Professional Documents
Culture Documents
FX2204/2208 BIWIRE
INSTRUCTIONS & LOG BOOK
ZONE L O C A T I O N
1
2 TECHNICAL
3 HELPLINE
01302 303350
4
7702-4032/V
NOTE:This fire alarm system requires regular checks, as specified in BS.5839 Part 1 1988, to verify correct operation. It is the responsibility of the
user of the fire alarm system to see that the necessary checks are carried out. Use the following log book pages to record test results.
FX2204/2208 BIWIRE
INSTRUCTIONS & LOG BOOK
ZONE L O C A T I O N
1
2 TECHNICAL
3 HELPLINE
01302 303350
4
7702-4032/V
NOTE:This fire alarm system requires regular checks, as specified in BS.5839 Part 1 1988, to verify correct operation. It is the responsibility of the
user of the fire alarm system to see that the necessary checks are carried out. Use the following log book pages to record test results.
FX2204/2208 BIWIRE
Instruction Manual and Log Book
It is vital that fire alarm panels are regularly checked for correct operation in accordance with BS 5839. An access code is required.This is printed on the keyfob.
Keep this in a safe place, with a call point test key (supplied with each break glass call point.)
Access Code: To operate this fire alarm panel, keypad access must first be gained. Keypad access is achieved by entering the correct access code on the
pushbuttons. Access is acknowledged by the rapid pulsing of the buzzer.This alows the user to Silence, Reset, Evacuate, Mute Buzzer or Disable the panel using
the same pushbuttons.
Functions: See details behind the drop down door on the front of the panel. Please follow the regular inspection checks below:
ALL SMOKE SENSORS SHOULD BE CHECKED FOR CORRECT OPERATION EVERY YEAR.
BATTERIES SHOULD BE REPLACED EVERY FIVE YEARS.
15
FX2204/2208 BIWIRE
Instruction Manual and Log Book
It is vital that fire alarm panels are regularly checked for correct operation in accordance with BS 5839. An access code is required.This is printed on the keyfob.
Keep this in a safe place, with a call point test key (supplied with each break glass call point.)
Access Code: To operate this fire alarm panel, keypad access must first be gained. Keypad access is achieved by entering the correct access code on the
pushbuttons. Access is acknowledged by the rapid pulsing of the buzzer.This alows the user to Silence, Reset, Evacuate, Mute Buzzer or Disable the panel using
the same pushbuttons.
Functions: See details behind the drop down door on the front of the panel. Please follow the regular inspection checks below:
2
ALL SMOKE SENSORS SHOULD BE CHECKED FOR CORRECT OPERATION EVERY YEAR.
BATTERIES SHOULD BE REPLACED EVERY FIVE YEARS.
15
DATE FOLLOW RESET INTERNAL VISUAL CALL POINT
CHECK PROCEDURE. BATTERY TEST COMMENTS
EXAMINATION TEST.CHECK ZONE AND LOCATION OF CALL CHECK ACCESS
CHARGE CHECK ALL SOUNDERS OPER- ISOLATE MAINS
INCLUDING POINT TESTED.TEST ALL CALL TO ALL CALL e.g. DETAILS OF FALSE ALARMS,FIRE PRAC- SIGNED
INDICATOR INDICATORS SHOW ATE EACH ZONE AND OPERATE TICES, MAINS FAILURES,
& SOUNDER BATTERY & POINTS IN ROTATION POINTS IS CLEAR
WEEKLY QUARTERLY SHOWS TO BE TESTED CALL POINT CALL ENGINEER ETC.
BUZZERS CONNECTIONS QUARTERLY
TEST TEST
1 2 3 4 5 6 7 8
14
Daily Inspection: Check that only the green ‘power on’ indicator is lit. Inspect for any fault indication. Notify any faults to a competent electrician.
14
Daily Inspection: Check that only the green ‘power on’ indicator is lit. Inspect for any fault indication. Notify any faults to a competent electrician.
3
QuarterlyTest:
Check all previous log book entries and verify any remedial action has been taken. Carry out the weekly test. Visually examine the battery and its connections, by
loosening the screws located behind the drop down door, and lifting off the front panel. Isolate the mains supply and check the battery is capable of supplying the zonal
sounders by operating a call point
AnnualTest: As Weekly Test and Quarterly Test described above. Additionally test all sensors and call points and check for correct operation.
