You are on page 1of 6

C o n s t r u c t i o n Te c h n o l o g y U p d a t e N o .

1 5

Current Approaches for


Mechanical Ventilation
of Houses
by J.C. Haysom and J.T. Reardon
This Update, the second of two on mechanical ventilation systems for
houses, describes current approaches to design and installation. It also
examines the distribution problem and looks at some of the shortcomings of
current approaches and how they might be overcome.
Current Approaches ventilation systems does not approximate
Current approaches to the mechanical the ideal very closely, F326 requires only
ventilation of houses are found in the CSA that the system have an on/off switch.
Standard F326, “Residential Mechanical Other forms of control, such as dehumidi-
Ventilation Systems,” and in the National stats, are permitted, but the on/off switch
Building Code of Canada 1995. must be able to over-ride them.
CAN/CSA-F326 Capacity
The CSA Standard F326 was first published F326 requires the ventilation system to
in 1989 and revised in 1991. It is the most have a total capacity equal to the sum of
comprehensive standard available on this the individual room ventilation require-
subject, and attempts to address the critical ments shown in Table 1. For most houses,
issues in the design and installation of an this will add up to about 0.3 air changes
ideal mechanical ventilation system (see
Construction Technology Update No. 14 for Table 1. Ventilation Capacity
a discussion of these issues). The extent to
which Standard F326 has been able to do Room Capacity, L/s
this is limited by available technology. Master bedroom 10
CAN/CSA-F326 is generally written in Other bedrooms 5
performance terms (that is, it states what Living room 5
must be accomplished rather than how to Dining room 5
accomplish it) and therefore provides a great
Family room 5
deal of flexibility with regard to the system
configuration needed for compliance. Recreation room 5
This standard addresses the pertinent Basement 10
issues as follows: Other habitable rooms 5
Control Kitchen 5
The greatest shortfall of a system that Bathroom or
complies with Standard F326 (hereafter water closet room 5
referred to as F326), relative to an ideal Laundry 5
system, is in the area of control. Because Utility room 5
available technology for demand-controlled
per hour (ach). The standard also requires the value represents the flow of air likely
that the system be capable of running at a to be produced by such a system. This
rate of 50% of this amount. In other words, approach has been widely used in Canada
it must have at least two delivery modes — without significant problems, even though
full capacity and half capacity. it can lead to pressurization of the house.
Distribution As well as limiting the flow of air, F326
F326 requires that the system be capable also places a limit of 10 Pa on the positive
not only of providing the total indoor/ pressure that can be brought about by the
outdoor air exchange rate (determined from discrepancy between the ventilation system
Table 1) but also of achieving this rate in intake and exhaust flows. This requirement
each room. Although the standard does not is necessary because in a very tight house,
specify how this is to be accomplished, a even if the flow discrepancy criterion
duct system is generally required. described above is satisfied, there is still
the possibility of creating a high positive
Sound level
pressure in the house, which can lead to
Currently, F326 does not set a maximum
very high flow at individual leaks, causing
sound output for fans since methods of test-
local interstitial condensation problems.
ing and acceptable sound levels had not
been fully agreed upon when the standard 1995 National Building Code
was last revised. It is expected that this The 1995 NBC requires all houses to have
issue will be addressed in a future edition. mechanical ventilation systems. Systems
that comply with F326 satisfy this require-
Interference with other systems
ment. However, F326 is a comprehensive
For dwellings with vented combustion
standard and is written in performance
appliances, F326 requires that the ventila-
terms specifically for trained mechanical
tion system, when operating at full capacity
systems designers. The NBC therefore pro-
and at the same time as a clothes dryer and
vides prescriptively described alternatives,
any other exhaust devices with a capacity
which are based on F326 and which can be
of 75 L/s or greater, not depressurize the
used by those who are not experts.
dwelling more than 5 Pa. This limit (of 5 Pa)
These prescriptive alternatives address
can be exceeded if the combustion appliance
the issues identified in the description of
has been rated for a higher level of depres-
the ideal system as follows:
surization. The potential for such depres-
surization can be determined by calculation, Control
when the airtightness characteristics of The 1995 NBC parallels F326 in that it
the dwelling are known, or by a test that requires only an on/off switch capable of
actually measures depressurization. over-riding any automatic controls.
Interference with the building envelope Capacity
F326 limits the amount of outdoor air that The NBC also parallels F326 in this area,
can be brought in relative to the amount of and uses the same table of individual room
air that is extracted, in recognition of the airflow requirements (that is, the total
fact that any excess of intake flow over capacity of the system must equal the sum
exhaust flow must be made up by outward of the room ventilation requirements shown
leakage through the envelope, which can in Table 1). It also requires the system to
lead to interstitial condensation. When the be capable of operating at a rate equal to
ventilation system is operating at full the full capacity as well as at 50% of this
capacity, the amount of outdoor air brought capacity.
in through intake components (e.g., supply Distribution
fans) must not exceed the amount of indoor There are basically two prescriptively
air extracted through exhaust components described approaches in the 1995 NBC —
(e.g., exhaust fans) by more than 0.12 L/s/m2 one that can be used in houses with
of the building envelope’s inner surface. forced-air heating systems and one that can
This value is based on the historical be used in those without such systems (see
approach to ventilating houses in which an Figures 1 and 2 for these configurations).
outdoor air intake duct is connected to the
return air plenum of a forced-air furnace;

