Manhole Dimensions D B: 7' X 7' Square Concrete NO. 3 Manhole Standard

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
757 views1 page

Manhole Dimensions D B: 7' X 7' Square Concrete NO. 3 Manhole Standard

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

REV.

5-27-01: CHANGED ITEM NUMBERS


102" IN GENERAL NOTE I. ADDED MAXIMUM
FOR DESIGN
MANHOLE DIMENSIONS DEPTH NOTE.
D USE ONLY
B INSIDE DIAMETER BOX SECTION MANHOLE

312"
PIPE WALL REV.5-30-02: MODIFIED REINFORCING
DIAMETER OF CUT-OUT MINIMUM MINIMUM STEEL.
THICKNESS
A500 (D) OF PIPE HOLES HEIGHTS DESIGN DEPTH
A A (INCHES)
(INCHES)
(INCHES) (INCHES) (FEET) REV. 7-29-02: CHANGED ASTM
A500

158"CLEAR
SPECIFICATION IN GENERAL NOTE B .
18 212 25 5712 4.40
A500

8 SPA.OF 6"
REV.9-11-02: CHANGED REINFORCING
A500 24 3 32 6412 4.94 STEEL IN BASE SECTION.

A500

62"

D
312 7112 » REV. 8-01-12: REVISED MANHOLE FOR

ON D-
30 39 5.48
COMPLIANCE WITH AASHTO LRFD BRIDGE
A500
DESIGN SPECIFICATIONS, 4TH EDITION
7812

258"CLEAR
36 4 46 6.02 WITH INTERIMS. REVISED REINFORCING,
A500

412"
GENERAL NOTES, LEGEND AND
A500 412 8512

SECTI
42 53 6.56 ADDITIONAL MISC. DRAFTING EDITS.
102"

102"
A500 REV. 4-1-14: ELIMINATED STIRRUPS.

212"
48 5 60 9212 7.10
C C A500
A500 REV. 02-20-2020: REDREW SHEET.
54 512 67 9912 7.65

2"CLEAR
312"
A503

10"
NG
3 EQ.
SPA.
60 6 74 10612 8.19

OPENI
24"
A503
DRAIN 2" CLEAR
A503 66 612 81 11312 8.73
A503
1 CUT-OUT HOLES BASED ON REINFORCED CONCRETE PIPE WITH

2 EQ.
312" 312"

SPA.
A500 WALL TYPE "B".

16"
A500
2 ALL FLEXIBLE PIPE MATERIALS REQUIRE GASKET. SEE STANDARD

258"CLEAR
A500
DRAWING D-PB-2.
SECTION *-*
T500
B ELEV. VIEW IS PROVIDED ON
2" CLEAR
3 CUT-OUT HOLES FOR PRECAST STRUCTURES TO BE FORMED IN
STANDARD DRAWING D-CB-99
D ORDER TO OBTAIN A SMOOTH EDGED HOLE. SCORED OR ETCHED
SHOWING REINFORCEMENT
PLAN VIEW HOLES WITH REINFORCING STEEL LEFT UNCUT WILL NOT BE
REQUIREMENTS AROUND PIPE LID REINFORCING
* OPENINGS
PERMITTED.

PIPE (BEYOND) REINFORCING STEEL LEGEND

8914"M AX.

8914"M AX.
98" 12" 8914" 36" LAP

N.