Every 2-3 Years:
Replace or return the smoke detectors for cleaning to ensure correct operation and freedom from false alarms. Special equipment is required for cleaning smoke
detectors. Consult technical helpline if in doubt.
Every 5 Years:
Replace sealed lead acid battery.
Cleaning:
When cleaning the panel, use a moist cloth. Do not use solvents or harsh abrasives.
ALL SMOKE SENSORS SHOULD BE CHECKED FOR CORRECT OPERATION EVERY YEAR.
BATTERIES SHOULD BE REPLACED EVERY FIVE YEARS.
13
QuarterlyTest:
Check all previous log book entries and verify any remedial action has been taken. Carry out the weekly test. Visually examine the battery and its connections, by
loosening the screws located behind the drop down door, and lifting off the front panel. Isolate the mains supply and check the battery is capable of supplying the zonal
sounders by operating a call point
AnnualTest: As Weekly Test and Quarterly Test described above. Additionally test all sensors and call points and check for correct operation.
Every 2-3 Years:
Replace or return the smoke detectors for cleaning to ensure correct operation and freedom from false alarms. Special equipment is required for cleaning smoke
detectors. Consult technical helpline if in doubt.
Every 5 Years:
Replace sealed lead acid battery.
Cleaning:
When cleaning the panel, use a moist cloth. Do not use solvents or harsh abrasives.
4
ALL SMOKE SENSORS SHOULD BE CHECKED FOR CORRECT OPERATION EVERY YEAR.
BATTERIES SHOULD BE REPLACED EVERY FIVE YEARS.
13
FOLLOW RESET CALL POINT
DATE INTERNAL VISUAL COMMENTS
CHECK PROCEDURE. TEST.CHECK BATTERY TEST
EXAMINATION ZONE AND LOCATION OF CALL CHECK ACCESS
CHARGE CHECK ALL INDI- SOUNDERS OPER- ISOLATE MAINS
INCLUDING POINT TESTED.TEST ALL CALL TO ALL CALL e.g. DETAILS OF FALSE ALARMS,FIRE PRAC- SIGNED
INDICATOR CATORS SHOW & ATE EACH ZONE AND OPERATE TICES, MAINS FAILURES,
BATTERY & POINTS IN ROTATION POINTS IS CLEAR
WEEKLY QUARTERLY SHOWS SOUNDER TO BE TESTED CALL POINT CALL ENGINEER ETC.
BUZZERS CONNECTIONS QUARTERLY
TEST TEST
1 2 3 4 5 6 7 8
12
.
Disable a Zone Circuit: Enter the access code,the buzzer will pulse rapidly,press pushbutton 4, this will cause zone 1 disable indicator to light.To disable this zone
and escape from this function press pushbutton 1’. This will cause the buzzer to pulse at a slow rate. To select another zone to be disabled, enter the access code
and press pushbutton 4 until the desired zone and disabled indicators are lit, press pushbutton 1 to select and escape.The buzzer will now pulse at a slow rate.
Disable the Zonal Sounders: Enter the access code, the buzzer will pulse rapidly, press pushbutton 4, until the sounder disabled indicator is lit.To disable the
zonal sounder and escape from this function press pushbutton 1’, this will cause the buzzer to pulse at a slow rate.This function disables the zonal sounders
on ALL zone circuits.
12
Disable a Zone Circuit: Enter the access code,the buzzer will pulse rapidly,press pushbutton 4, this will cause zone 1 disable indicator to light.To disable this zone
and escape from this function press pushbutton 1’. This will cause the buzzer to pulse at a slow rate. To select another zone to be disabled, enter the access code
and press pushbutton 4 until the desired zone and disabled indicators are lit, press pushbutton 1 to select and escape.The buzzer will now pulse at a slow rate.
Disable the Zonal Sounders: Enter the access code, the buzzer will pulse rapidly, press pushbutton 4, until the sounder disabled indicator is lit.To disable the
zonal sounder and escape from this function press pushbutton 1’, this will cause the buzzer to pulse at a slow rate.This function disables the zonal sounders
on ALL zone circuits.
5
Disable Both Zone and Zonal Sounder Circuits: Enter the access code, the buzzer will pulse rapidly, press pushbutton ‘4’, until all zone disable indicators and
the sounder disable indicators are lit.To disable all zones and the zonal sounders, press pushbutton ‘1’, this will cause the buzzer to pulse at a slow rate.
