Breakthrough technology
Innovation
Standards are at the center of our product development.
Groundbreaking research and design has
resulted in innovative LV switchgear, pro-
viding users with greater quality, safety
and reliability. Today’s LV products feature
meticulously designed technology: even
the casing material is used in the PA (Poly-
mer Ablation type Auto-Puffer) to provide
greater safety and high voltage breaking
performance.
2
Contents
Contents
3
The six stoutly reasons
High reliability
Safe and fault-free operation is guaranteed
by various protective mechanisms and
safety functions. Reliability is provided due
to high operating durability.
Global
In addition to complying with well-known
international norms and standards, the low
voltage switchgears are also certified by
several marine approvals.
4
The six stoutly reasons
Electronic trip
relay
Intelligent
Magnetic contactor with mounted thermal The main functions, including trip status,
overload relay of the MS-N series alarm and load current are displayed on the
LCD screen of the SUPER AE and can also be
output as signals.
Customer friendly
Functionality, compatibility and perfect
Thermal overload relay mechanical design are the main features
Auxilliary contacts of the low voltage switchgears supplied by
included
Mitsubishi Electric .
Not all features are available on all LVS. Please check applicability.
5
The six stoutly reasons
PERFORMANCE
A diverse product range helps you make the right product choice.
6
The six stoutly reasons
7
Air Circuit Breakers
SUPER AE –
Air Circuit Breakers
The range of air circuit breakers and load
interrupter switches is complemented by
a comprehensive range of accessories. In
contrast to earlier models it is now possible
to save space by installing some accesso-
ries (for example the UVT undervoltage trip)
inside the breaker unit.
All live components in the vicinity of the
control connections have IP20 protection
rating.
Individually confi-
gured protection
The circuit breakers are delivered with an
electronic trip relay. It is available in versi-
ons for all standard power supply voltages.
Optional modules are also available for most
common applications like protecting trans-
formers, cables, motors and generators. This
Mitsubishi Electric Air Circuit Breakers are built for the global demands of the 21st century ensures optimum protection for long time,
short time and instantaneous tripping.
Very user-friendly In addition to options like pre-alarm,
design ground fault and earth leakage protection,
the electronic trip relay provides complete
All breakers in the series are available in protection against overloads and short cir-
both 3 and 4 pole versions with fixed or dra- cuits. The protection characteristic can be
wout configurations to suit your individual adjusted individually for the needs of your
requirements. There are only three standard application.
sizes, making planning much easier.
The main functions, including trip status,
alarm and load current are displayed on
the LCD screen and can also be output as
signals. For easy and quick recognition of
alarms, the screen automatically turns red
when a fault is detected.
Frame size 1
Frame size 2
Frame size 3
8
Air Circuit Breakers
Standard PC
MELSECNET/10- MELSECNET/10
Interface Card
Broad perfor-
mance range PLC
Rated short circuit breaking capacity Ics Rated short time withstand current Icw Profibus/DP module
9
Moulded-case circuit breakers
WSS – Moulded-Case
Circuit Breakers
With its innovative breaking technology
all Mitsubishi Electric breakers offer grea-
ter safety and even faster circuit-breaking
speed through the use of the latest switch-
off technology and innovative engineering,
with an innovative electronic trip relay.
Mitsubishi Electric breakers of the WS-V and
WSS series are available in 4 different versi-
ons which can be used for a wide range of
applications:
10
Moulded-case circuit breakers
*optional
11
Magnetic contactors and relays
MS-N –
Magnetic Contactors
Incorporation of
CAN terminal for
simple wiring
By adopting a CAN terminal, there is no
need to remove the screws. The integra-
ted terminal screw and screw holder set in
a plastic screw holder, prevent the loss of
screw. When each pole is moved and the
screw loosened, the screw naturally sets in
the screw holder. This is Mitsubishi Electric
’s original patented CAN terminal.
Unified design
The design of the MS-N Series is unified with
a white front face brightening the inside of
the panel and providing a cleaner image.
Mitsubishi Electric magnetic contactors protect your investment Reduced arc space
By developing a new extinguishing mecha-
nism, the arc space has been reduced to
Reliable motor approximately 1/3 against the previous
protection generation. The new contactors are now
significantly smaller, reducing the need for
Compact dimensions, modular expansion
costly cubicle space and allowing the con-
options and a power-saving design – those
tactors to fit easily and neatly into small
are the key characteristics of Mitsubishi
recesses of a machine or cabinet.
Electric ’s low-voltage switchgear products.
The MS-N series includes magnetic contac-
tors, thermal overload relays and contactor
relays. DIN installation rail support and stan-
dardised terminal spacing make installation
and wiring particularly simple.
12
Magnetic contactors and relays
Improved magnet
Use of a spiral kick-out spring improves
the dynamic balance of the moving parts, Coil Stationary core
extending the core life and generally stabi-
lizing the core movement. Through the use
Efficient electromagnet thanks to advanced
of modern technology, the efficiency of the engineering
magnet has been improved. The contactor
can withstand a voltage drop of 35 % with
the contact closed.
