Professional Documents
Culture Documents
82274343
82274343
CHAPTER 3
3.1 INTRODUCTION
when load variation occurs. By comparing the rotor speed r and reference
1 Kg
X E ( s) PC ( s) F ( s) (3.1)
R 1 sTg
33
PG ( s) Kt
G( s) (3.2)
X E ( s) 1 sTt
The typical range of turbine time constant Tt varies from 0.1 to 0.5
seconds (Elgerd 1983).
ΔPG=ΔPD (3.3)
WK .E H Pr kW - s
0
(3.4)
H = inertia constant
2f
WK . E H Pr 1 0 (3.6)
f
∆f = change in frequency
d
WK .E 2HP0 r d f (3.7)
dt f dt
PD
f Df (3.8)
f
36
2 HPr d
PG PD f Df (3.9)
f o dt
PG s PD s
F s (3.11)
2H
D 0 ( s)
f
Kp
F s PG s PD s (3.12)
1 sT
p
2H
where Tp = Power system time constant
Df 0
1
Kp = Power system gain
D
V1 V2
Ptie,1 sin( 10 20 ) (3.13)
X 12
where
where
V1 V2 cos( 10 20 )
T12 = Synchronizing power coefficient
Pr1 X 12
deviation
𝜔 = 2𝜋𝑓 (3.15)
1 d
f (3.16)
2 2 dt
f
1 d
(3.17)
2 dt
2 fdt (3.18)
39
Ptie,1 2T12 f1dt f 2 dt (3.19)
Where Δf1 and Δf2 are incremental changes in frequency of area 1 and 2
respectively
Similarly,
Ptie, 2 2T12 f 2 dt f1dt (3.20)
V2 V1 cos( 20 10 ) Pr1
where T21 (3.21)
Pr 2 X 12 Pr1
P
T21 r1 T12 a12T12 (3.22)
Pr 2
p
a12 r1
Pr 2
The incremental power balance equation for area 1is given by,
2H1 d
PG1 PD1 (f1 ) B1 f1 Ptie,1 (3.24)
f 0 dt
1
Where K p1 Power system gain for area 1
D1
2H1
T p1 = Power system time constant for area 1
f 0 D1
2T12
Ptie,1 ( s) F1 (s) F2 (s) (3.26)
s
2T21
Ptie, 2 ( s) F2 (s) F1 (s) 2a12T12 F1 (s) F2 (s) (3.27)
s s
∆F = frequency change, Hz
different entities and VIU structure is not there. Instead of a single utility, it is
replaced by GENCOs, TRANSCOs, and DISCOs. A number of GENCOs and
DISCOs are there in a deregulated power system. Therefore, for the
transaction of power, a DISCO can enter into a mutual contact with any
GENCO. “Unilateral transactions” or “poolco transactions” refers to those
transactions, in which, a DISCO demands power from GENCOs of its own
area. “Bilateral transactions” are those in which a DISCO can enter into a
contract with GENCO in another area, for power transaction (Kumar et al.
1997). An impartial entity named ISO enables the transactions. In addition to
controlling the transaction of power, many “ancillary services” need to be
controlled by ISO. AGC is one of the ancillary services done by ISO.
(3.29)
2T12
Ptie12,act F1 F2 (3.30)
s
2 4 4 2
Ptie12,sch cpf ij PLj cpf ij PLj (3.32)
11 j 3 i 3 j 1
The Area Control Error (ACE) signals can be generated using tie-
line error signals.
apf1 0 0 0
0 apf2 0 0
apf_matrix= (3.36)
0 0 apf3 0
0 0 0 apf4
distributed between the maximum and minimum limits and the ideal values of
scaling parameters are determined, which limits or reduces the total error
function, in the specified time period. The objective function is initially
defined, focusing on the desired constraints and specifications, in the process
of designing a modern heuristic optimization technique based controller. The
integral square error (ISE) criterion is made use of as an objective function for
optimizing the proposed controller performance. The objective function can
be stated as (Hota & Mohanty 2016)
t
F ISE f1 f 2 Ptie dt
2 2 2
(3.39)
0
Minimize F
Subject to
Where F is the objective function, SFi min and SFi max are the minimum and
maximum value of the control parameters (Karthikeyan 2013).
49
From the literature survey, it was found that plenty of research has
been performed in the LFC of the conventional interconnected power system
and a few works were done in the LFC of a deregulated power system. The
LFC in a deregulated power system is a difficult process due to its complexity.
Most of the earlier works on LFC of deregulated power system were done using
conventional controllers. The performance of a conventional controller depends
upon the value of its gain. The conventional controllers are suited for linear
systems but power system is nonlinear, and, when operating point changes, the
value of gain will not change. Therefore, to overcome this problem, many
researches were focused on various optimization techniques, to find the optimal
gains of conventional controllers. This is due to the fact that conventional
controllers are simple and reliable but they are not suited for nonlinear systems.
used to find the optimum scaling factors of the FLC. Thus, the key objectives
of the research work are concluded as follows:
3.7 SUMMARY