Professional Documents
Culture Documents
General Specification
ENGINEERING GMW15867
HVAC & PT Cooling
STANDARDS
behind the burst device e.g. evaporator. On the The refrigerant temperature during operation is
high pressure side excessive operating pressure is between (-12…+165) °C and +180 °C short term
caused by malfunction of high pressure limitation (5 minutes max. each for a total of 168 h).
of the compressor. 3.1.3.2 Low Pressure Side The pressure relieve
Each pressure relieve device shall operate device shall not be located near the hot engine or
automatically. No other methods by mechanical, other heat source underhood, therefore, the
thermostatically and electrical control are allowed environmental temperatures are in the range of
to use for the activation of the pressure relieve • -40 °C in switched off condition and/or
device.
• -12 °C during refrigeration system operation to
The most important differences between the relief
valve and the burst device are: • +120 °C permanent to
• Lower component strain than by explosive • +135 °C short term (5 minutes max. each for a
decompression, because normally the system total of 168 h)
is not completely emptied to ambient pressure The refrigerant temperature during operation is
level. between (-12…+80) °C.
• Because the relief valve closes at a certain 3.1.4 Interfaces.
pressure the system normally never run 3.1.4.1 High Pressure Side. Pressure relieve
without refrigerant. devices shall in principle be integrated in the
• The noise level in case of relief valve system directly or close to the pressure source.
response relative to burst device response is The relief valve and/or the burst device on the high
lower. pressure side are therefore part of the
compressor.
• The function of the relief valve shall be tested
without damaging the relief valve. 3.1.4.2 Low Pressure Side. Additionally another
pressure relieve device shall be provided on the
3.1.3 Ambient Environment and Operating
low pressure side because of the maximum
Conditions. This defines the ambient
operating pressure on the low pressure side.
temperatures and refrigerant temperatures which
the components are exposed to. As orientation the In compliance with SAE J639, overpressure by
following values are defined for operating and non overcharging and also by blocking shall be
operating AC system. If the AC system is switched avoided, therefore, the relief valve or burst device
off the ambient conditions are equal to on the low pressure side shall be located
environment temperatures which are relevant for upstream directly after the expansion device and
the design and construction of the pressure relive before the evaporator.
devices. 3.1.4.3 Non-Interchangeability. The pressure
3.1.3.1 High Pressure Side. The pressure relieve control devices for high and low pressure side are
device shall be mounted directly in the compressor not allowed to interchange one another. Therefore
as part of compressor assembly. Due to the typical the outside design of the pressure control
location of the compressor is near the hot engine, elements shall be so different that mismatch is
therefore, the environmental temperatures are in impossible. A metric fine left threat shall be used
the range of: for high pressure side with size M12x1 and for low
pressure side with size M14x1. A hexagonal bolt
• -40 °C in switched off condition and/or
head without thread marking is required.
• -12 °C during refrigeration system operation to 3.1.4.4 No Cross Section Reduction. When
• +130 °C permanent to installing the pressure relieve devices in the
• +150 °C short term (5 minutes max. each for a respective AC pipe and compressor, the detail
total of 168 h). dimensions of the interface shall be reviewed
carefully to ensure that the end plugged into the
For special application - extreme hot - which shall
line and the housing of the compressor does not
be defined by GM
negatively influence the flow cross section of the
• -40 °C in switched off condition and/or medium. The reduced cross section of the flow
• -12 °C during refrigeration system operation to path will cause pressure losses. Such pressure
losses are not allowed for the normal function of
• +150 °C permanent to
the pressure relieve device.
• +180 °C short term (5 minutes max. each for a
total of 168 h).
3.1.5 Safety and Usage Definition. The change of response pressure shall be in the
installation location of both pressure relieve direction of lower pressures, whereby complete
devices shall be selected to assure that refrigerant resealing shall further be assured. The emptying
blow-off is outside the passenger compartment of the system shall be 250 kg/h.
including AC unit, air intake and luggage Especially for burst device: The emptying of the
compartment. AC system to closely ambient pressure level
Additionally, the installation locations and blow-off depends on drain diameter and design. The initial
directions of the pressure relieve devices shall be emptying speed of the AC system shall be
such that personal injury of persons near the 5 MPa/s. As initial pressure the response pressure
vehicle and the system is not possible in case of of the burst device may be used.
refrigerant blow-off. The burst sound level shall be 3.2.1.2 Leak Rate. The R744 leak rates of the
such that no personal injury of persons near the pressure relieve devices are limited to a value of
vehicle and the system is possible. 1 g/year maximum.
