Professional Documents
Culture Documents
Contents: Page
LEDs
Mode selector
AUI/ITP interface
15-pin sub-D
with slide lock
SEND/RECEIVE Interface
S7 Communication
PG/OP Communication
Installation
Plug in the CP and screw it tight
Connect the CP to Industrial Ethernet
Provide 24V voltage supply
Notes
You must use the same voltage source that is used for the CPU or IM361
The two flaps at the front must be kept closed during operation.
When installing the module, ensure that the ventilation slits at the top and
bottom are not covered and that the air can circulate freely.
SEND/RECEIVE Interface
Max. No. of connections 16
Max. data length for SEND
or RECEIVE block 8 Kbytes
from CP Version 5 (FW V3.00)
and NCM for IE V 4.02 SP1
S7 Communication
Max. No. of connections 16
Multiprotocol Operation
Max. No. of connections 32
LEDs
Mode selector
AUI/ITP interface
15-pin sub-D
with slide lock
SEND/RECEIVE Interface
S7 Communication
PG/OP Communication
Time-of-Day Synchronization
Functions
SEND/RECEIVE interface
with module 6GK7 443-1EX02-0XE0 and NCM V5 SP2 with FETCH/WRITE
functionality
Provides an interface for data communication based on OSI Layer 4
Between SIMATIC S7 and
- SIMATIC S7-300/-400
- SIMATIC S5
- Computer/PC
S7 Communication
Between SIMATIC S7 and
- other SIMATIC S7
(S7-300 server only,
S7-400 client and server)
- HMI devices
- PC
This type of communication requires no further configuring of the CP443-x
PG/OP Communication
Remote programming of S7 stations connected to the same network.
From STEP7 V5 remote programming of S7 stations in other networks is also
possible with the following modules and all later versions
– 6GK7 443-1BX01-0XE0 (CP 443-1 with modified hardware)
– 6GK7 443-1EX01-0XE0 (CP 443-1 TCP with modified hardware)
– 6GK7 443-1EX02-0XE0 (CP 443-1 Multiprotocol module)
SEND/RECEIVE Interface
S7 Communication
PG/OP Communication
Time-of-Day Synchronization
Time-of-day synchronization
Slots The CP can be plugged into any rack whose slots have P and K bus connections.
That is: - Central Rack CR2
- Universal Rack UR1 or UR 2
as either central controller or expansion unit
The CP can be plugged into all slots in the rack which have P and K bus
connections, apart from the slots for the power supply and the main CPU.
Note A K bus connection is essential when using Universal Rack UR1 or UR2 as an
expansion rack!
SEND/RECEIVE Interface
Max. No. of connections 64
using module
6GK7 443-1EX02-0XE0
Max. No. of TCP connections 10
Max. data length for SEND
or RECEIVE block 8 Kbytes
from CP 443-1 Version 7
from CP 443-1 TCP Version 5
and from NCM for IE V 4.02 SP1
S7 Communication
Max. No. of connections 48
Multiprotocol Operation
Max. No. of connections 64
The TPETXD / TPETXD_N and TPERXD / TPERXD-N signals form the ITP interface
Configuring
Via MPI or Ethernet LAN
with
NCM S7 for Industrial Ethernet (NCM IE)
executable with STEP 7 under Windows 95/98/NT
Version V4.x executable with STEP 7 V4.02
– Can be ordered as optional software on CD-ROM with a license
diskette
Version V5.x executable with STEP 7 V5.x
– Can no longer be ordered as a separate product
– Included with STEP 7 V5.x (STEP 7 CD)
– Licence no longer required
– NCM S7 manuals also included on the STEP 7 CD
Memory NCM IE requires approx. 30 Mbytes of memory on the hard disk, depending
Requirements on the operating system and file system used.
Readme File Before you start using NCM IE be sure to read the notes in the Readme file. This
contains additional information about NCM IE .
Service Pack (SP) You will find information about any necessary service packs and hot fixes at the
following Internet address
Internet http://www.ad.siemens.de/csi/net
CP 1430 TF
SIMATIC S5
CP 1430 TCP
CP 1473 MAP
Communication Functions
and Services
– PG/OP communication
– S7 communication
– S5-compatible communication
– Standard communication
IT
Socket
MAP
Key
S5-Compatible
Communication SEND/RECEIVE, Fetch/Write
O S5-Compatible
Communication SEND/RECEIVE