Specification.
10.4 Item 7, Ref 385, negative by Lobo and McCall. There was a motion made by DeCarlo and
seconded by Toon to find the voter persuasive and to accept a substantive change and change
response to TAC. The motion passed by a vote of 25-0-0.
Minutes of the Kansas City Convention, 2015
10.5 Item 7, Ref 386, negative by Carino. There was a motion made by DeCarlo and seconded by
Toon to find the voter persuasive and to accept a substantive change and change response to
TAC. The motion passed by a vote of 27-0-0.
6.1.4.3 Architectural concrete OPTIONAL RESPONSE TO TAC
reference—If specified in Contract Specify if mock-up of architectural concrete Not Accepted.
Documents, surface quality and is to match an architectural concrete Committee believes checklist
appearance of mockup shall match reference sample or a . S specifyic is clear on the language to
a reference sample or portions of location(s) in a designated existing specify where on the project
an existing structure designated by structure. of architectural concrete reference the mock-up is to be located.
Architect/Engineer. in Contract Documents. Accepted. Editorial.
10.6 Item 7, Ref 388 (related to 6.1.4.5), negative by Hover. There was a motion made by DeCarlo
and seconded by Toon to find the voter non-persuasive because there is a definition already
established for “acceptance”. The word “periodic” simply refers to frequency which is a
variable from project to project and should be established in the required preconstruction
conference. 301 states that periodic acceptance does not constitute final acceptance which can
only be achieved after the work has been completed. The motion passed by a vote of 25-2-1.
10.7 Item 7, Ref 388 and 389, negative by McCall, Carino, and Lobo. Lobo and McCall withdrew
their negatives on Ref 389. There was a motion made by DeCarlo and seconded by Carino to
find the McCall persuasive on Ref 388 and to accept a substantive change. The motion passed
by a vote of 26-0-1.
6.1.4.4.a Construct field mockups using same procedures, RESPONSE TO TAC
equipment, and materials that will be used for production Accepted.
of architectural concrete. Accepted field mock-up shall Substantive Change.
will serve as the reference to which concrete will be
compared to which architectural concrete will be
compared for periodic and final acceptance. Provide field
mockups representative of the expected quality that will
be achieved during production of architectural concrete.
Construct field mockups at an acceptable location on site.
Provide a simulated repair area to demonstrate an
acceptable repair procedure. Repair procedure shall will
be suitable to provide an acceptable color and texture
match. Protect from physical damage and retain the
mockups until final acceptance of architectural concrete.
RESPONSE TO TAC
Not Accepted.
Substantive Change.
The added sentence is not of value and
hinges on the word quality. The existing
wording states that a field mockup is made
with the procedures that will be used for the
structure and that it has to satisfy the Owner.
19
Minutes of the Kansas City Convention, 2015
10.8 Item 9, Ref 449, negative by Prenger. There was a motion made by Gajda and seconded by
Toon to find the voter persuasive and to accept a substantive change and change response to
TAC. The motion passed by a vote of 26-0-0.
8.1.3 Temperature limits— OPTIONAL RESPONSE TO TAC
Unless otherwise Specify if alternative maximum temperature limit in Not Accepted.
specified, the following concrete after placement can be other than 158°F. This is important
temperature limits shall Maximum temperature is limited to minimize future information that is not
apply for mass concrete durability concerns due to delayed ettringite formation readily found
placements: [DEF] and potential reductions in ultimate strength. elsewhere and
(a) the maximum A maximum temperature limit of 170°F can be used if specifiers/users
temperature in concrete the concrete mixture consists of portland cement and appreciate having this
after placement shall not any one of the following as a percentage of total in the document.
exceed 158160°F; and cementitious materials: Additionally, this
(b) the maximum a. At least 25 percent by mass of ASTM C618 class F information is similar
temperature difference fly ash, or to that published in
between center and surface b. At least 35 percent by mass of ASTM C618 class C ACI 301-10.
of placement shall not fly ash, or
Substantive Change.
exceed 35°F. c. At least 35 percent by mass of ASTM C989 slag
cement, or
d. 10 percent by mass of ASTM C618 class N
metakaolin, or
e. At least 35 percent by mass consisting of a
combination of ASTM C618, Class C or F fly ash or
ASTM C989 slag cement, and at least 6 percent ASTM
C1240 silica fume (maximum 10 percent).