The integration of the pressure relieve devices into These leak rates are determined according to the
a third component, e.g. expansion device or load collectives shown in Appendix A, Table 1 for
connector block, shall be in such a way that the the low pressure side and in Table 2 for the high
pressure relieve devices is from the outside of the pressure side.
component removable. To avoid that the pressure
The pressure relieve devices shall be installed as
relieve device will be opened or will be replaced
follows:
inappropriately e.g. through a screw, a warning is
required on the pressure relieve device. The • HD: High Pressure side in test block e.g.
warning shall say e.g.: Do not remove or the compressor block without further leakage
corresponding ‘ISO symbol’ shall be used. points such as tube connections and shaft
3.2 Product Characteristics. The test seal on it.
temperature for the following physical tests is • ND: Low Pressure side in test block e.g.
(+23 ± 5) °C according to DIN 50014 unless refrigerant pipes or expansion device without
otherwise specified. further leakage points.
A minimum of 5 test samples are required for each The measurement is made with a mixture of R744
test. and the refrigerant oil specified. The ratio of the
The test results shall be documented as part of mixture of R744 and the oil shall be same as the
PPAP documents to GM. specified value of the AC system of the vehicle.
After filling the test block, compressor block etc.
3.2.1 Performance Requirements. The minimum the test unit shall be shacked to allow the oil being
response pressures at which the pressure relieve on the entire internal surface.
devices shall respond at the earliest are:
Each load condition shall be maintained until a
• 15 MPa on the high pressure side (HD) steady-state condition of the leakage reached, but
• 11 MPa on the low pressure side (ND) at least 48 h. Leakage shall be determined in a
The pressure relieve devices shall be open system evacuated as required. C02 leakage is
completely and at which the pressure in the determined with a mass spectrometer and/or an
refrigerant circuit shall not increase any further equivalent leak detector. The average leak rate
are: shall be determined as follows:
n
• 17 MPa on the high pressure side (HD)
VR m = ∑ VRi ⋅ Gewi
• 13 MPa on the low pressure side (ND) i =1
The response pressure (RP) intervals of the VRm average leak rate of the sample
pressure relieve devices are:
• 15 MPa < RP for HD side < 17 MPa VRi leak rate in the load condition i
• 11 MPa < RP for ND side < 13 MPa Gewi weighting factor for the load
Especially for relief valves: The relief valve shall condition i
close at a pressure, which is 1.2 MPa below the Compliance with these requirements shall be
response pressure. After ten responses the assured after all function tests and for the entire
response pressure shall be still within the specified vehicle life cycle.
response interval. After each response, the relief
valve shall return to a safe condition, i.e., the
Especially for Relief Valve: After five responses Test conditions for low pressure side:
the leak rate may increase to 1.5 g/year. After • pressure cycles: 150 000
> 10 actuations the leak rate may increase to
2 gram/year maximum. • test duration: 292 h (150 000 x 7 s)
Repeated leak rate test: The repeated leak rate • test pressures: (2.5…9) MPa abs.
test is made under the load condition No.3 and • test medium: hydraulic or refrigerator oil
shall be used for the single and series tests which • temperature of test oil: (+80 ± 2) °C
will be defined later.
