GENERAL NOTES

V-2603 Notas Generales


CONDENSATES STABILIZATION
DRUM 1. DELETED.
2. FOR EMERGENCY SHUT DOWN CAUSE AND EFFECT RELATION SEE DOCUMENT
LPG/F-PCF-GN-PRF-00-001 "CAUSE AND EFFECT CHART".
3. PROVIDE A SHORT RADIUS ELBOW INSTALLED AT SEPARATOR INLET.
4. IMPINGEMENT PLATE.
5. PSV INLET/OUTLET DIAMETERS CONFIRMED BASED ON FINAL VENDOR INFORMATION.
6. COMPENSATION SIGNAL FROM PRESSURE TO FLOW.
7. DRAINS AND VENTS ACCORDING TO DISCHARGE TYPE ARE GOING TO THE FOLLOWING P&DS:
DISCHARGE TYPE P&ID
NOTE 7 PU-PRE-07-074-1/1
VC COLD FLARE
FIRE PU-PRE-07-071-1/1
VH 1½"G3" NOTE 5 SET @425 PSIG VL LOW PRESSURE FLARE PU-PRE-06-061-1/1
SET AT H NOTE 10 VH HIGH PRESSURE FLARE MP-PRE-05-002-1/1
650 psi-g PIC 50 - 100%
NOTE 7 DC CLOSED DRAIN PU-PRE-09-091-1/2-2/2
2604
PSV L VH 8. DELETED.
2602A 9. BOOT SPECIFIED FOR OPERATIONAL ROUTINES PURPOSES.
10. PARALLEL CONTROL DEFINED TO ENSURE PROPER OPERATION OF PV-2604A/B.

4"-VH-26014-A2A1-VA
3/4"BA-14
4"-VH-26013-A2A1-VA
4"BA-15FP 4"x3" 11. HAND SWITCH IS LOCATED AT MATRIX PANEL IN CCR.
PY
LO A2A1 12. FOR TYPICAL DRAIN ARRANGEMENT DETAILS SEE P&ID: LPG/F-PCF-GN-PRE-00-001-01

3"x 1½"
FIRE B2A1 2604B
1½"G3"
SET AT NOTE 5

NOTE 10
0 - 50%
RO
650 psi-g HH
PSV PV 2604

B2A1
A2A1
PI
2602B 2604B
2605
SPARE LL

3/4"BA-14
4"BA-15FP 4"x3"

3"x 1½"
LO 3"x2" 2"300# 3"x2" 4BA-05

3/4"BA-01
A2A1 4"x3"
FO LO
B2A1
NOTE 6
3/4"GL-01 3/4"GL-01 NOTE 2 SEE DETAIL "E"
A2A1 1A11 FI NOTE 12
B2A1 2"GL-03 3/4"BA-01 3/4"BA-01
LC 2604
SEE DETAIL "H" SEE DETAIL "H"
NOTE 12 NOTE 12
PIT PY
2605 2604A
LC LO FIT

3/4"MDB2A1-2
FP FP TI

3"BA-05
3"BA-05 3"BA-05 2604 PV
2614

LO
2604A VAPOR FEED
1½" TO CT-2603
3/4"BA-01
2"BA-05 4"-PG-26004-B2A1-VA 4"-PG-26005-B2A1-VA
LC MP-PRE-26-004-1/1
4"x3" 3"-300# 4"x3"

3/4"BA-01

3/4"BA-01

3/4"BA-01
4"x2" 4"x2" 4"BA-05 4"BA-05

(DO NOT POCKET)


2"
3/4"GL-01

CC FC DETAIL "A"
MIXED CONDENSATES 2601 SEE DETAIL "E"
FROM HE-2614 SEE DETAIL "E" NOTE 12

3"-PG-26012-B2A1-VA
MP-PRE-26-001-1/1 6"-PC-26003-B2A1-VA ZLO ZLC
NOTE 12
XXX XXX
I
3"BA-05 3"GL-03
PIT
2604 I I I
SDY

2"MDB2A1-2
XXX
4"BA-05
2"BA-05
6"BA-05

SEE DETAIL "K"


2"BA-05
2"BA-05

3"BA-05 NOTE 12 ZSO ZSC PST


SEE DETAIL "J" XXX XXX XXX
HH NOTE 12
LI
2"BA-05 SDV
2602 V-2603 HHL: 62 in XXX
HL: 42 in 2"BA-05
LL: 22 in
NOTE 3 LLL: 12 in
GW NOTE 4 GW
LIT 24" 24" LG LIT
1A11 2602 MH SEE DETAIL "I" MH 2603A 2603
NOTE 12
NOTE 2
2"BA-05 ECC PLANT
2"BA-05 LOCAL EMERGENCY
N2 HOSE 2"CK-04 V.B.
CONNECTION
2"BA-05 HS HS
3/4"BA-01