Re-enable the Zone Circuit(s): (The Disabled and Zone Disabled Indicator(s) are on):
Enter the access code, the buzzer will pulse rapidly, press pushbutton ‘4’ until the disabled indicator for desired zone to be re-enabled is off, then press push-
button ‘1’ to re-enable the zone and escape.
Re-enable the Zone Sounder Circuit: (The Disabled and Zone Disabled Indicator are on):
Enter the access code, the buzzer will pulse rapidly, press pushbutton ‘4’ until the sounder disable indicator is off, then press pushbutton ‘1’ to re-enable the
zonal sounders and escape.
Re-enable the Zone and Zonal Sounder Circuits: (All Zone and Sounder Disabled Indicators are lit):
Enter the access code, the buzzer will pulse rapidly, press pushbutton ‘4’ until all zone and sounder disable indicators are off. Press pushbutton ‘1’ to re-enable
the zone and sounder circuits, and escape.
ALL SMOKE SENSORS SHOULD BE CHECKED FOR CORRECT OPERATION EVERY YEAR.
BATTERIES SHOULD BE REPLACED EVERY FIVE YEARS.
11
Disable Both Zone and Zonal Sounder Circuits: Enter the access code, the buzzer will pulse rapidly, press pushbutton ‘4’, until all zone disable indicators and
the sounder disable indicators are lit.To disable all zones and the zonal sounders, press pushbutton ‘1’, this will cause the buzzer to pulse at a slow rate.
Re-enable the Zone Circuit(s): (The Disabled and Zone Disabled Indicator(s) are on):
Enter the access code, the buzzer will pulse rapidly, press pushbutton ‘4’ until the disabled indicator for desired zone to be re-enabled is off, then press push-
button ‘1’ to re-enable the zone and escape.
Re-enable the Zone Sounder Circuit: (The Disabled and Zone Disabled Indicator are on):
Enter the access code, the buzzer will pulse rapidly, press pushbutton ‘4’ until the sounder disable indicator is off, then press pushbutton ‘1’ to re-enable the
zonal sounders and escape.
Re-enable the Zone and Zonal Sounder Circuits: (All Zone and Sounder Disabled Indicators are lit):
Enter the access code, the buzzer will pulse rapidly, press pushbutton ‘4’ until all zone and sounder disable indicators are off. Press pushbutton ‘1’ to re-enable
the zone and sounder circuits, and escape.
6
ALL SMOKE SENSORS SHOULD BE CHECKED FOR CORRECT OPERATION EVERY YEAR.
BATTERIES SHOULD BE REPLACED EVERY FIVE YEARS.
11
FOLLOW RESET CALL POINT
DATE INTERNAL VISUAL COMMENTS
CHECK PROCEDURE. TEST.CHECK BATTERY TEST
EXAMINATION ZONE AND LOCATION OF CALL CHECK ACCESS
CHARGE CHECK ALL INDI- SOUNDERS OPER- ISOLATE MAINS
INCLUDING POINT TESTED.TEST ALL CALL TO ALL CALL e.g. DETAILS OF FALSE ALARMS,FIRE PRAC- SIGNED
INDICATOR CATORS SHOW & ATE EACH ZONE AND OPERATE TICES, MAINS FAILURES,
BATTERY & POINTS IN ROTATION POINTS IS CLEAR
WEEKLY QUARTERLY SHOWS SOUNDER TO BE TESTED CALL POINT CALL ENGINEER ETC.
BUZZERS ONNECTIONS QUARTERLY
TEST TEST
1 2 3 4 5 6 7 8
10
10
7
NORMAL AND FAULT INDICATION
CONDITION INDICATION COLOUR BUZZER
Normal Power On indicator on Green Off
Mains or Power On indicator on Green
Charger Failure General Fault indicator on Amber Pulsing*
Charger Fault indicator flashing Amber
Zone short/open circuit Zone indicator flashing Amber Pulsing*
Zone Disable Zone indicator on Amber Pulsing*
Sounder Disable Sounder indicator on Amber Pulsing*
Sounder and Zone indicator on Amber Pulsing*
Zone Disabled Sounder indicator on Amber
Weekly Test in progress Test in progress indicator on Amber Pulsing*
Walk Test in progress Test in progress indicator on Amber Pulsing*