Test conditions for high pressure side without
The leak rate determined according to creeping:
Appendix A, Table 1 and Table 2 (at standstill
+30 °C and a system pressure of 7 MPa) is • pressure cycles: 150 000
defined as the base leakage for the pressure • test duration: 292 h (150 000 x 7 s)
relieve device. This value shall not be exceeded • test pressures: (5…14.5) MPa abs.
during all repeated leak rate tests. The tolerance is
set to 20 %. The load condition shall be • test medium: hydraulic or refrigerator oil
maintained for 48 h according to this paragraph. • temperature of test oil: (+155 ± 2) °C
3.2.1.2 Resistance to Under Pressure/Vacuum. The timing of the pressure cycles for high and low
The pressure relieve devices shall be installed pressure side as shown in Figure 1, the duration of
according to paragraph 3.2.1.1 in test blocks the pressure ramp is 0.5 s and of the holding
which are completely sealed to the environment by pressure is 3 s.
soldering. A vacuum of 0.5 kPa absolute shall be Figure 1: Pressure cycles for high and low
applied to the pressure relieve devices and pressure side without creeping
maintained constant for 5 minutes. The allowed
< 0.5 3s
pressure increase shall not exceed 0.5 kPa within
30 minutes and with pump switched off.
During this test function shall not be impaired.
Pressure in MPa
During the creeping test function the pressure pressures are 14 MPa for the high pressure side
relieve valve shall not be impaired nor the form and 10 MPa for the low pressure side. The test
malleable changed. shall be performed at room temperature.
After this test, the leak rate test according to The test sample is exposed to a sinusoidal
paragraph 3.2.1.1 shall be repeated and the vibration in vertical direction as follows:
respond pressure according to paragraph 3.2.1.3 • frequency 20 Hz sinusoidal
shall be repeated.
• No. of cycles: 3.6 x 106 (duration 50 h)
3.2.1.5 Temperature Cycling Test. The pressure
relieve devices shall be tested in the condition • acceleration: ± 31.4 m/s2 (this shall be result
assembled with the pipe, expansion device and/or to a amplitude: ± 2 mm)
the compressor as follows: After this test, the leak rate test according to
Fill the test sample with test medium hydraulic or paragraph 3.2.1.1 shall be repeated and the
refrigerator oil and apply following pressure: respond pressure according to paragraph 3.2.1.3
shall be repeated.
ND: low pressure side 10.5 MPa
If functional component parts made from plastic:
HD: high pressure side 14.5 MPa Subsequently this test shall be made in the cold
The temperature cycle intervals are: chamber at -20 °C and a pressure 2 MPa with the
• ND: from [(-40…+120) ± 2] °C other conditions remaining the same.
• HD: from [(-40…+160) ± 2] °C After this test, the leak rate test according to
paragraph 3.2.1.1 shall be repeated and the
The soak and/or cooling speed is ±1 °C/minute.
respond pressure according to paragraph 3.2.1.3
The holding time at the min/max values are shall be repeated.
30 minutes each, the total cycle duration:
3.2.1.7 Corrosion Test. The salt spray tests are
• HD: 460 minutes (30 – 200 – 30 – 200) accelerated corrosion test of the pressure relieve
• ND: 380 minutes (30 – 160 – 30 – 160) devices using a cyclically sprayed aqueous, acetic
Total test duration: sodium chloride solution as corrosion agent.
• HD: 77 h 10 cycles The corrosion test shall be performed 20 days
according to:
• ND: 63 h 10 cycles
• SWAAT ISO 9227
After this test, the leak rate test according to
paragraph 3.2.1.1 shall be repeated and the and 24 weeks according to
respond pressure according to paragraph 3.2.1.3 • Alternating Climatic Corrosion Test to
shall be repeated. ISO 9227
3.2.1.6 Vibration Test. For the vibration test the Both tests are described in Appendix A Table 3
pressure relieve devices shall be installed and Table 4.
according to paragraph 3.2.1.1 in test blocks The pressure relieve devices shall be leak tight
which are completely sealed to the environment by over the total test. After the test no functional
soldering. failure shall be occur due to corrosion.
The test sample shall be filled internally with water
or refrigerant oil to a level of 30 % and after with
nitrogen in the space above. The average
© Copyright 2008 General Motors Corporation All Rights Reserved
After this test, the leak rate test according to The leak rate test according to paragraph 3.2.1.1
paragraph 3.2.1.1 shall be repeated and the shall be repeated after each response. In this
respond pressure according to paragraph 3.2.1.3 case, the test time may be reduced to 6 h.
shall be repeated. 3.2.2 Physical Characteristics.