13
Application solutions
A wide field of
applications
Construction
– Steel bridge manufacturing
– Tunnel boring systems
Food and drink
– Bread manufacture
(mixing/baking)
– Food processing
(washing/sorting/slicing/packaging)
Leisure
– Multiplex cinema projection
– Animated mechatronics
(museums/theme parks)
Medical
– Respiration machine testing
– Sterilization
Pharmaceutical/chemical
– Dosing control
– Pollution measurement systems
– Cryogenic freezing
– Gas chromatography
– Packaging
Mitsubishi Electric low voltage switchgears are used in a wide range of areas. Plastics
– Plastic welding systems
– Energy management systems for
Mitsubishi Electric operates eight branches Mitsubishi Electric products are found in a
injection moulding machines
in Europe, where it has maintained a pre- variety of industrial, infrastructure and ser-
– Loading/unloading machines
sence for more than 25 years and developed vice sector contexts, ranging from critical
– Blow moulding test machines
a constantly growing and far- extending applications in the pharmaceuticals indus-
– Injection moulding machines
network comprising links to other compa- try to state-of-the-art leisure and entertain-
nies and reliable partnerships. ment facilities. Here are just a few examples Printing
of recent applications:
On the technical side, three manufacturing Textiles
and automation centres form the basis of Agriculture
Transportation
tailored automated solutions, further cen- – Irrigation systems
– Sanitation on passenger ships
tres already being planned. – Plant handling systems
– Sanitation on rail rolling stock
– Sawmills
A Europe-wide network, the European – Fire tender, pump management
Service Group (ESG), provides interfaces to Building management – Waste disposal truck management
experienced engineers and offers distribu- – Smoke detection monitoring
Utilities
tors support throughout every phase of the – Ventilation and temperature control
– Waste water treatment
project. – Lift (elevator) control
– Fresh water pumping
– Automated revolving doors
– Telephone management
– Energy management
– Swimming pool management
14
Low Voltage Switchgears Productrange
FX Family
Product catalogue for programmable logic controllers and
Brochures
accessories for the MELSEC FX family
HMI Family
Product catalogue for operator terminals, supervision software
and accessories
FR Family
Product catalogue for frequency inverters and accessories
MR Family
Product catalogue for servo amplifiers and servo motors as well as
motion controller and accessories
Q/L Family
Product catalogues for programmable logic controllers and
accessories for the further MELSEC PLC series
Robots Family
Product catalogue for industrial robots and accessories
Automation Book
Overview on all Mitsubishi Electric automation products, like frequency
inverters, servo/motion, robots etc.
2
Contents
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
6
10
3
SAE – Base Units
4
SAE – Base Units
1 2 3 4 5
Type Technical standards Connection Drawout type accessories Electrical accessories 1
AE1000-SW IEC 60947-2 Drawout type Cell switch Auxiliary switch
AE1250-SW EN 60947-2 (CE) Horizontal terminal Shorting b-contact Motor charging device
6 7 8 9 J
Mechanical accessories Electronic trip relay Relay accessories Network Special environment
Push button cover General use Extension module CC-Link® Interface unit Moisture-fungus treatment
Counter WS type Display Profibus DP Interface unit Corrosion resist
Cylinder lock Generator protection use MCR switch MODBUS® Interface unit
à Terminal cover WM type Neutral CT I/O unit
Door frame On request: External ZCT
Dust cover Special use VT-W unit
Interphase barrier WB type
Mechanical interlock
Door interlock Optional
G1: Ground fault protection
E1: Earth leakage protection
AP: 2nd Additional Pre-alarm
N5: Neutral pole 50 %
protection
For details on our full range including accessories contact your local distributor
5
SAE – Base Units
Specifications
SUPER AE – WORLD SUPER SERIES Breaker type AE 1000- SW AE 1250- SW AE 1600- SW AE 2000- SWA
1 Frame size
Rated insulation voltage (AC V) 50/60 Hz
A
Ui
1000 1250
1000
1600 2000
6
SAE – Base Units
7
SAE – Base Units
Connections
Connection arrangements
1 The following connecting methods are available for the AE1000-SW – AE3200-SW.
Connection Horizontal connection Vertical connection Front connection Vertical terminal adapter Front terminal adapter
SAE – Base Units
Fixed type — —
Drawout type
The following connecting methods are available for the AE2000-SWA, AE4000-SWA and AE4000-SW – AE6300-SW.
Fixed type
(FIX-VT)
Drawout type
(DR-VT)
Special equipment
Remark (on request)
Connection image: AE2000-SWA, 3-pole type
For AE2000-SWA, AE4000-SWA, AE4000-SW, AE5000-SW and AE6300-SW models, vertical terminal only is available.
