1. INTRODUCTION • As Faraday first law of induction stated that Any change in the magnetic field of a coil of wire will cause an emf to be induced in the coil. • This emf induced is called induced emf • The magnetic field produced by a coil will be as shown in the first part of Fig. With the fluctuating nature of the alternating current, the magnetic field associated with the coil will also fluctuate. 2. TRANSFORMER EQUIPMENT • 2.1 CORE Core is constructed of cold rolled grain oriented sheet steel laminations with a high magnetic permeability and a very low no load loss. Each lamination is insulated on each side with magnesium-silicate-phosphate coating to reduce the eddy current loss. 2. TRANSFORMER EQUIPMENT • 2.2 WINDINGS Windings consist of copper conductors and solid insulation materials such as insulation paper, press board and so on. • We usually select copper conductors considering transformer capacity, permissible current, temperature rise limits and mechanical strength to withstand the electromagnetic force produced by a short circuit current without damage. • In manufacturing transformers, the most suitable winding method has to be employed according to the capacity, voltage and tap range of each transformer. 2. TRANSFORMER EQUIPMENT • 2.2 WINDINGS 2. TRANSFORMER EQUIPMENT • 2.2 WINDINGS 2. TRANSFORMER EQUIPMENT • 2.3 TAP CHANGERS • Tap changers are used to modify the voltage ratio of a transformer. This can be done by adding or subtracting the tapping winding’s turns from those of the main winding. An on-load tap changer can change tap position when the transformer is energized and carrying full load current. A de_energized tap changer must only be operated when the apparatus is isolated from the system. Tap changers’ brands and models are indicated on their name Plates,If tap voltage is to be known, it can be seen on transformer name plate 2. TRANSFORMER EQUIPMENT • 2.3 TAP CHANGERS • Tap changers are used to modify the voltage ratio of a transformer. This can be done by adding or subtracting the tapping winding’s turns from those of the main winding. An on-load tap changer can change tap position when the transformer is energized and carrying full load current. A de_energized tap changer must only be operated when the apparatus is isolated from the system. Tap changers’ brands and models are indicated on their name Plates,If tap voltage is to be known, it can be seen on transformer name plate 2. TRANSFORMER EQUIPMENT • 2.3 TAP CHANGERS 2. TRANSFORMER EQUIPMENT 2.4 TERMINALS Getting transformer's windings terminal out of the main tank is done by the bushing which is fixed on the cover. Bushings are consisted of copper, exist conductor and porcelain insulator. Generally DIN type insulators, which are fixed copper stud bolt, are used for the 45 kV and under (45 kV) resistance limits. Over 45 kV, condenser type bushings are used. Conductors are became from an inserted metal pipes which are covered with a kind of paper insulation. Thereby homogeny voltage is provided between the conductor and insulator by the conductor. Condenser bushing’s types depend on a transmission line system and its type may be oil/air, oil/oil, oil/SF6. Bushings may be protected with an oily/fatty or airy cable box, if there is a customer requirement or an environmental 13 pollution where the transformer is used. 2. TRANSFORMER EQUIPMENT 2.4 TERMINALS Getting transformer's windings terminal out of the main tank is done by the bushing which is fixed on the cover. Bushings are consisted of copper, exist conductor and porcelain insulator. Generally DIN type insulators, which are fixed copper stud bolt, are used for the 45 kV and under (45 kV) resistance limits. Over 45 kV, condenser type bushings are used. Conductors are became from an inserted metal pipes which are covered with a kind of paper insulation. Thereby homogeny voltage is provided between the conductor and insulator by the conductor. Condenser bushing’s types depend on a transmission line system and its type may be oil/air, oil/oil, oil/SF6. Bushings may be protected with an oily/fatty or airy cable box, if there is a customer requirement or an environmental 13 pollution where the transformer is used. 2. TRANSFORMER EQUIPMENT 2.5 MAIN TANK – COVER – CONSERVATOR 2.5.1 MAIN TANK Protection of core and coil assembly in the transformer is very important, especially in case of high voltage and large current transformer. While achieving the optimized size of transformer to suit the site condition for installation, the main role of the tank is to protect the core and coil assembly and the tank is manufactured to have sufficient strength to withstand internal and external faults that may occur during operation. Various ancillary devices such as lifting lug, jack pad, pulling eye and skid base are designed and provided on the tank so that the completely assembled transformer 14 unit can be moved in any direction without damage by using rollers, plates or rails. 2. TRANSFORMER EQUIPMENT 2.5 MAIN TANK – COVER – CONSERVATOR 2.5.2 COVER The active part assembly is mechanically affixed to the cover plate with all connections made, and is processed prior to lowering and locating into the tank. 2.5.3 CONSERVATOR The conservator is an expansion vessel that provides fluid head for the transformer and fittings, and accommodates the change in the volume of fluid as its temperature fluctuates. The fluid volume fluctuation may be due to either a change in ambient temperature or a change in transformer loading. 2. TRANSFORMER EQUIPMENT 2.6 TRANSFORMER OIL Transformer oils perform at least four functions for the transformer. - Oil provides insulation, provides cooling, and helps extinguish arcs. - Oil also dissolves gases generated by oil degradation, moisture and gas from cellulose insulation, deterioration, and gases and moisture from whatever atmosphere the oil is exposed to. - Close observation of dissolved gases in the oil, and other oil properties, provide the most valuable information about transformer health. 