If aluminum parts are used an even surface 3.2.2.1 Dimensions and Capacity. The
corrosion and/or shallow pitting corrosion is dimension of the pressure relieve devices shall be
permitted with a wall thickness up to 30 %. Pitting designed together with the component in which
corrosion and other corrosion mechanisms e.g. the device will be integrated.
inter-crystalline corrosion are not allowed.
3.2.2.2 Mass Properties. The mass of the
3.2.1.8 Decompression Test. In case an pressure relieve device on the low pressure side
elastomer is in direct or indirect contact with the shall not exceed 50 g and of the high pressure
refrigerant, a decompression test shall be made. side 75 g.
The pressure relieve device shall be assembled 3.2.3 Dependability.
with a test block as described in
3.2.3.1 Target Life. Due to the fact that the
paragraph 3.2.1.1. With a suitable fixture the
pressure relieve devices are safety components
pressure relieve device is kept open permanently,
the function of the pressure relieve devices shall
such that the elastomers shall be tested in direct
be assured for an average vehicle life of at least
contact with the refrigerant.
15 years and/or 300 000 km and/or
The pressure relieve devices are exposed to a 6200 operating hours.
pressure of 14 MPa for high pressure side and
For pressure relief valve: At least ten times of the
10 MPa for low pressure side at a temperature of
responses or the resealing within the activation
+130 °C.
interval shall be assured for the vehicle life. After
For the actual compression test the pressure is this test, the relief valves shall return to a “safe
reduced to environment level within < 10 s. condition“, i.e., the change of the response
Malfunctions are not allowed. pressure shall be towards lower pressures only,
After this test, the leak rate test according to whereby the defined leak rate shall further be
paragraph 3.2.1.1 shall be repeated and the assured.
respond pressure according to paragraph 3.2.1.3 The function of pressure relieve valve seals shall
shall be repeated. be assured for vehicle life time.
3.2.1.9 Minimum Number of Relief Valve blow- 3.2.3.2 Class 1 and Class 2 Type Problems.
off. After ten responses, the response pressure of 3.2.3.2.1 Class 1 Type. Not applicable.
the relief valves shall be still within the specified
3.2.3.2.2 Class 2 Type. Not applicable.
response interval.
3.2.3.3 Reliability Requirements. Not applicable.
The response intervals according to paragraph
3.2.1.3 are: 3.2.4 Serviceability. The pressure relieve devices
of high and low pressure side shall not be
• 15 MPa < PR < 17 MPa high pressure side
interchangeable and shall therefore be at least of
• 11 MPa < PR < 13 MPa low pressure side different outer designs, see paragraph 3.1.4.3.
To inspect the repeatability of the blow-off Both pressure relieve devices shall be installed
process, a test shall be performed with a such that a visual inspection is possible in vehicle
refrigerant/oil mixture with 5 % oil content. The service. At the same time it shall assured that
response valve pressure is uniformly increased at there is no risk of injury for service personnel due
a rate of (0.8…1.0) MPa/s until the valve opens. to refrigerant blow-off or due to burst sound level.
The pressure shall be reached within the The orientation of the pressure relieve device shall
respective response interval. be controlled in the packaging design.
Compliance with these requirements shall be Removal of the pressure relieve devices from the
assured after all function tested including ten outside of the component shall be possible without
responses. special tools.
After this test, the test pressure shall be reduced 3.2.5 User System/Subsystem/Component/Part
until the relief valve closes. The pressure resulting Interface. Not applicable.
shall not be more than 1.2 MPa below opening
pressure.
3.3 Design and Construction. The pressure utilizing the Part Recyclability / Recoverability
relieve devices shall be designed such that Report Form. Reference Appendix A of
external influences (temperature, weather, dirt, GMW3116, Recyclability, Recoverability
etc.) do not impair their function. Under certain Guidelines.
circumstances a protective cap and/or shield shall Suppliers shall be use Statistical Process Control
be provided, which shall not negatively impact the (SPC) in all critical areas as determined by the
pressure relief function of the refrigeration circuit vehicle platforms. The hose suppliers and hose
(reduction of cross section, icing, etc.). couplers shall maintain records of audits and SPC
Sealing of the pressure relieve devices shall be data for at least three years. These records shall
metallic, i.e., without elastomers. be available to the vehicle platforms and the
Especially for relief valves only: For the relief Global T/HVAC Center. Also, the hose supplier
valves used, it shall be assured that the relief bore records shall be available for the hose coupler.
is not plugged by icing in case of refrigerant blow- 3.3.1.3 Parts Guidelines. The component shall be
off. compatible with all climatic and driving conditions.