For the purpose of determining the total cementitious
materials content in a concrete mixture, add the total
mass of Portland cement, fly ash, slag cement,
metakaolin, silica fume, and powdered limestone in the
concrete mixture. For blended cements, count the
individual component materials separately.
Additionally, a maximum temperature limit of 180°F
can be used when the requirements for the 170°F
maximum temperature limit are met, and all of the
following additional requirements are met:
1. The placement is protected from moisture.
2. The placement is not in contact with the ground
3. The concrete in the placement has a water
cementitious material ratio less than 0.38
Specify if maximum temperature difference limit in
concrete after placement can be other than 35°F. The
temperature difference must be limited to minimize
thermal cracking. A higher temperature difference limit
may be acceptable depending on concrete properties,
placement dimensions, and reinforcement configuration.
The temperature difference limit for a specific concrete
mixture and placement conditions can be determined
through numerical simulations and comparing calculated
thermally induced tensile stresses with current tensile
strength of concrete. Refer to ACI 207.2R for additional
guidance.
10.10 Item 9, Ref 455 and 456, negative by Carino and Malisch was tabled.
20
Minutes of the Kansas City Convention, 2015
10.11 Item 5, Ref 230 and Ref 278, negative by Krauser. There was a motion made by Prenger and
seconded by Carino to find the voter persuasive and to accept a substantive change and change
response to TAC. The motion passed by a vote of 24-0-2.
4.1.2.7 Mixture proportion adjustments— SUBMITTALS RESPONSE TO TAC
Requests for A adjustments to mixture Concrete mixtures Not Accepted.
proportions or changes in materials made Requests for adjustments to mixture Committee disagrees.
during the course of the Work, along proportions. 4.1.2.7 deals with
with supporting documentation showing Requests to adjust mixture proportions adjustments to previous
conformance with the Contract necessary for workability or consistency. submitted mixtures.
Docuements. , made during the course of If Contractor desires to decrease the Substantive Change.
the Work. cementitious materials content of the
concrete mixture after having satisfied the
requirements of 4.2.3.6, review a request
for acceptance of the proposed revised
mixture with a lower cementitious
materials content on a trial basis.
If Contractor finds it necessary to
increase the cementitious materials
content, review a request for acceptance
of the proposed revised mixture with a
higher cementitious materials content on
a trial basis.
Confirm adequacy of modified
proportions has been verified from a set
of new field test data.
4.2.3.5 Field verification of OPTIONAL RESPONSE TO TAC
selected mixture proportions—If Specify if field verification of concrete
Accepted.
required, conduct field verification of the mixtures is required. Specify method
Substantive Change.
effects of placement methods on concrete for sampling at point of placement.
mixture characteristics. Using materials
and mixture proportions accepted for use SUBMITTALS
in the Work, verify that concrete can be Requests for adjustments
placed using the intended placing to mixture proportions.
method. Place concrete mixture using
Project equipment and personnel.
Evaluate the effect of placement
methods on slump and air content.
Verify that slump and air content
obtained at the point of placement
are acceptable. Make suitable corrections
to the placing methods or to mixture
proportions, if needed. Submit
adjustments to mixture proportions.
21
Minutes of the Kansas City Convention, 2015
10.12 Item 5, Ref 254, negative by Gajda and Lobo. Gajda withdrew Part 2 of his negative. There was
a motion made by Prenger and seconded by Gajda to find the voters persuasive and to accept a
substantive change. The motion passed by a vote of 23-0-4.
4.2.2.7.b Freezing and thawing resistance— MANDATORY Accepted.
Unless otherwise specified, provide concrete Designate in Contract Substantive Change.
meeting the requirements of Table 4.2.2.7.b Documents the exposure
based on exposure class assigned to class for portions of the
members for freezing and thawing exposure in structure requiring
the Contract Documents. Submit resistance to freezing and
documentation verifying compliance with thawing. For exposure class F3,
specified requirements. indicate if it is plain concrete.
Refer to ACI 318 for additional
guidance.
OPTIONAL
Specify alternative mixture
requirements for freezing and
thawing resistance.