N.
A502

A502

A502

A502
A500
A500
A500

A500
A500
A500

A500

A500

A500

A500

A500

A500

A500

A500
A500

6"M I

6"M I
32"

32"
A501 S/W H500
VARIABLE

8914"

8914"
A501
AVOID STACKING OF SPLICES BY 9012" 8914" 3158" DIA.
312" 312" 312" 212" 412" 312"
STAGGERING LAP LOCATIONS VARIABLE
2 EQ. 3 EQ. 8 SPA. OF 6" A502
SPA. SPA. H500 H501
VARIABLE
16" 24" 62" A503 T500
DIMENSIONS SHOWN IN THIS LEGEND ARE OUTSIDE TO OUTSIDE OF BAR. 8914"
OPENING
L500 STANDARD C.R.S.I. HOOK AND TIE DETAILS SHALL APPLY, EXCEPT AS NOTED.
PORTLAND 102" L500
CEMENT
GROUT 2" CLEAR
C :\U sers\jj00547\D esktop\10-102.00 C atch B asins and M anholes IP \102.03 M anholes IP \D M H 6-20200220.dgn

10" 2" CLEAR GENERAL NOTES


2" CLEAR
SEE NOTE I 1" CLEAR 2" CLEAR A DRAWING TO BE USED FOR ALL CAST-IN-PLACE 7’ X 7’ NO. 3 CONCRETE MANHOLES AND ALL PRECAST 7’ X 7’
NO. 3 CONCRETE MANHOLES. SEE STANDARD DRAWING D-CB-99 FOR ADDITIONAL CONSTRUCTION NOTES &
10"
9"

DETAILS.

SECTION C-C B THIS DIMENSION MAY VARY FROM A MINIMUM OF 0 INCHES TO A MAXIMUM OF 24 INCHES AS LONG AS 2534
INCHES IS SATISFIED. THE CONTRACTOR HAS THE OPTION OF USING BRICK OR STANDARD PRECAST CONCRETE
9"
RISER FRAMES. THE USE OF BRICK SHALL BE LIMITED TO 6 INCHES. IF THIS DIMENSION EXCEEDS 6 INCHES,
934"
PRECAST CONCRETE RISER FRAMES SHALL BE USED AS SHOWN ON STANDARD DRAWING D-RF-1.
MANHOLE MAXIMUM DEPTH NOTE
C THIS DRAWING DEPICTS THE MINIMUM HORIZONTAL REINFORCING AT THE TOP OF MANHOLE WALLS. SEE
* SECTION E-E
634"

MAXIMUM DEPTH FOR THIS STRUCTURE IS 28.00’. ADDITIONAL DETAILS ON STANDARD DRAWING D-CB-99 FOR TALLER SECTIONS AND STEEL PLACEMENT ABOVE PIPE
OPENINGS.

D CAST-IN-PLACE MANHOLES SHALL BE CONSTRUCTED IN ACCORDANCE WITH STANDARD SPECIFICATIONS, SECTION

C
611 AND/OR SPECIAL PROVISIONS UNLESS SUPERSEDED BY THIS DRAWING. THE CONTRACTOR MAY, WITH

SEE NOTE
PERMISSION FROM THE ENGINEER, SUBSTITUTE PRECAST MANHOLES FOR CAST-IN-PLACE MANHOLES PROVIDED
K

24" 24" THAT ALL PRECAST ELEMENTS MEET ASTM C913 (CURRENT EDITION) UNLESS SUPERSEDED BY THIS DRAWING.
SEE NOTE B

2"
9"

B
SEE NOTE

L500
OPENING OPENING
ON -SEE NOTE

E THE FOLLOWING MATERIAL PROPERTIES ARE REQUIRED FOR BOTH CAST-IN-PLACE AND PRECAST STRUCTURES:
N.
12"

84" 84"
MI

GHT

9" 9" 9" 9" CONCRETE: f’c = 4,000 POUNDS PER SQUARE INCH AT 28 DAYS
REINFORCING STEEL: ASTM A615, Fy = 60,000 POUNDS PER SQUARE INCH
2 SPA.OF 3"
M UM HEI

2" CLEAR 2" CLEAR ALL REINFORCING IS TO BE INSTALLED AS DETAILED ON THIS DRAWING.
6"M AX.

GROUT
F PRECAST MANHOLE UNITS WHICH ARE DAMAGED DURING SHIPMENT OR INSTALLATION WILL BE REJECTED. IT
SER SECTI

SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REPLACE DAMAGED MANHOLE UNITS AT THEIR OWN
NI

EXPENSE.
OUTS) C
ON -SEE TABLE FOR M I

C.