2
temperature before it reaches the furnace
Bathroom exhaust
Principal exhaust
fan suitable for fan intended for heat exchanger and the living areas of the
intermittent use
continuous use house. (Very cold air passing over the heat
exchanger can cause premature deterioration.)
The use of heating ducts to distribute
Manual or
automatic
outdoor air. The outdoor air is then
control,
interlocked to Manual
distributed throughout the house by the
furnace fan control regular heat-distribution (duct) system.
The supplementary fans. These fans (e.g.,
Kitchen exhaust
fan intended for
kitchen and bathroom exhaust fans) make
intermittent use up the discrepancy between the capacity of the
Normal
heating principal exhaust fan and the minimum
ducts
required capacity of the system.
Manual control

Bathroom exhaust
Outdoor Principal exhaust fan intended for
air duct fan suitable for intermittent use
continuous use

Return air
plenum Manual or
automatic
control,
interlocked
to air handler Manual
control
Figure 1. Ventilation system configuration for a
house with a forced-air heating system Kitchen exhaust
fan intended for
intermittent use
Ventilation
The main features of the configuration ducts
for a house with forced-air heating are: High outlets

Manual control Duct heater


The principal exhaust fan. This fan is the
heart of the system. It draws air from Outdoor
air duct
throughout the dwelling. Although the Thermostatic
occupants and their activities determine its Supply fan control

operation, the fan should be capable of


operating continuously. At this time, how-
ever, there is no standard method of testing
and designating fans for continuous use.
Therefore, such a designation is not yet Figure 2. Ventilation system configuration for a
mandatory. house without a forced-air heating system
The principal exhaust fan is expected
to provide a relatively low level of ventila-
tion — 50% of the minimum required The main features of the configuration
capacity of the system (such that it can run for houses without forced-air heating sys-
continuously without excessive noise and tems are:
without excessive energy penalty). Its con- The principal exhaust fan. This fan
trol is placed in a central location, such as performs the same function as the fan in a
a living room, family room or hallway, and house with forced-air heating and is sized
it is wired directly to the furnace circula- and controlled in the same ways. However,
tion fan so that whenever the principal its control is wired to the supply fan rather
exhaust fan is turned on, the circulation fan than to a furnace circulation fan.
is also activated. The supply fan. This fan has the same
The outdoor air duct. When the furnace capacity as the principal exhaust fan and
circulation fan is turned on, it draws out- operates whenever the principal exhaust
door air through the outdoor air duct. This fan operates, drawing outdoor air in
air is then mixed with return air in the through the outdoor air duct.
return air plenum in order to increase its