Table 4.2.2.7.b—Requirements For Exposure Category Substantive Change from
F: Freezing and thawing exposure Ref 4.
Table 4.2.2.7.b
Exposure Maximum Minimum Additional Changes to reflect
class w/cm* fc, psi Air content requirements 318-14
F0 NA 2500 NA
Table
F2 0.45 4500 NA
4.2.2.7.b.1
F3
Table Table
Plain .45 4500
4.2.2.7.b.1 4.2.2.7.b.2
Concrete
10.13 Item 6, Ref 319, negative by Malisch. There was a motion made by Prenger and seconded by
Toon to find the voter persuasive and accept a substantive change and change response to TAC.
Will take topic of surface temperature as new business. The motion passed by a vote of 21-0-1.
5.3.2.1.b Cold weather— Concrete OPTIONAL RESPONSE TO TAC
temperatures at delivery shall meet the Not Accepted.
Specify minimum temperature of
requirements of 4.2.2.5. Do not place Substantive Change.
reinforcing steel before placing
concrete in contact with surfaces less than Will take up surface
concrete. See ACI 306R for
35°F. temperature as new business
additional guidance.
Unless otherwise specified, this requirement in next cycle after 306
shall not apply to reinforcing steel. document is published.
22
Minutes of the Kansas City Convention, 2015
10.14 Item 5, Ref 320, negative by Malisch was withdrawn. The temperature limit will be taken up as
new business.
10.15 Item 6, Ref 321, negative by Malisch was withdrawn and item will be taken up as new business.
10.16 Item 6, Ref 322, negative by McCall. There was a motion made by Prenger and seconded by
Greene to find the voter persuasive and to accept a substantive change and change response to
TAC. The word continuously will be taken up as new business. The motion passed by a vote of
18-0-4-1. Prenger made a motion and Greene seconded to find the negative voters non-
persuasive because there is not currently a better term for continuously used in our industry. The
motion passed by a vote of 17-5-1.
5.3.2.4.a Deposit concrete in a manner that RESPONSE TO TAC
does not result in cold joints continuously and Not Accepted.
as near as practicable to the final position. Substantive Change.
Keep original language and will take up
the term “continuously” as New Business.
10.17 Item 6, Ref 323, negative by Malisch. There was a motion made by Prenger and seconded by
Greene to find the voter persuasive and to accept a substantive change and change response to
TAC. The motion passed by a vote of 23-0-0.
5.3.2.4.b Deposit concrete in one layer RESPONSE TO TAC
or in multiple layers. Do not place Not Accepted.
fresh concrete against concrete that has Substantive Change.
achieved a degree of setting that would We argued out “degree of setting” in several
result in cold joints unless construction meetings and decided to keep the language.
joint requirements of 5.3.2.6 are met. Take up as new business to find better terminology
to describe when a cold joint might form.
10.19 Item 4, Ref 199, negative by Carino. There was a motion made by Turner and seconded by
Toon to find the voter persuasive and to accept a substantive change and change response to
TAC. The motion passed by a vote of 21-0-0.
3.2.1.6 Wire—Use plain or deformed wire as indicated OPTIONAL RESPONSE TO TAC
in Contract Documents. Plain and deformed wire shall Specify if plain or deformed Not Accepted.
conform to one or more of the specifications given in wire is to be used in Welded Wire
3.2.1.6.a through 3.2.1.6.d. Plain wire is acceptable for structure. reinforcement is
spirals. MANDATORY addressed in 3.2.1.7.
3.2.1.6.a Plain or deformed steel wire shall conform to Specify the following for Substantive Change.
ASTM A1064/A1064M. A82/A82M. wire reinforcement:
3.2.1.6.b Deformed wire size D4 and larger shall (i) material specification,
conform to ASTM A496/A496M. (ii) wire size
3.2.1.6.d Stainless steel wire shall conform to ASTM (iii) if applicable, special
A1022/A1022M. minimum yield strength
3.2.1.6.c Epoxy-coated wire shall conform to ASTM A (iv) additional specification
884/A 884M. Coating damage incurred during for galvanizing or epoxy
shipment, storage, handling, and placing of epoxy- coating.
coated wires shall be repaired . Repair damaged coating
areas with patching material in accordance with ASTM
A884/A884M material manufacturer’s written
recommendations. If damaged area exceeds 2 percent
of surface area in each linear foot of each wire, wire
shall not be used.
