AVG. NATURAL GROUND LVL

A A

2500 FROM AVG. NATURAL GROUND LVL.


01-08-16 R1 COLUMN REINFORCEMENT REVISED
A A

750
DATE Rev PARTICULARS Drwn Check
REVISIONS :
A A
NOTES :-

100
A A

T16@130c/c
@EXT.BOT
B B B B TYPICAL SECTION OF EXPANSION JOINT COLUMN GENERAL NOTES :-
1. ALL DIMENSIONS, UNLESS OTHERWISE STATED, ARE IN MILLIMETERS
T20@150c/c
@EXT.BOT 2. MISSING OR AMBIGUOUS DIMENSIONS IN ANY DRAWING ARE

A
B B A A TO BE CLARIFIED FROM AUTHORITY CONCERNED.

A
A 3. DO NOT SCALE DRAWING, FOLLOW ONLY WRITTEN DIMENSIONS.
A A B B B B B B A A
4. PLEASE CHECK THE DIMENSION WITH RESPECT TO ARCHITECTURAL
A
PLANS BEFORE EXECUTION.

B
A AVG. NATURAL GROUND LVL STRUCTURAL NOTES :-

A
B
1. TYPE OF STRUCTURE :- R.C.C. FRAMED STRUCTURE HAVING
GROUND + 4 FLOORS & ONE FUTURE FLOOR IS CONSIDERED.

A
A ONE FUTURE FLOOR IS CONSIDERED PART A,B,C & D .

2500 FROM AVG. NATURAL GROUND LVL.


B
2. DESIGN FORCES :-

B
A A B B C C A A B DEAD LOADS IS : 875(PART-1)

B
A
A LIVE LOADS IS : 875(PART-2)
B

300
B
1000 1000 EARTHQUAKE LOADS IS : 1893-2002,IS:13920-1993 (EQ. ZONE III, R=5, I=1.5)
A B 3. SPECIFICATIONS OF P.C.C./R.C.C. WORK SHALL BE AS PER IS : 456-2000.
B B

B
A

A
A
4. CONCRETE GRADE:- R.C.C M 25, P.C.C (1:4:8) UNLESS SPECIFICALLY STATED.

B
B 750 750

B
B 5. (5.1) CEMENT FOR R.C.C. WORK :- 53 GRADE CEMENT.
(5.2) REINFORCEMENT :- HYSD/TMT STEEL (CRS FE-500 GRADE) UPTO PLINTH AS PER IS :1786-2008

750

750
B
A

B
A A B B C C A B (5.3) REINFORCEMENT :- HYSD/TMT STEEL (Fe-500D GRADE) ABOVE PLINTH AS PER IS :1786-2008

C
B
6. ALL COLUMN SIZE REDUCTION SHALL BE DONE BY EQUALLY

100
B ON BOTH SIDE HENCE CENTER LINE OF BOTH UPPER & LOWER

A
C
COLUMN SHOULD BE THE SAME.

B
B 7. MORTAR PROPORTION IN AERATED LIGHT WEIGHT CONCRETE BLOCK : 1:5 CEMENT MORTAR.

B
A A B B B B

B
B B A SECTION C-C 8. CLEAR COVER TO REINFORCEMENT :

B
FOOTING : 60 mm COLUMN : SIDE UP TO 200 = 30 mm

C
B SLABS : 25 mm SIDE ABOVE 200 = 40 mm.

B
B
A A B B
B

B B B B C B BEAMS : 30 mm

A
B

A
B
CLEAR COVER SHALL BE MEASURED FROM STIRRUPS.

B
B 9. ORIENTATION OF COLUMN SHALL BE STRICTLY FOLLOWED AS SHOWN IN THE PLAN.

B
B

B
B B 10. IN COLUMNS NOT MORE THAN 50% BARS SHALL BE SPLICED AT A SECTION.

A
B B
B B B B AVG. NATURAL GROUND LVL 11. ALL COLUMNS REINFORCEMENTS SHALL BE WITH STAGGERED LAP JOINT.
B

B
A
B
B

B 12. STRIPPING TIME OF FORM WORK FOR RCC- AS DECIDED BY SITE


B

B
B B B ENGINEER IN ACCORDANCE WITH IS-456/2000.