Available connections
Breakers
A1000-SW AE1250-SW AE1600-SW AE2000-SWA AE2000-SW AE2500-SW AE3200-SW AE4000-SWA AE4000-SW AE5000-SW AE6300-SW
Connections
Horizontal U U U — U U U — — — —
Fixed type FIX-VT — — — U — — — U U U U
(FIX) FIX-VTA u u u — u u u — — — —
FIX-FTA u u u — u u u — — — —
Horizontal U U U — U U U — — — —
DR-VT u u u U u u u U U U U
Drawout type DR-FT
u u u — u u u — — — —
(DR)
DR-VTA u u u — u u u — — — —
DR-FTA u u u — u u u — — — —
V Standard v Option — Not available
8
SAE – Base Units
Further elements that must be ordered: AE1600-SW AE1600-SW 3P Fix, Bare, AX10 193923 AE1600-SW 4P Fix, Bare, AX10 193924
v Accessories as required AE2000-SW AE2000-SW 3P Fix, Bare, AX10 193929 AE2000-SW 4P Fix, Bare, AX10 193930
AE2500-SW AE2500-SW 3P Fix, Bare, AX10 193931 AE2500-SW 4P Fix, Bare, AX10 193932
AE3200-SW AE3200-SW 3P Fix, Bare, AX10 193933 AE3200-SW 4P Fix, Bare, AX10 193934
AE2000-SWA AE2000-SWA 3P Fix, Bare, AX10 193925 AE2000-SWA 4P Fix, Bare, AX10 193926
AE4000-SWA AE4000-SWA 3P Fix, Bare, AX10 193935 AE4000-SWA 4P Fix, Bare, AX10 193936
AE2000-SWA AE2000-SWA 3P D/O, Bare, AX10 193927 AE2000-SWA 4P D/O, Bare, AX10 193928
AE4000-SWA AE4000-SWA 3P D/O, Bare, AX10 193937 AE4000-SWA 4P D/O, Bare, AX10 193938
9
SAE – Accessories
P1
HID
BIS
SU
MIT
M CR
INS 8T6422412 68
10
MP1E Ir0(A)= 10 1216Ii(xIr6016
0) 1
TNY W
U18000 151.1.2 15 2025304 ILx.2 )
R .4601.1.515. 0 0T.1L.0(s
ERR% 6.060.10.3
PAL .5Ir44).5500..53 )0.5O
LIL 2.5IL33(x I2tFM
F
ILTdLSI1.52 dIr)(O I2tTdN s(sAR
IsI2 IP A L
(IxpL)TA ItTsLIdi Isx TR .1015
.3.15.10.00.3.5
E 0.50.7 00.8.05 1.50.8
TYP G I1g0.10.3 10.0.91.53.0Tg3).0 (s
RNU FgxIn)( 2REETS T
GRT Ig .8.941.0 TRL/S )OSC
S.7T6 O VE(LE K
TE .68Ip
Lifting hooks HP
10
SAE – Accessories
In addition to manual operation, the closing There is always the option of manual operation
spring can be charged automatically by an in an emergency. A closing coil (CC) is required
electric motor every time the breaker is closed
(ON charging method).
for closing the breaker by remote control, and a
shunt trip device (SHT) is required for opening
it in this way.
2
If the closing spring is to be charged automati-
cally whenever the breaker is opened, then this This warrants the prevention of pumping, both
SAE – Accessories
can be done through an additional auxiliary electronically and mechanically. The circuit of
contact (AXb) (OFF charging method). As soon the motor is separate from the ON/OFF circuit
as charging is completed, a visual display on the (CC, SHT).
front says “CHARGED”.
The “CHARGED” signal is also available via the
413 (TS+) and 414 (TS-) terminals (included in
the standard MD configuration).
Order information Art. no. 168514 168515 168516 168517 168518 168519
11
SAE – Accessories
This is the device that automatically trips the Time range for tripping time:
breaker when the circuit voltage drops below INST (0.2 sec or less)/0.25 sec/0.5 sec/
the nominal voltage, and comprises a UVT coil 0.8 sec/1.0 sec/1.5 sec/3 sec.
and UVT controller.
MITSUBISHI
2 Time delay
0.5s or more
D1
SAE – Accessories
IN1 OUT3
D1
UVT controller External unit (attached
to UVT controller) UVT controller
D2
Trip button IN2 OUT4 D2
DT1 UVT coil Trip contact UVT coil
DT1
DT2 min 0.2 sec
max. 2 m DT2
Breaker max. 2 m Breaker
Order information Art. no. 203341 203342 203343 203344 203345 203346 203347 203348
Accessories UVT coil: art. no. 168525; UCON label: art. no. 168526 (Packing unit: 10 pcs)
Notes:
– Please order for each UCON one UVT coil, and for delay setting one UCON lable.
– In case of 380–460V AC, the external unit is attached.
– The operating time is a guarantee value when it drops from 85 % or more of rated voltage.
– Time delay should be allowed for 1.5 s between applying the voltage to the UVT and closing the breaker.
– If a remote trip function is required, remove the shorting bar (DT1–DT2) and connect a normally closed switch, rated 0.5 A at 150 V DC across them.
– Usage ambient temperature is a range of max. 40 °C to -5 °C.