3.3.1 Materials, Processes and Parts Selection The function of the component shall be fulfilled
Guidelines. any time.
3.3.1.1 Material Guidelines. All the materials The components shall not be contaminated with
used shall be in compliance with the applicable residues, such as deposits, scale, cuttings and
GM material standards and the drawing grease. The maximum permissible contaminations
requirements. due to flushable, soluble and solid residues shall
be 10 mg/m2 (unless otherwise specified), with
Materials used shall be hazardous to human
respect to the internal surface. 40 % max. may be
health and environment not at any time during the
soluble and 60 % max. insoluble. The size of the
components life cycle.
internal surface is determined from the appropriate
The component shall be compatible externally with drawing for the component. The test shall be
oil, fuel and any other media used in vehicles and performed according to DIN 8964.
internally with each media used for the AC system 3.3.2 Design Guidelines and Constraints. The
per GM engineering (oil, refrigerant, odorant).
component shall be designed in compliance with
The inner surfaces of the component shall be the GM drawing requirements. GM part numbers
clean without any manufacturing residues, which and the drawings shall be used for GM production.
may be dissolved during operation by refrigerant
Compliance with the characteristics described in
R744 or the respective compressor lubricant and
the functional description in addition to those in the
result in contamination and/or plugging of the
drawing is the responsibility of the supplier if the
refrigerant circuit.
pressure relieve device.
For component design and packaging design, the
Statistical methods shall be used to demonstrate
underhood condition affected by temperature
compliance by the supplier.
(engine radiation), weather (salt in the winter
time), mechanical loads (rough track) and The supplier shall ask for the valid version.
comparable factors shall be considered. Neither Detailed design and process Failure Mode and
function nor service life of the pressure relieve Effects Analysis (FMEA) shall be submitted to the
devices shall be impaired. release engineer which will be maintained as part
3.3.1.2 Processes Guidelines. The supplier shall of the records of the Design and Product
provide DFMEA and PFMEA to GM for review and Validation. The FMEA shall be updated each time
discussion. The design FMEA shall include a change occurs. FMEA shall be submitted with
particularly computational demonstration of the GM PPAP documentation
compliance of strength and service life and 3.3.3 Identification and Marking. The pressure
tolerances analyses of the components. relieve devices shall be permanently identified with
Development and manufacture to ISO 9001 the date of manufacture of the assembly,
standard shall be assured. manufacturer's identification, manufacturing
location and assembly part number.
Materials developed to this standard shall be
optimized to provide maximum end-of-life cycle All pressure relieve devices shall be marked with
value utilizing the Vehicle Recyclability / the appropriate GM part no. to GME14090.
Recoverability Calculation Sheet. Recycled
content shall be reported to the approving and
procuring Materials Engineering Department
© Copyright 2008 General Motors Corporation All Rights Reserved
3.3.4 Workmanship. Due to the high pressures 4.2 Validation Cross Reference Index.
inherent with R744, testing shall be only 4.2.1 Combined Test. This is an aging test using
performed by properly trained personnel using the tests described above in the following
equipment capable of these tests with adequate sequence:
safety margins. All material shall be used in
accordance with the supplier Material Safety Data • 50 % of Pressure cycling
Sheet (MSDS). • 50 % of Temperature cycling
3.3.5 Interchangeability. See paragraph 3.1.4.3. • 50 % of Vibration test
3.4 Documentation. Samples of components or • 10 days SWAAT salt spray test
material released to this standard shall be tested • 50 % of Pressure cycling
for conformity with the requirements of this
standard and approved by the responsible GM After this test, the leak rate test according to
Department prior to the start of delivery of paragraph 3.2.1.1 and the respond pressure
production level components or materials. according to paragraph 3.2.1.3 shall be repeated.