Construction Technology Update No. 15 3


The outdoor air duct. When the supply in houses with spillage-susceptible
fan is turned on, outdoor air is drawn in combustion appliances, any such large
through this duct. Since, in this case, there exhaust devices (i.e., greater than 75 L/s
is no return air to temper the outdoor air, exhaust capacity) must be provided with
another means must be used to warm up make-up air.
this air before it is circulated to the living In the past, the NBC and other codes and
areas. standards tended to rely on the passive
The duct heater. This heater warms up the supply of make-up air through openings
incoming outdoor air before it reaches the provided for this purpose. This is no
supply fan. longer felt to be a reliable approach for a
The use of ventilation ducts to distribute simple, prescriptively described system
outdoor air. The outdoor air from the because it does not have sophisticated
supply fan is distributed through a rudimen- depressurization controls (such as those
tary system of small ducts installed for this provided in F326). According to the 1995
purpose. These ducts must go to each bed- NBC, make-up air must be provided by a
room and to any storey without a bedroom. supply fan that is automatically activated
Unlike heating ducts, they can be of com- whenever the exhaust device requiring
bustible materials. make-up air is activated. If spillage-
The supplementary fans. These fans have susceptible combustion equipment is not
the same sizes and functions as those in a used, make-up air does not have to be
house with a forced-air heating system. provided.
Sound level Even at the relatively low level of
The 1995 NBC requires all fans constitut- depressurization likely to occur when the
ing part of the ventilation system to have ventilation system is operated at its “high
sound ratings not exceeding 2 sones rate or episodic” level, an open fireplace
(53 decibels) with the exception of kitchen operating in its “die-down,” or smoldering,
exhaust fans, which are permitted to have stage can spill products of combustion into
sound ratings of 3.5 sones (60 decibels). the house. In the absence of more sophisti-
cated controls to prevent such levels of
Interference with other systems
depressurization (such as those provided in
The portion of the system that is suitable
F326), the only available safeguard is the
for continuous use includes the principal
installation of a carbon monoxide detector
exhaust fan along with either the furnace
in any room that has an open solid-fuel-
circulation fan or the supply fan (in houses
burning device. Where this is not a viable
without forced-air heating). When operating
option, the prescriptively described alter-
in this mode, the system is balanced since
natives must be abandoned in favour of a
the volume of air extracted by the principal
system that complies with F326.
exhaust fan is approximately equal to that
brought in by the other fans. Interference with the building envelope
The portion of the system that operates Because these configurations are either
infrequently, for short periods of time, pressure-neutral (when only the principal
(known as the “high rate or episodic” por- exhaust fan is operating), or mildly depres-
tion) includes the supplemental exhaust surizing (when other fans are operating),
fans, which operate when the principal they are not likely to pressurize the house
exhaust fan is not able to provide an ade- and therefore not likely to increase the
quate rate of air change. When operating potential for interstitial condensation in
in this mode, the system is unbalanced, the building envelope.
although it does not usually depressurize The Distribution Problem
the house significantly unless other In the two configurations described above,
exhaust devices (e.g., a clothes dryer) are the distribution of outdoor air to the rooms
used at the same time. However, if there are or spaces where it is needed is relatively
other large exhaust devices (e.g., a stove- simple in houses with forced-air heating
top barbecue) in the house, high levels of systems but somewhat more problematic in
depressurization can occur if these devices houses with other types of heating systems.
are operated on their own. For this reason,

4 Construction Technology Update No. 15


In the configuration shown in Figure 2, mechanical ventilation system) and of the
ducts must be added to a house that would possibilities the system offers for exercising
otherwise not need them. For this reason, some control over the ventilation of the
IRC researchers are investigating alternative house, there is a tendency to view the
methods of ensuring proper distribution of energy cost with some alarm and to seek
outdoor air in houses without forced-air some means of reducing it.
heating systems. To date, the findings can One way to do this is simply to turn off
be summarized as follows: the ventilation system, or to use it less;
• Ducted systems can provide adequate however, this can result in poor indoor air
distribution of outdoor air. quality, mould on interior building surfaces
• Central exhaust fans, such as those in and interstitial condensation in the building
kitchens and bathrooms, used without envelope. Another approach is to incorpo-
some other means of distribution, do not rate a means of recovering heat from
provide adequate distribution of outdoor outgoing indoor air and transferring it to
air to bedrooms. the incoming outdoor air. The heat recov-
• Distributed exhaust systems that have ery ventilator is the most commonly used
pick-ups in the upper storey rooms can equipment with this capability. (Figure 3
provide even distribution of outdoor air. shows how it can be used to satisfy the
An example of this type of system con- requirements of the NBC.) However,
sists of an attic-mounted exhaust fan ventilation systems with heat recovery
with manifolded intakes branching to all capability inevitably cost more than those
bedrooms. This system could be com- without. Therefore, this extra cost needs
bined with a central passive inlet vent to to be weighed against the cost of the
reduce the depressurization of the house energy saved.
and increase total indoor/outdoor air
exchange.
Bathroom exhaust
• The combination of a central exhaust fan fan intended for
with distributed passive air inlets does intermittent use

not achieve an even distribution of air


since the inlets on the upper level
become outlets in cold weather as a
result of stack effect. Under these cir- Manual control
cumstances, lower storey rooms receive
too much outdoor air, and upper storey
Kitchen exhaust
rooms too little. This approach might be fan intended for Normal
viable in milder climates in Canada. intermittent use heating ducts