The closing coil is a device to close the breaker zz Closing time is from the initial energization
by remote control. Only one closing signal of the closing coil to the completion of the
(about 100 msec.) is sent even when the closing closing of the main contacts.
coil supply is maintained ON. zz As CC is one-pulse driven, it is not necessary
zz An interlock to prevent pumping is provided to insert AXb for burning prevention pur-
electrically. poses. Inserting AXb will cause anti-pumping
function to be ineffective.
12
SAE – Accessories
Specifications
Rated voltage
SHT-DO48-W
(V) 24–48 DC
SHT-A500-W
380–500 AC
SHT-AD250-W
100–250 (AC/DC)
2
Applicable voltage range (V) 16.8–52.8 266–550 70–275
SAE – Accessories
Operating voltage (V) 24/48 380–500 100/250
0.5/0.7 (AC 380 V 250 VA, 0.4/1.4 (AC 100 V 100 VA,
AC (A) —
Inrush current AC 500 V 300VA) AC 250 V 150 VA)
(peak value)
DC (A) 2.5/6.0 (DC 24 V 100 W, 0.6/1.6 (DC 100 V 100 W,
—
DC 48 V 200 W) DC 250 V 200 W)
Closing time a (sec) max. 0.04 or less max. 0.04 or less max. 0.04 or less
C2 SHT
This is the contact that is used to remotely indi- zz The chattering time at the time of contact
cate the ON or OFF status of the breaker. ON-OFF is below 0.025 sec.
zz The a and b contacts may turn simultane- zz For special environment specification, the
ously to ON instantaneously at the time of contact capacity gets deteriorated. Apply for
changing the contact; Pay attention to the further detail.
contact state when designing circuits.
Counter (CNT)
58
02
00
00
13
SAE – Accessories
The cell switches can be set for all the Switch function Disconnected
Disconnected Connected
Connected
relevant positions, i.e. connected, test and
Disconnected
discon. Test
test Operation
operation
disconnected.
Each cell switch consists of 4 individual
switches.
CONNECTED
2 CL–C
TEST
CL-T
DISCONNECTED
SAE – Accessories
CL-D
Cell switch
Specifications CL-4-W BIF-CL-W a
Load Resistive Inductive Resistive Inductive
AC 460 V 5 2.5 5 2.5
AC 250 V 10 10 10 10
AC 125 V 10 10 10 10
Contact capacity (A)
DC 250 V 3 1.5 3 1.5
DC 125 V 10 6 10 6
DC 30 V 10 10 10 10
Maximum contacts Total 4c
The interlock device locks the circuit breaker There are two locking options available:
into the OFF position. zz Cylinder lock (CYL)
The relevant key can only be taken out in the zz Castell lock (CAL) a
OFF position of the circuit breaker, so that it
can also be used for unlocking other breakers.
Order information Art. no. 168539 168540 168541 168542 168543 168544
a The closing basis for the Castell lock can be designed individually. Further details on request.
The safety shutters cover the main conduc- The safety shutters can also be locked with
tors of the cradle side (supply and load side) a mechanical locking device (SST LOCK). The
automatically when the circuit breaker is padlocks have to be supplied by customer.
drawn out.
When checking the main circuit, the safety
shutters on the supply and load sides can be
opened independently of one another.
14
SAE – Accessories
SAE – Accessories
Shorting b-contact (SBC)
Vertical terminal adapters allow you to turn For AE2000-SWA, AE4000-SWA, AE4000-SW,
power connection by 90°. AE5000-SW and AE6300-SW models, vertical
terminal only is available.
FTA- FTA- FTA- FTA- FTA- FTA- FTA- FTA- FTA- FTA- FTA- FTA-
Specifications 163F-W 164F-W 253F-W 254F-W 323F-W 324F-W 163D-W 164D-W 253D-W 254D-W 323D-W 324D-W
AE1000– AE1000– AE2000– AE2000– AE3200-SW AE3200-SW AE1000– AE1000– AE2000– AE2000–
Application (breaker) AE3200-SW AE3200-SW
AE1600-SW AE1600-SW AE2500-SW AE2500-SW AE1600-SW AE1600-SW AE2500-SW AE2500-SW
Pole 3 4 3 4 3 4 3 4 3 4 3 4
Typ Fixed Drawout
Shipping contents pieces 6 8 6 8 6 8 6 8 6 8 6 81
Order information Art. no. 169331 169332 169333 169334 169335 169336 169337 169338 169339 169340 169341 169342
15
SAE – Accessories
This is the device to prevent parallel charge zz In case of drawout type,the interlock works
of 2 or 3 units of breakers, and it can interlock at “CONNECTED” position, and in another
the breakers mechanically without fail. All position the interlock is released, which is
combinations are available among any models convenient for and easy maintenance and
from AE1000-SW to AE4000-SWA. inspection of the breaker.
Please apply for further details of AE4000-SW zz When to turn OFF one breaker and then
2 to AE6300-SW. turn ON another breakers, please take an
interval 0.5 seconds or more.
Further the interlock is possible among the
different connection types or poles, such as zz MI for 3 breakers can not be installed to
SAE – Accessories
fixed type or drawout type, 3 pole or 4 pole. In combine with Door Interlock (DI).
combination with electric interlock, the higher
safety interlock system can be secured.