23
Minutes of the Kansas City Convention, 2015
10.21 Item 4, Ref 203, negative by McCall. There was a motion made by Turner and seconded by
Toon to find the voter persuasive and to accept a substantive change. The motion passed by a
vote of 21-0-0.
3.2.1.7 Welded wire reinforcement—If OPTIONAL RESPONSE TO TAC
specified in Contract Documents, use welded Specify sheets or rolls of plain or Accepted.
wire reinforcement Use welded wire deformed welded wire reinforcement Substantive Change.
reinforcement specified in Contract and, if required, epoxy-coated or
Documents and conforming to one of the stainless steel welded wire
specifications given in 3.2.1.7.a through reinforcement. Refer to WRI Manual
3.2.1.7.e. of Standard Practice for additional
3.2.1.7.a Plain welded wire reinforcement guidance.
shall conform to ASTM A1064/A1064M MANDATORY
A185/A185M, with welded intersections Specify the following for welded
spaced no greater than 12 in. apart in wire reinforcement:
direction of principal reinforcement. (i) material specification,
3.2.1.7.b Deformed welded wire (ii) sheets or rolls,
reinforcement shall conform to ASTM (iii) wire size and spacing
A1064/A1064M A497/A497M, with welded (iv) if applicable, special minimum
intersections spaced no greater than 16 in. yield strength
apart in direction of principal reinforcement. (v) additional specification for
galvanizing or epoxy coating
10.22 Item 4, Ref 208, negative by Carino. There was a motion made by Turner and seconded by
Toon to find the voter persuasive and to accept a substantive change and change response to
TAC. The motion passed by a vote of 21-0-0.
3.2.2.2.a If welding of steel OPTIONAL RESPONSE TO TAC
reinforcement is specified, comply If desired, specify requirements for welding Not Accepted.
with AWS D 1.4/D 1.4M unless preparation (such as removal of zinc or
Committee will consider as
otherwise specified. Do not tack epoxy coating) more stringent than those in
new business for next cycle.
weld reinforcement. AWS D 1.4/D 1.4M.
Welded assemblies of steel Specify desired requirements for chemical Substantive Change.
reinforcement produced under composition of reinforcing bars more
factory conditions, such as welded stringent than ASTM specifications. Specify
wire reinforcement, bar mats, and special heat treatment of welded assemblies,
deformed bar anchors, are allowed. if required. Specify supplementary
requirements for welding of wire to wire,
and welding of wire or welded wire
reinforcement to reinforcing bars or
structural steel elementssteels.
10.23 Item 4, Ref 216, negative by Malisch, Carino, and McCall. There was a motion made by Turner
and seconded by Toon to find the voter persuasive and to accept a substantive change and
change response to TAC. The motion passed by a vote of 18-0-0.
3.3.2.5 Welded wire reinforcement— For OPTIONAL RESPONSE TO TAC
slabs-on-ground, edge of welded wire If welded wire reinforcement sheets are Accepted.
reinforcement shall be no farther from to be used, specify method of lapping at Substantive Change.
formed edge of slab than greater of (a) edges and ends of sheets. Specify where
specified cover, and (b) 2 inches. Lap welded wire reinforcement may extend
24
Minutes of the Kansas City Convention, 2015
splice edges and ends of welded wire through control movement joints,
reinforcement sheets as indicated in including sawcut joints.
Contract Documents. Unless otherwise MANDATORY
specified, do not extend welded wire Specify method of lapping at edges and
reinforcement through control movement ends of reinforcement. sheets.
joints. OPTIONAL
For slabs-on-ground, edge of welded wire For welded wire reinforcement sizes
reinforcement shall be within 2 in. of smaller than D11 or W11, specify if
formed concrete edge, but not closer than rolled wire reinforcement is acceptable
specified cover.
Place, support, and secure welded wire MANDATORY
reinforcement in accordance with CRSI Specify required tolerance on placement.
RB4.1 to maintain positioning in slab Refer to WRI Manual of Standard
during concrete placement. Practice for additional guidance.
Respectfully Submitted,
Michelle L. Wilson
Secretary, ACI 301
25