2500 FROM AVG. NATURAL GROUND LVL.


B

B B B B

B
B

13. STRUCTURAL ENGINEER & ARCHITECT IS NOT RESPONSIBLE FOR


A

A
A A B B B B B B
CENTERING,SHUTTERING, QUALITY OF CONSTRUCTION MATERIAL

B
B AND WRONG INTERPRETATION OF DRG.
A

A
14.CONTRACTOR SHALL BE FULLY RESPONSIBLE
A

FOR ALL EXECUTION WORK AT SITE.

B
B B B B A A B
A
A

B 15. THE EXCAVATED AREA OF PLINTH/FOUNDATION TO BE REFILLED WITH

A
A MURRUM/GOOD EARTH OR AS DIRECTED BY EIC.
B

B 16. COMPACT THE MURRUM TO GIVE A FIELD DENSITY OF 60-62 KG/CFT (2.3GM/CC),
1000 1000

750
A

17. MINIMUM SAFE BEARING CAPACITY OF SOIL FOR FOUNDATION MUST BE


A A C C A
B B B B A A
150 KN/SQM.(15.0 TON/SQM). AT 2.5 M. DEPTH FROM LOWEST EX.G.L. OR UP TO HARD STRATA.

A
18. DEVELOPMENT LENGTH ( Ld ) OF BAR FOR SPLICING SHALL BE ASPER
LAP LENGTH SCHEDULE OF BAR.

100
A

19. R.C.C. BAND SHOULD BE PROVIDED AT WINDOW SILL LEVEL.


A

B B 20. CHICKEN WIRE MESH SHOULD BE PROVIDED AT ALL THE JUNCTION OF


SECTION B-B R.C.C. AND BRICK WORK.
A

21. ABOVE ROOF LEVEL COLUMN FOR FUTURE EXPANSION SHALL BE


A A C C B B B B A A CONSTRUCT UP TO 1200MM HEIGHT.

A A
A A
AS-BUILT DRAWINGS
AVG. NATURAL GROUND LVL

A A B B B B B B A A CLIENT :-
A A A A A
MEDICAL EDUCATION DEPARTMENT GOVERNMENT

2500 FROM AVG. NATURAL GROUND LVL.


B B
A A B B B B B B B B A A
OF RAJASTHAN
A A A A A
PROJECT MANAGEMENT CONSULTANT :-

NATIONAL BUILDINGS CONSTRUCTION

750
A A C C C C C C B B B B B B C C C C C C C C A A
CORPORATION LIMITED

100
100
ASSOCIATE CONSULTANT :- AKA CONSULTANTS (INDIA) PVT. LTD.
SECTION A-A
PROJECT :-
SCALE MEDICAL COLLEGE CAMPUS FOR 100 MBBS ADMISSIONS
B B B B B B B B B B B B B B B B B B A A 1:200
ANNUALLY & UP GRADATION OF GOVT. DIST. HOSPITAL
INTO TEACHING HOSPITAL, DUNGARPUR,RAJASTHAN.
A A B B B B B B B B B B B B B B B B B B B B B B A A
COLLEGE BLOCK
B B
SIZE
TITLE :-
A1
BOTTOM REINFORCEMENT LAYOUT
A A A A A A A A A A A

A A B B B B
DATE : - 04.05.2020 DRWN BY :- V.S. CHKD BY :- S.G.

NORTH
A A A A A A A A A A A N
W NW
N

NE
THIS DRAWING IS COPYRIGHT OF-

W
SW

E
NATIONAL BUILDINGS CONSTRUCTION CORPORATION S
SE
E
BOTTOM REINFORCEMENT LAYOUT LIMITED (NBCC), AND IS NOT TO BE REPRODUCED,
HANDED OVER TO OTHER PERSON OR USED FOR ANY
S
STRUCTURE ENGINEER ARCHITECT
PURPOSE OTHER THAN THAT FOR WHICH IT HAS BEEN
ISSUED. OTHERWISE IT SHALL BE COPYRIGHT VIOLATION.
NBCC DRG. NO. : - 621 - MC - E - S - 2002 SHEET NO. : - 1 OF 1