ACB 1 u | u ACB 1 u | u u
ACB 2 u u | ACB 2 u u | u
144
ACB 3 u u u |
47 134
Type 1 2 3 4 5 6 7 Type 1 2 3 4 5
ACB 1 u | u u | | u ACB 1 u | u u u
ACB 2 u u | u | u | ACB 2 u u | u u
1000 (Max.)
ACB 3 u u u | u | | ACB 3 u u u | |
[mm]
Specifications MI-203F-W MI-204F-W MI-403F-W MI-404F-W MI-203D-W MI-204D-W MI-403D-W MI-404D-W MI-IW-W
AE1000–1600-SW AE2000–3200-SW AE1000–1600-SW AE2000–3200-SW
Application (breaker) Wire set for all mechanical
AE2000-SWA AE4000-SWA AE2000-SWA AE4000-SWA
interlock devices required for
Breaker type Fixed Drawout combination of 3 ACBs
Number of poles 3 4 3 4 3 4 3 4
Order information Art. no. 168963 168964 168965 168966 168967 168968 168969 168970 168971
16
SAE – Accessories
SAE – Accessories
Dust cover (DUC)
17
SAE – Accessories
These current transformers (CT and sensor coil) Current transformers of type CT-06mmm serve
are suitable for the main conductor and the the reduction of IN max. on an AE1000.
N conductor.
CT-06-W CT-06-W CT-06-W CT-06-W CT-10-W CT-12-W CT-16-W CT-20-W CT-20-W CT-20-W CT-25-W CT-32-W
2 Specifications
Application (breaker) a
025 031 050 063 100 125 160 125
AE1000-SW AE1000-SW AE1000-SW AE1000-SW AE1000-SW AE1250-SW AE1600-SW AE2000-SW AE2000-SW AE2000-SW AE2500-SW AE3200-SW
160 200 250 320
Rated current IN max b (A) 250 315 500 630 1000 1250 1600 1250 1600 2000 2500 3200
SAE – Accessories
Order information Art. no. 193939 193940 193941 193942 193943 193944 193945 193946 193947 193948 193949 193950
a Shipping contents includs CT and sensor coil for 1 pole. Other transformers on request.
b At 40 °C and 50/60 Hz
N2
NCT
NCT
Order information Art. no. 168986 168987 168988 168989 168990 168991 168992 168993
Specifications ZCT-163-W ZCT-323-W ZCT-324-W ZT-15B-W ZT-30B-W ZT-40B-W ZT-60B-W ZT-80B-W ZT-100B-W
Application Load circuits Transformer ground wire
Hole diameter for wire a (mm) 230x60 (oval) 370x108 (oval) 500x108 (oval) Ø 15 Ø 30 Ø 40 Ø 60 Ø 80 Ø 100
Order information Art. no. 168994 168995 168996 168997 168998 168999 169000 169001 169002
a Further details on request.
18
SAE – Accessories
These power supplies are used for supplying the The PW3-W is included as standard power sup-
ETR base unit. They are equipped with 6 outputs ply in the ACB's.
(alarms and errors).
SAE – Accessories
Order information Art. no. 168985 (standard) 168562 168563
The electronic trip relay can be checked by this trip relay without the breaker being connected
field test device when the breaker is at test or to the main supply. The breaker will trip when
disconnect position. So it allows you to test the tested.
HI
Specifications Y-2000
BISTER
88
SI
GN
AL
88
DO
S1
S2
VT T
AR
ST
OP
ST
Y-2000
With the breaker taken out of its cradle, this Specifications Test Jumper
device enables the breaker to be electrically Cable length (m) 3 a
opened and closed, and the operating sequence
to be checked. Order information Art. no. 168977
3 m length of cable is equipped as standard. a Other lengths on request
Other lengths available on request.
Interphase barriers
19
SAE – Electronic Trip Relay
3 Display
Several measuring data (current,
voltage, power etc) and alarms can
SAE – Electronic Trip Relay
20
SAE – Electronic Trip Relay
Standard functions
3
Neutral pole overcurrent protection (NP)
NCT
Neutral CT is required for Ground fault or Neu-
tral pole protection, when 3 pole breaker is used
for 3 phase 4 wires system. (see page 18)
ZCT
ZCT is required for a few amperes earth leakage
protection, and is combining ER plug.
(see page 18)
21
SAE – Electronic Trip Relay
Characteristic table
WS
General use
3 LTD+STD+INST/MCR
SAE – Electronic Trip Relay
WM
Generator protection use
LTD+STD+INST/MCR
Note:
WB type for special use is available on request.
Type G1 E1 AP
TRIP side Selfholding Selfholding —
Non Self- Non Self- Non Self-
ALARM side holding holding holding
Description:
Self-holding type: The output condition is held until it is reset.
Non self-holding type: The output is reset if it is returned to the normal condition.