• Closed bedroom doors with typically Manual or


automatic
sized door undercuts do not hinder the control for HRV
interlocked to
adequate distribution of air provided by Manual control
furnace fan
forced-air heating systems when the fur- Heat recovery
nace circulation fan is operating. ventilator
Supply fan
Heat Recovery
Because the cold air entering the house Principal
must be heated, indoor/outdoor air exhaust fan

exchange, whether provided by leakage or Return air


by mechanical ventilation, brings with it plenum

an energy and a cost penalty. In the past,


when this air exchange took place without Figure 3. Ventilation system configuration with a
the whirring of fans, people tended to heat recovery ventilator for a house with a forced-
ignore the energy cost or simply attribute it air heating system
to the need for the house to “breathe.” But
once there is a greater awareness of the air
exchange taking place (by means of a

5
This weighing of costs has been done in References
the Model National Energy Code for 1. ASHRAE 62-1989, Ventilation for
Houses, which includes regionally sensi- Acceptable Indoor Air Quality. American
tive requirements for all parts of Canada. Society of Heating, Refrigerating and
One such requirement deals with whether Air-Conditioning Engineers, Atlanta, GA.
or not heat recovery must be incorporated 2. Standard CAN/CSA-F326-M91,
into mechanical ventilation systems. In Residential Mechanical Ventilation
deciding whether or not heat recovery Systems. Canadian Standards
should be required in a particular region, Association, Etobicoke, ON.
the committee that developed this code 3. National Building Code of Canada, 1995.
employed extensive life-cycle cost analyses Canadian Commission on Building and
based on regional energy and construction Fire Codes, National Research Council
costs. The results can be summed up as of Canada, Ottawa.
follows: 4. 1989 Survey of Airtightness of New,
• for gas-heated houses, heat recovery is Merchant Builder Houses. Haysom,
required only in the coldest regions; J.C., Reardon, J.T., and R. Monsour.
• for oil- and electrically heated houses, Indoor Air ’90: The Fifth International
heat recovery is required almost every- Conference on Indoor Air Quality and
where in Canada. Climate, v. 4, Toronto, 1990.
5. Residential Air System Design. Heating
The Future of Mechanical Refrigerating and Air-Conditioning
Ventilation of Houses Institute of Canada (HRAI), Islington, ON,
In time, mechanical ventilation systems 1986.
will likely approach the ideal (see 6. Complying with Residential Ventilation
Construction Technology Update No. 14), Requirements in the 1995 National
as demand-controlled ventilation becomes Building Code. Canada Mortgage and
more practical and economical as a result Housing Corporation, Ottawa, 1996.
of research and development. At the same 7. Airtightness and Energy Efficiency of
time, it is possible that the amount of New Conventional and R-2000 Housing
indoor/outdoor air exchange required will in Canada, 1997. Canada Centre for
decrease. This could come about through Mineral and Energy Technology, Natural
the introduction of limits on pollutant Resources Canada, Ottawa.
emissions from building materials and fur-
nishings. However, our ability to identify
pollutants of concern and to set safe and Mr. John Haysom is a senior technical advisor
practical limits on emissions is still very with the Codes and Evaluation Program of the
limited. National Research Council’s Institute for
Finally, there is growing evidence that Research in Construction.
houses being built today are even tighter
than those tested in the 1989 survey. In Dr. J.T. Reardon is a research officer with the
light of this evidence, the continued viability Indoor Environment Program of the National
of the prescriptively described solutions Research Council’s Institute for Research in
in the NBC for houses that incorporate Construction.
spillage-susceptible combustion appliances
will have to be re-examined.

© 1998
National Research Council of Canada
May 1998
ISSN 1206-1220

“Construction Technology Updates” is a series of technical articles containing


practical information distilled from recent construction research.

For more information, contact Institute for Research in Construction,


National Research Council of Canada, Ottawa K1A 0R6
Telephone: (613) 993-2607; Facsimile: (613) 952-7673; Internet: http://irc.nrc-cnrc.gc.ca

You might also like