2"BA-05
2"BA-05

SP H 2"BA-05 1452B 1A11 1452


2"BA-05 3"BA-05
3/4"GL-01

038 C 6"BA-05
5 ft

LG
2"BA-05

HL: 20 in HS
TI TIT TE LL: 8 in 2604
2613 2613 2613 1452A

3/4"GL-01 NOTE 11

2"BA-05 2"BA-05 3/4"BA-01

THIS DOCUMENT IS PROPERTY OF TIPIEL SA IT MAY NOT BE COPIED, REPRODUCED AND/OR CIRCULATED WITHOUT AUTHORIZATION
ESTE DOCUMENTO ES PROPIEDAD DE TIPIEL SA Y NO DEBE SER COPIADO, REPRODUCIDO Y/O CIRCULADO SIN SU AUTORIZACIÓN.
MIN
2"GL-03

2"GL-03

2"BA-05
H
B2A1 B2A1 LIC
2"-MG-26006-B2A1-VA
VISIBLE A2A1 A0G1 2603
OPEN/ L TI
2"-DC-26010-A2A1-VA

SP HS DOCUMENTOS DE REFERENCIA
2"-VC-26264-A0G1-N

I CLOSE Reference Documents


2"GL-03 2615
313 J 2603B DOCUMENTO No. DESCRIPCIÓN
REF. Document No. REV. Description
NOTE 9 H
FIC
NOTE 2 2603 TIT
L
CLOSE 2615
3CQ 2BG 1A11
DC VC REVISIONES
Revisions
NOTE 7 NOTE 7 DETAIL "A" FIT TE 0 29-JUN-2018 ISSUED FOR CONSTRUCTION E.GARCIA I.SANCHEZ O.SANGUINOD.MANRIQUE

Calle 38 No. 8-62 Bogotá - Colombia.


SDV 2603 FV 2615 (CONTRACT 3010893)
D3 26-APR-2018 DETAILED ENGINEERING FINAL ISSUE E.GARCIA I.SANCHEZ O.SANGUINOD.MANRIQUE
2603 2603 LIQUID FEED (CONTRACT 3010893)
1½" TO CT-2603
6"-PC-26008-B2A1-VA 6"-PC-26009-B2A1-VA MP-PRE-26-004-1/1
A2 01-FEB-2018 ISSUED FOR COMMENTS M.SANTAMARIA I.SANCHEZ O.SANGUINOD.MANRIQUE
(CONTRACT 3010893)
6"BA-05 (DO NOT POCKET) (TWO PHASE FLOW)
3/4"BA-01

6"300# 6"x3" 6"x3" 6"BA-05 6"x4" 4"300# 6"x4" D2 29-DEC-2016 APPROVED FOR DESIGN (REVISED AS SHOWN) H.MONTOYA O.SANGUINO A.ARRIETA

3/4"BA-01
3" C.LOPEZ

3/4"BA-01
FC FC D1 15-NOV-2016 APPROVED FOR DESIGN C.LOPEZ H.MONTOYA O.SANGUINO A.ARRIETA
A1 28-SEP-2016 ISSUE FOR COMMENTS C.LOPEZ H.MONTOYA O.SAGUINO A.ARRIETA
SEE DETAIL "D" FECHA DESCRIPCIÓN PREPARÓ CHEQUEÓ APROBÓ AUTORIZÓ
SEE DETAIL "D" REV. Date Description Prepared by Checked by Approved by Authorized by
NOTE 12 NOTE 12

4"BA-05 4"GL-03

INGENIERÍA COMPRAS CONSTRUCCIÓN Y PUESTA EN


SERVICIO DE LA PLANTA DE ESTABILIZACIÓN DE
CONDENSADOS DEL CPF CUPIAGUA

DRUMS V-2603
TYPE HORIZONTAL
PIPING AND INSTRUMENTATION DIAGRAM
HEIGHT / LENGTH 26.5 ft
DIAMETER 91 in CONDENSATES STABILIZATION DRUM
OP. PRESSURE 425 psig
OP. TEMPERATURE 84 °F ESCALA CONTRATO PLANO No. HOJA
Scale Contract Drawing No. Sheet REV.
DES. PRESS. INT/EXT 650 psig
DES. TEMPERATURE 140 °F / 40 °F
DE
MATERIAL C.S N/A 3010893 LPG/F-PCF-MP-PRE-26-003-1/1 01 Of 01 0
TRIM NUMBER PC-26086-B2A1-VA
CÓDIGO TIPIEL:
1348-0000-PID-0021-03-01
ARCHIVO CAD: LPGFPCFMPPRE26003.1-1.0 PID - CONDENSATES STABILIZATION DRUM.dwg FDP ISO A1_1 : ISO A1 841x 594mm
CAD File