22
SAE – Electronic Trip Relay
CT rating table
Additional function
23
SAE – Electronic Trip Relay
(MCR: option a)
3 RUN-LED
3 Uninterrupted current Iu
setting dial
SAE – Electronic Trip Relay
ERR.-LED
24
SAE – Electronic Trip Relay
(MCR: option a)
RUN-LED
3 LTD pick-up current IL
setting dial
3
25
SAE – Electronic Trip Relay
3
Setting item Adjustable setting range Accuracy Setting for shipment
SAE – Electronic Trip Relay
Ip
Current
Ip
Current
Lighting
PAL-LED
Blinking
ON OFF
PAL OUT
1/2 TL
(contact output)
26
SAE – Electronic Trip Relay
If MCR switch is built in the breaker and the dial Specifications MCS-W
for INST/MCR on Main setting module is set to Optional setting Module MCR
any MCR position, MCR function is operative.
MCR function: During a closing operation of Order information Art. no. 168570
the breaker, Instantaneous characteristics is
operative. And it becomes inoperative when the
breaker is in the closed position.
27
SAE – Electronic Trip Relay
1 2 3 4 5 6 7 8
ing accuracy
By adopting high-performance ASIC, various
measuring elements (load current, voltage,
energy,harmonics, etc.) and high measuring
accuracy are realized.
3
Setting item Adjustable setting range
SAE – Electronic Trip Relay
This is the module that displays and sets various zz Graphical display
information, for example, measurement, trip By adopting dot matrix type LCD, graphical
MITSUBISHI DP1 and alarm, setting of output contacts and so on. display such as bar graph display of load
zz Multi display of measuring element current, harmonic currents and characteristic
It enables to easily monitor the comparison curve are realized.
of each measuring element by multi display There are 2 types of this module. One is the ETR
(load current 4 phases multi display and volt- attachment type (DP1). Another is the panel
age multi display) on one screen. attachment type (DP2) and is connected to
zz 2-colours back light extension terminals of control circuit by 2 m
cable (5 m cable will be available on request).
If trip or alarm occurred, back light colour
changes from green to red automatically.
The VT-W measurement module enables to It is to be placed separatetly outside the the
measure voltages, powers, energies, harmonic breaker. A connection cable of 2 meters length
currents and etc. by connecting the ETR with is included.
Extension module (EX1).
28
SAE – Electronic Trip Relay
These Interface units can expand the future pos- zz Intelligent control by Multi-data
sibility in various communication and Intelligent c ommunication
control.a It comes into being the Intelligent control
zz Applicable to various open networks. by Multi-data communication through these
These units are applicable to various interface units to PLC/SCADA, which transfer
open network systems such as CC-Link®, the measurement information, setting
Profibus DP and MODBUS® (RS485), which values, error information and trip and alarm
can be built in easily. i nformation.
MELSECNET/10
3
I/O unit
MELSEC PLC
AE-SW
The input & output controlling unit BIF-CON is remotely, like a ON or OFF operations or Spring-
available for the remote controlling and remote charging.Further, by combining the drawout
monitoring of the breaker condition through position switch (BIF-CL), the monitoring of
the various network systems. drawout position become available in case of
With this BIF-CON in addition to the interface the breaker drawout type.
unit, it become possible to control the breaker
Specifications BIF-CON-W
Application I/O unit network module
29
SAE – Electronic Trip Relay
Combination sample Display module + Extension module Display module + Extension module + VT-W unit
Type 1 = EX1 2 = DP1 – 3 = DP2 1
1 = EX1 2 = DP1 – 3 = DP2,VT-W 1
1 Main setting module WS WM WS WM
2 Optional setting module NP AP G1 E1 NP AP G1 E1 NP AP G1 E1 NP AP G1 E1
3 Power supply P3 – P5 P3 – P5
Measurement
Load current (±2.5 %) u u
Leakage current (±15 %) c — — — u — — — u — — — u — — — u
Voltage (±2.5 %) — u
3 Power (active, reactive, apparent) (±2.5 %) — u
Power factor (±5 %) — u
Energy (active, reactive) (±2.5 %) — u
SAE – Electronic Trip Relay
30
SAE – Electronic Trip Relay
31
MCCB Overview
World Super Series WSS – The extensive breaker series from Mitsubishi Electric
The circuits of the Mitsubishi Electric breaker series are amongst the The system is based, among other things, on the well-known and proven
smallest compact circuit breakers in the world with electronic overload microprocessor technology.
indication of this kind.