G APPROPRIATE SIZING AND LOCATION OF LIFTING DEVICES SHALL BE THE RESPONSIBILITY OF THE FABRICATOR.
OUTS
SEE TABLE FOR
OUT HOLE

USE L500 @ 6"C.


PE

C.
J

RI
PE

SEE TABLE FOR


NLET PI

OUT HOLE

PE CUT-

H THE CONTRACTOR IS TO PATCH ALL LIFTING DEVICE HOLES WITH GROUT AND PLACE A MINIMUM OF ONE (1)
H501 @ 6"C.
J
D -OUTLET PI
SEE NO TE

A501
PE CUT-

INCH OF COVER OVER THE HARDWARE OF THESE DEVICES ON BOTH TOP AND BOTTOM SURFACES.
SEE NO TE

INSIDE DIA. OF INLET S/W H500


I ALTERNATIVE JOINT DETAILS MAY BE ACCEPTABLE. SEE STANDARD DRAWING D-CB-99 FOR ADDITIONAL
CUT-

D -I

»
ABOVE PI

APPROVED BY FHWA
PIPE D DETAILS.
CUT-

AT PI

(ALL OTHERS APPROVED BY TDOT)

L
J SEE ROADWAY PLANS DRAINAGE TABULATION FOR PIPE INLET AND OUTLET ELEVATIONS. IF NEEDED, INVERT
M UM
SEE NOTE
15"LAP
(

ELEVATIONS MAY BE ADJUSTED AS DIRECTED BY THE ENGINEER IN ORDER TO ACCOMMODATE INLET AND
BOX SECTI

12:1 12:1
N.

NI

OUTLET PIPES.
D
312"M I

Y=
MI

24:
1MI D 4 STATE OF TENNESSEE
NIMUM
Y= K FOR CASES WHERE THE OUTLET PIPE DIAMETER IS LARGER THAN THE INLET PIPE DIAMETER, A MINIMUM 2734
4
STANDARD
INCH DEPTH SHALL BE MAINTAINED ABOVE THE OUTLET PIPE.
2"

DRAWING

2" CLEAR 2" CLEAR


DEPARTMENT OF TRANSPORTATION
3/23/2020 11:27:05 A M

L THE CONTRACTOR MAY ELIMINATE THE A501 BARS BY LENGTHENING THE VERTICAL LEG OF THE H500 BARS SO
H500 THAT 112" OF CLEAR COVER IS PROVIDED AT THE TOP OF THE STRUCTURE.
8"

8"

H500
MONOLITHIC BASE SECTION MONOLITHIC BASE SECTION STANDARD
M SEE STANDARD DRAWING D-MH-4 FOR DETAILS REGARDING CAST IRON COVERS AND FRAMES, AND DETAILS
FOR VARIOUS STEPS. 7’ X 7’ SQUARE
9" 6" 9 SPACES OF 8" 6" 9" 9" 6" 9 SPACES OF 8" 6" 9"
NON-SHRINK GROUT PER
STANDARD N PAY DEPTH MEASUREMENT MADE FROM TOP OF MANHOLE LID TO OUTLET FLOW ELEVATION. PAYMENT INCLUDES CONCRETE
BARS H500 BARS H500 RISER SECTION AND LID. PAYMENT FOR MANHOLE WILL BE MADE UNDER ITEM NUMBERS:
SPECIFICATIONS SECTION
102" 918 REQUIRED AROUND 102"
NO. 3
PIPE OPENINGS ONLY 611-01.02, MANHOLES, > 4’-8’ DEPTH, EACH, (THROUGH)

SECTION A-A SECTION B-B 611-01.07, MANHOLE, > 24’-28’ DEPTH, EACH. MANHOLE

NOT TO SCALE
09-05-1997 D-MH-6