2. TRANSFORMER EQUIPMENT 2.7 COOLING SYSTEM Explanation Designation 1. First letter: Internal cooling medium in contact with the Windings. -O: Mineral oil or synthetic insulation liquid -K: Insulating liquid -L: Insulating liquid with no measurable fire point 2 Second letter: Circulation mechanism -N: Natural convection flow through cooling equipment -F: Forced circulation through cooling equipment 2. TRANSFORMER EQUIPMENT 2.7 COOLING SYSTEM 3. Third letter: External cooling ODWF -A: Air, W: Water 4. Fourth letter: Circulation mechanism for external cooling equipment -N: Natural convection -F: Forced circulation 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.1 Oil Level Indicator The oil level indicator is used for indicating the oil level in a conservator and is usually installed on a removable end cover. When the oil level reaches pre-set low or high positions, mechanically actuated micro-switches will operate and send alarm signals. The oil level indicator consist of an indicating dial, a coupling magnet (or cam) to link the internal mechanism with the indicating pointer, drive gear, a float connected to a lever arm bar and micro switch. When the float rises or falls with oil level change, it rotates the arm which is connected to the drive gear. The drive gear has a fixed gear ratio determined by the lever arm length, thus converting up and down movement rotation. By means of a cam or a coupling magnet the indicating pointer will also rotate. 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.1 Oil Level Indicator 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.2 Oil to Air Separator Bag The function of the flexible fluid to air separator bag is to reside within the transformer conservator allowing any change in fluid volume due to fluid temperature fluctuations, but by separating the fluid from the air, protecting the fluid from any type of contamination or external corrosive or aging agents, such as oxygen, ozone, humidity etc. 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.3 Bucholz Relay The Bucholz relay is used for checking whether any internally generated gas has been collected, or there is very low oil level or there has been an oil flow surge due to a serious fault in the transformer. The Bucholz relay consists of enclosure, a terminal box, two floats and one baffle, two permanent magnets and some magnet contact tubes. The Bucholz relay is installed in the pipework between the transformer tank and the conservator and under normal circumstances it remains completely filled with oil and the buoyancy of the floats ensures that they maintain their highest positions. 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.3 Bucholz Relay 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.4 Silikagel and Dehumidifier Silikagel is a kind of material which takes moisture in the damp air in the conservator. Silikagel is held together by the case which is called dehumidifier. The particles in the air are kept by filling the oil bottom of the dehumidifier. Silikagel and dehumidifier are used in the conservator with or without separator. 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.5 Pressure Relief Device Should there be an occurrence of a serious fault inside the transformer, the energy of arc is of colossal proportions and its peak is reached almost instantaneously. Dissipation of this vast energy creates gases which give rise to high pressures within the transformer tank since the liquid inside is incompressible. Failure to release this pressure could cause the tank to rupture, spill and spray hot and burning oil over a large area including onto adjacent personnel and/or equipment. A fast pressure build up requires a fast acting device to relieve the pressure, and having released it to reclose automatically to minimize the loss of oil. 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.5 Pressure Relief Device 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.6 Safety Valve (Auto Shut-Off Valve) The lowest oil level in the conservator will be higher than the highest oil level in the main tank of the transformer. So when there is a serious leakage from the tank, the oil will flow from the conservator to replenish the oil that has escaped from the transformer tank. In order to prevent such a situation, a safety valve can be used. The usual design of auto shut of valve has two separated oil cavities inside the casing. By detecting the differential pressure due to oil flow speed in these two cavities, a float and a float arm is actuated, thus driving a magnet which causes the valve to shut off. 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.7 Oil and Winding Temperature Indicator Hot oil moves to top of the main tank. Therefore the devices, which measure changes of winding and oil temperature, are at the top of the main tank. Winding temperature thermometer shows the temperature by simulating. The current, which coming from the current transformer, gets through the parallel resistance system in the SST. One of these resistances is fixed and the other one may be calibrated by the potentiometer. In this way the heating element becomes hot with calibrating the current, which is passing above the static resistance. So winding temperature is simulating by this way. Calibrating the current, that is passing above the static resistance, makes the heating element heat. 2. TRANSFORMER EQUIPMENT 2.8 PROTECTION DEVICES 2.8.7 Oil and Winding Temperature Indicator Hot oil moves to top of the main tank. Therefore the devices, which measure changes of winding and oil temperature, are at the top of the main tank. Winding temperature thermometer shows the temperature by simulating. The current, which coming from the current transformer, gets through the parallel resistance system in the SST. One of these resistances is fixed and the other one may be calibrated by the potentiometer. In this way the heating element becomes hot with calibrating the current, which is passing above the static resistance. So winding temperature is simulating by this way. Calibrating the current, that is passing above the static resistance, makes the heating element heat.