4 MITSUBISHI OFF
IEC60947-2
JIS C 8201-2
EN60947-2
40°C
Icu/Ics
MITSUBISHI
NO-FUSE BREAKER
MODEL
NF400-SEP
OFF
JIS
Ue
550VAC
460VAC
220VAC
IEC 60947-2
Icn
35kA
50kA
85kA
MITSUBISHI
NO-FUSE BREAKER
IEC60947-2
EN60947-2
Ue
Icu/Ics
25/13kA
NO-FUSE BREAKER Ue
8/8kA EN 60947-2
690VAC
65/33kA
400A
690VAC Icu/Ics 500VAC
MODEL
NF1000-SS 85/43kA
NF250-SEV 30/30kA 10/10kA 440VAC
MODEL 500VAC 30/30kA 85/43kA
36/36kA 400VAC
440VAC 42/42kA 125/63kA
1000A
230VAC
36/36kA 45/45kA
415VAC 3P In Cat. B Icw 20kA 0.1s
400
POLE 85/85kA
36/36kA
250A
40°C
400VAC 690VAC
In Ir 500-1000A
MCCB Overview
36/36kA Ui
380VAC 50 - 60Hz
85/85kA 50kA
230VAC 8kV 500VAC 85kA
Uimp 250VAC
POLE
Ui690V
3P
Uimp 8kV
ON MITSUBISHI ELECTRIC
Cat.A ON
PUSH TO
IIIIIII IIIIIII IIIIIII IIIIIII
TRIP PUSH TO TRIP
MITSUBISHI ELECTRIC
T Ir
TEST Ip 300 4 5 6
8 10 PUSH TO TRIP
Is 250
350 3.5 7 6 12
Ii 220 3
TL 2.5 8 14
Ts 200 400 2 10 4 16
Ii(X400A)
Ii(X100A) Ir(A) IS(xIr)
.2
TEST 60 80 .1 OVER
PAL
T Ir .10 70%
100 .06 .3 .07
Ip 12
Is Ip(xIr)
Ii TL(sec) TS(sec)
TL
Ts
4 5 6 8 10
300 .7 .8 12
250 3 7 6
350 14
T Ir 225 8
16
Ip 1 2 10 4
Is .5
Ii 200 IS (×In, Ir ) II(×400A)
TL Ir(×400A)
Ts In(A) .2 .8 .9
60 100 .1
TEST 150
.3 .7 1.0
12 .06
T S (s) IP (×In, Ir)
T L (s)
10 SEV
7,5 HV
5 SV SV
32
MCCB Overview
Outline
t
en
Mitsubishi Electric MCCBs feature excellent The contacts open and close rapidly,
em
arc-extinguishing performance by virtue regardless of the moving speed of the
ov
of the optimum combination of grid gap, handle, minimizing contact wear and
md
shape, and material. ensuring safety.
pi
Ra
4
MCCB Overview
Magnetic flux
Grid
Moulded case (cover)
Magnetic
force
Arc Handle
zz Trip indication
The automatically tripped condition is indicated
by the handle in the center position between ON
Arc extinction and OFF; the yellow or white line cannot be seen
in this position.
The figure shows the handle in tripped position.
Arc runner zz Resetting
The arc is instantaneously transferred Resetting after tripping is performed by first
to the arc-extinguishing chamber (see MITSUBISHI OFF
IEC60947-2
JIS C 8201-2
EN60947-2
40°C
Icu/Ics
moving the handle OFF position to engage the
NO-FUSE BREAKER
the figure above) by the arc runner, mechanism, then returning the handle to ON to
Ue
8/8kA
690VAC
MODEL
NF250-SEV 500VAC
440VAC
30/30kA
36/36kA
POLE
3P
zz Trip-Free
mance.
Ui690V Uimp 8kV
Cat.A ON
PUSH TO
TRIP
IIIIIII IIIIIII IIIIIII IIIIIII Even if the handle is held at ON, the breaker will
T Ir
trip if an overcurrent flows.
TEST Ip
Is
zz Contact on Mechanism
Ii
TL
Ts
Ii(X100A)
Trip button (push to trip) Even in the worst case in which welding occurs
Enables tripping mechanically from owing to an overcurrent, the breaker will trip and
outside, for confirming the operation the handle will maintain to ON, indicating the
of the accessory switches and the energizing state.
manual resetting function.
33
MCCB Overview
A microcomputer and Mitsubishi Electric’s original IC fulfill a new high level of safety
Safer and more reliable power Alarm function monitors and anticipates interruptions
Electronic device loads, such as inverters, distort Our electronic moulded-case circuit breakers The pre-alarm module (with contact output) is
the current waveform. Mitsubishi Electric’s feature a pre-alarm system as standard. The optional available with electronic molded-case
electronic breakers use a digital detector to pre-alarm outputs an alarm before the circuit and earth-leakage circuit breakers (on request).
measure the current’s effective value and breaker trip is activated. When the load current
minimize overload tripping errors. This enables exceeds the set pre-alarm current, it outputs a
precise protection of the circuit. pre-alarm signal (from a solid-state relay) and
lights the LED.
current IP
the high-voltage fuse, OCR and the low voltage
fuse. Short time-delay tripping current IS
Load
Load current Short time-delay
operating time TS
Instantaneous tripping
current II
Current [A]
NF400-SEW 3P
Long time-delay Short time-delay
operating time TL operating time TSd
34
MCCB Overview
The program calculates the short-circuit levels and currents at all neces-
sary points for all switchgear components, including the power supply
transformer and circuit breakers, the emergency generators, the indi-
vidual motor and capacitor group branch circuits and all the other power
distribution circuits, down to the last circuit breaker. This makes it possible
4
to select the ideal breaker for every task, for optimum performance and
MCCB Overview
cost-efficiency.
