Professional Documents
Culture Documents
ABSTRACT
Earthing systems in distribution and transmission networks are designed to provide adequate safety levels under normal
operating and fault conditions. It is well known, however, that designs made for power frequency operation have a
different response under high frequency and transient conditions. Such conditions arise during fault and switching
transients as well as when the system is subjected to lightning strikes.
This paper reviews current recommendations and practice for high frequency and transient earthing system design. It
also describes simulation studies of various earthing scenarios under variable frequency and transient conditions. These
include surge arrester earthing electrodes, tower bases and substation grids The effect of electrode arrangements, mesh
dimensions and above-ground conductors were quantified.
188
3. High frequency and transient studies
The performance of earthing systems under transient
conditions can be investigated by representing impulse
shapes by their spectral components using FFT. Based
10 7 I 1.2
1.0
-s-
on frequency spectra obtained for 115, 8/20 and 30/80 6
impulses, it was found that frequencies of interest for 0.8 5
U
these impulses extend into the h4Hz region and this
0.6
may explain why enhancements to basic earth grids
such as rods are sometimes referred to as ‘high 0.4
frequency’ earth electrodes [ 3 ] . To quantify the
2 0.2
performance o f various earth electrode systems under
transient conditions, the frequency response of
impedance and the transient response were simulated 0 0.0
using an electromagnetic field s o h a r e . Three 0 1 2 3 4 5
scenarios were considered; a) general substation Time Qls)
earthing, b) surge arrester earthing and c) tower base
earthing.
189
rods causes very little change in the impedance significant effect in reducing the earth impedance for
magnitude. all frequencies above the ‘upturn’ frequency. This can
c) Increasing mesh density be attributed to a reduction in the inductance o f the
arrangement, and the effect is therefore more
Grid mesh density can be varied uniformly across the pronounced for low resistivity soil.
grid as a whole or it may be enhanced locally within
particular areas of the grid. Figure 3 shows an example Table 2 Grid earth impedance ai selected frequencies
of the effect of increasing the overall mesh density on with downlead enhancement ($2)
I
l0Rm earth resistivity 10 !2m earth resistivity
0.006 0.03
1
I.Ei-01 l.E+02 l.Ei-03 l.EM4 1.Et05 l.Ei-06 1.EM7
Frequency (Hz)
Figure 4 Possible dawnleaad enhancemenf Figure 6 Effect of bonding to surge arrester bases
190
there is considerable difference in the potential of the potentials at the tower top and at the tower base
between points 1 and 2 at high frequency. In the second are shown in Figure 8. For the 1/5 current shape, the
case, interconnection is provided between points 1, 2 first maximum seen in the tower top potential occurs at
and 3 while current injection remains on the central 300ns, which corresponds to twice the tower travel
downlead. Curves (c) and (d) in Figure 6 show that time of a wave travelling at the speed of light. After
interconnection results in a considerable reduction in that time, i.e. when the wave reflected from the ground
earth impedance at high frequency, above lOOkHz (cf. arrives at the top of the tower, the potential decreases.
curves (a) and (c)). However in this case, Subsequent oscillations can be explained by successive
interconnection also increases the potential markedly at reflections between the top and base of the tower.
point 1. Detailed inspection the current and potential response
at the tower base shows there is a time delay, which is
3.3 Tower base earthing equivalent to the tower travel time of 15011s. For
With the continuing encroachment of high-voltage impulses with a slower rise time, oscillations are still
lines upon urban areas, the rise of potential acquired by evident but less pronounced, as can be seen in Figure 9,
a tower during a fault has become of greater concern. For the 8/20 impulse, the maximum value of the
Also, power line towers have been increasingly used potential at the tower top is higher than that at the
for the installation of mobile telecommunication
stations and antennae ('GSM'). The interconnection of
1500 11
the steel lattice towers by the earth wire provides lower
impedances at individual towers but extends the area of
the earthing system affected by faults. The design of
tower earthing systems, like other earthing systems, is 1100
currently based on their performance under power 7
frequency fault conditions with respect to step and y 900
-
m
._
touch potentials. However, there is lack of information c
E
regarding their performance under transient conditions. 5 700
Simulations were carried out on a 45m-high tower
500
(Figure 7). The modelled physical structure of the
c
lattice tower consists of cylindrical conductors having a 300 2
diameter of 0.04m. The tower legs for both towers 1 III I
extend to a depth of 3Sm. The square base dimensions
are 6.86 x 6.86m. The impulse current was apptied at
100 I
the top of each single isolated tower and a peak -100
magnitude of lOkA was used for the injected current
for all impulse shapes. The tower response subjected to
a double-exponential impulse current was examined for Figure 8 Impulse response of a full tower to a 1/5,
different values of earth resistivity. lOkA impulse current (looam)
For the lOORm condition, the computed time variations
Energisation xEt03
.............*........
A f? point
0'
0 6 I2 18 24 30
191
tower base, with the travel time delay still visible in the 5 References
tower base potential. As the impulse rise time is further
1. ANSIiIEEE Std.80, ‘IEEE Guide for Safety in AC
increased, the induced component of voltage is less and
Substation Grounding’, The Institute of Electrical
the potential shapes at the top and base of the tower
and Electronic Engineers, 2000
become nearly similar.
2. IEEE Std. 142-1991, ‘IEEE recommended practice
for grounding of industrial and commercial power
4 Conclusions
systems’, The Institute of Electrical and Electronic
The frequency and impulse response of various Engineers, 1991
earthing systems has been investigated using 3. EA TS-41-24, (Electricity Association, Technical
simulations based on electromagnetic field theory. For Specification 41-24): ‘Guidelines for the Design,
substations earthing systems, it was found that Installation, Testing and Maintenance of Main
reinforcements to the basic design such as additional Earthing Systems in Substations’, Electricity
rods, increasing mesh density and downlead Association Services Limited, 1992
enhancement could significantly improve transient 4. HD 637 SI, ‘Power installations exceeding 1kV
performance and it is clear that individual designs AC’, European Committee for Electrotechnical
should be tailored according to local resistivity Standardisations (CENELEC), 1999
conditions. Specifically, mesh density reduces 5. BS6651:1999; ‘Code of practice for protection of
impedance over a frequency range related to resistivity structures against lightning’, British Standard 1999
and enhancements to downleads will reduce the overall 6. Takeuchi, M. et al,: ‘Impulse characteristics of a
inductance. In the case of surge arrester earthing, the 500kV transmission tower footing base with
reduction of earth potential rise at the point of injection various grounding electrodes’, 24” International
as a result of above-ground interconnection must be Conference on Lightning Protection ICLP-98, pp.
weighed up against the increase in transferred potential. 513-517, Birmingham (UK), 1998
The impulse response of towers was shown to be
dependent on the shape of the impulse current. Impulse Address of authors:
currents with a slow rate of rise gave a mainly resistive High Voltage Group
response while the response to fast impulses showed School of Engineering
significant osciIlations which can be explained by the Cardiff University
Newport Road
travelling wave effects. PO Box 925
Cardiff CF24 OYF
Wales, UK
Tel: 44 29 20875904/4608/5953
hftp:/nYww.cf.ac.uWengin/research/highvolt
192