Any change to the component or material e.g., 4.3 Supporting Paragraphs.
design, function, properties, manufacturing 4.3.1 Chemical requirements. Compliance with
process and/or location of manufacture requires a the requirements to dryness and interior and
new release of the product. It is the sole exterior cleanliness is required in assembly with
responsibility of the supplier to provide the the compressor, expansion device and/or
customer, unsolicited, with documentation of any refrigerant pipe or expansion device.
change or modification to the product/process, and 4.3.2 Interior Cleanliness. The internal parts of
to apply for a new release. pressure relieve device shall be free of all
If not otherwise agreed to the entire verification contamination that could impair the operation
test shall be repeated and documented by the and/or the performance of the assembly, such as
supplier prior to start of delivery of the modified or metal particles, dirt, foreign material, and residual
changed product. In some cases a shorter test manufacturing material.
may be agreed to between the responsible GM The internal parts of pressure relieve device shall
Department and the supplier. contain zero moisture as received by GM.
3.4.1 Test Results. With reference to this The internal parts of pressure relieve device shall
standard the measurement results shall be be free of burrs, sharp corners, etc. which may be
summarized in a test report. detrimental to assembly and function.
3.4.2 Deviations from Test Procedure. All the definitions of interior cleanliness of GM
Deviations from the requirements of the test technical specification of R134a components shall
procedures shall have been agreed upon. Such apply to this standard.
requirements shall be specified on component The soluble and solid residues which can be
drawings, test certificates, reports etc. washed away with solvent shall not exceed
3.5 Support of System/Subsystem/Component/ 10 mg/m2 (unless otherwise specified) and shall
Part After Sale. Not applicable. not contain any abrasive materials. All residues
3.6 System/Subsystem/Component/Part shall be < 15 mg/part.
Operator Training. Not applicable. The measures shall be performed according to
3.7 System/Subsystem/Component/Part DIN 8964 C1 and C2.
Characteristics. Not applicable. Abrasive materials are not allowed. The particle
3.7.1 System/Subsystem/Component/Part size shall be 60 µm (depending on
Definition. Not applicable. R744 compressor standard) unless otherwise
specified.
4 Validation 4.3.3 Exterior Cleanliness. The exterior surface
4.1 General. The test temperature for the of the pressure relieve devices shall be
following physical tests is (+23 ± 5) °C according 30 mg/part of residues, lubricants and any other
to DIN 50014 unless otherwise specified. contaminants.
The validation report shall be delivered to GM. The assembly and component parts shall be free
of all contamination that could impair the operation
Statistical test validation method shall be used to and/or the performance of the assembly, such as
ensure the required relieve burst pressure. metal particles, dirt, foreign material, and residual
manufacturing material.
© Copyright 2008 General Motors Corporation All Rights Reserved
The assembly shall contain zero moisture as 5.1 Shipping Caps. All assemblies shall have
received by GM. shipping caps, as specified by the detail drawing
The assembly and component parts shall be free which maintain a fully installed position, until the
of burrs, sharp corners, etc. which may be hose / pressure relieve valve / compressor etc.
detrimental to assembly and function. assembly is installed into a final system assembly.
The shipping caps shall be according to
4.3.4 Quality Assurance in Production. The test
GM10009C. During removal, there shall be no
temperature for the following physical tests is
degradation of features as represented by the
(+23 ± 5) °C according to DIN 50014 if not
detail drawings. This would include but not be
otherwise specified.
limited to, dislodging of sealing mechanism (if
The validation report shall be delivered to the required), damage to threads or sealing areas.
responsible GM department.
4.3.4.1 Response Pressure for Valves. Each 6 Notes
part (100 %) shall be tested when it is installed 6.1 Glossary. Not applicable.
into its component (compressor, lines, expansion
device) similar to paragraph 3.2.1.1. 6.2 Acronyms, Abbreviations, and Symbols.
To inspect the blow-off, the component is filled
with R744. The pressure is uniformly increased at AC Air Condition
a rate of (0.5…0.1) MPa/s until the valve opens. CASS Copper-Accelerated Salt Spray
The pressure reached shall be within the
respective response interval: CDS Component Data Standard
• 15 MPa < PR < 17 MPa high pressure side DFMEA Design Failure Mode effect Analysis
• 11 MPa < PR < 13 MPa low pressure side FMEA Failure Mode effect Analysis
4.3.4.2 Response Pressure for Burst Devices.
Statistical test validation method shall be used to HD High pressure side
ensure the required relieve burst pressure. As an LSL Lower Standard Limit
example the statistical method is shown in
Appendix 2 for the low pressure side. For the high MSDS Material Safety Data Sheet
pressure side the parameters has to be adapted. ND Low pressure side
4.3.4.3 Leak Rate. Each part (100 %) shall be
tested when it is installed into its component PAG Polyalkylene glycol
(compressor, lines, expansion device) similar to PFMEA Process Failure Mode Effect Analysis
paragraph 3.2.1.1 at (+23 ± 5) °C with e.g. R744,
He, air. POE Polyolester
The applied pressures are for low pressure side PPAP Production Part Approval Process
9 MPa and for high pressure side 14.5 MPa. The
pressure shall be applied for 10 s. Leak detector PXV Pressure Expansion Valve
or mass spectroscopy shall be used for detection. RP Response pressure
The leak rate of 10 g/year R744 shall be proofed.
SPC Statistical Process Control
A correlation between used test medium and R744
is required. SWAAT Sea Water Acetic Acid Test
USL Upper Standard Limit
5 Provisions for Shipping
The refrigerant pressure relieve devices All physical parameters and units used refer SI
assemblies shall be compatible with commercial units; in particular it shall be observed that the
shipping by air, rail, truck. and/or boat and include pressures indicted are always absolute pressures.
retaining provisions if necessary. Degradation of Symbol Unit Description
the pressure relieve devices assemblies M R744 kg/h Refrigerant Mass Flow
appearance, performance, and/or durability due to
T R744 °C Refrigerant Temperature
shipping is not acceptable. Upon successful
completion of required manufacturing quality P R744 MPa Refrigerant Pressure
levels, the pressure relieve devices assembly shall
be prepared for delivery in accordance with the
requirements specified below:
Appendix A
A1
Table 2: Statistic Load Collectives Low Pressure Side
p t weighting factor
n load collective (ND)
in MPa in °C in %
1 standstill -30 °C 1.43 -30 4
2 standstill 0 °C 3.5 0 16
3 standstill +30 °C 7.2 +30 70
4 operation +10 °C evaporator 4.5 +45 2
5 operation 0 °C evaporator 3.5 +30 3
6 heating 7.0 +100 5
Table 3: Statistic Load Collectives High Pressure Side
p t weighting factor
n load collective (HD-hot)
in MPa in °C in %
1 standstill -30 °C 1.43 -30 4
2 standstill 0 °C 3.5 0 16
3 standstill +30 °C 7.2 +30 70
4 operation 10.0 +130 4
5 idle 13.0 +165 1
6 heating 7.0 +100 5
Table 6: Expected qualitative results of the tests at +30°C and +120°C with respect to the obtained
opening pressure of the valve
Estimated quantity Measurements at +120°C Measurements at +30°C
mean value 11.90 MPa 12.20 MPa
standard deviation s 0.16 MPa 0.14 MPa
Cp 2.08 2.38
Cpk 1.88 1.90
Figure 2: Expected qualitative results of the tests at +30 °C and at +120 °C with respect to the
obtained opening pressure
LSL USL
0.35
0.25
0.2
s
0.15 s
0.1
0.05
0
110 112 114 116 118 120 122 124 126 128 130
1 n
Eq 1: x= ∑ xi
n i =1
(sample size n = 125)
Eq 2: s=
1 n
n − 1 i =1
(
∑ xi − x )2
(sample size n = 125)
Example:
Table 7: Cpk values and corresponding number of parts out of the specification limits in ppm (parts
per million), worst case values are given, i.e. the distribution is assumed to be centered so that an
equally portion of parts out of the specification limits at both sides is expected.
Table 7 is added to make the meaning of the Cpk value more comprehensible.