The calculated results, the hardware model suggestions and the wiring
diagram with all the relevant values can be processed and used as docu-
mentation for the switchgear installation. Another welcome extra is the
free Internet update service.
35
MCCB Overview
4 6
7
Large terminal covers (TC-L)
see page 67
98
ALc
96
ALb
98
ALa
ALARM SWITCH
5A
3A
0.4A
Connections for Plug-in
0.2A
9 see page 61
125V
250V
125V
250V
AC
AC
DC
95
c
DC
b
96
AX AL
a
98
a
14
ALAX-2GSWLS
14
AXa
MITSUBISHI ELECTRIC
b
12
12
AXb
11
Mechanical interlock (MI)
c
10 see page 68
11
AUXILIARY SWITCH
AXc
5A
3A
0.4A
0.2A
125V
250V
125V
250V
AC
AC
DC
DC
11 OFF Lock with 3 padlocks (HL) see page 64
F
F
O
T
E
S
E
T Ir
R
TEST Ip
PUSH Is
TO Ii
TRIP TL
Ts
Ii(X100A)
14 17
ON
SOURCE
D3 D2
P3 P2
Hi Lo
D1
P1
D
E
P
P
I
R
T
F
F
O
E
R
UVTSA250-2GSWRS
PUS
TO H
TRIP
15 18
OFF
S4
ON
S2
K1 K1
K1 S1
K2
K2
P2 Uc
K3
P1 Supply
SW1 Power
Uc K2
K3 Operating
K3
Circuit
S2 S4
S1
P1 P2
SHT
C1
S1
AC100-240V
50/60Hz
C2
S2
P2 S1 S2 S4
P1
MODEL MSDBA-NF25GSW
MITSUBISHIMODULE A0106
POWER SUPPLY SERIAL:
NO-FUSE BREAKER ON
MODEL NF250-SGW
50/60Hz
Uimp 8kV
Ui 690V
Push to Cat.A
EN60947-2
IEC60947-2
40°C
JIS C 8201-2 (MANU)
ON Ue
Icu/Ics
8/8kA
690VAC Dis-
22/22kA
525VAC charge
30/30kA
500VAC
36/36kA
AUTO 440VAC
36/36kA
380/415VAC Push
Push to 230VAC
85/85kA
36
MCCB Overview
4 5 6 7
2 3
MCCB Overview
1 9 8
EN60947-2
MITSUBISHI
IEC60947-2
40°C
NO-FUSE BREAKER
OFF JIS C 8201-2
Ue
Icu/Ics
8/8kA
690VAC
MODEL
NF250-SEV 500VAC
440VAC
30/30kA
36/36kA
36/36kA
415VAC
36/36kA
In 250A 400VAC
380VAC
36/36kA
9
85/85kA
230VAC
3P
POLE
Ui690V Uimp 8kV
Cat.A ON
PUSH TO
IIIIIII IIIIIII IIIIIII IIIIIII
TRIP
T Ir
TEST Ip
Is
Ii
TL
Ts
Ii(X100A)
2 3
4 5 6 7
37
MCCB Overview
WS-V series
Type/Series
NF32-SV NF63-SV NF125-SGV NF125-SEV NF160-SGV
Rated current In max. [A] 32 63 125* 125* 160*
Rated insulation voltage Ui [V] AC 600 600 690 690 690
Number of poles 3 3/4 3/4 3/4 3/4
Rated 690 V — — 8/8 8/8 8/8
S series
breaking 500 V —
capacity [kA] IEC 947-2 AC a
EN 60 947-2 (50/60 440 V 125/125
VDE 0660 Hz) 400 V 150/150
(Icu/Ics) 230 V 150/150
Dimensions WxHxD [mm] 105x165x68
Type NF125-UV
Rated current In max. [A] 125
Rated insulation voltage Ui [V] AC 690
Number of poles 3/4
Rated 690 V 10/10
U series
38
MCCB Overview
MCCB Overview
50/50
50/50
90/90
105/140x165x68
NF250-HGV NF250-HEV NF400-HEW NF630-HEW NF800-HEW
250* 250* 400* 630* 800*
690 690 690 690 690
3/4 3/4 3/4 3/4 3/4
10/8 10/8 10/10 15/15 15/15
50/50 50/50 50/50 50/50 50/50
65/65 65/65 65/65 65/65 65/65
75/75 75/75 70/70 70/70 70/70
100/100 100/100 100/100 100/100 100/100
105/140x165x68 105/140x165x68 140/185x257x103 140/185x257x103 210/280x275x103
NF250-RGV NF400-REW NF630-REW NF800-REW
250* 400* 630* 800*
690 690 690 690
3 3 3 3
— 15/10 20/15 20/15
— 70/35 70/35 70/35
125/125 125/63 125/63 125/63
150/150 125/63 125/63 125/63
150/150 150/75 150/75 150/75
105x165x68 140x257x103 140x257x103 210x275x103
NF250-UV NF400-UEW NF800-UEW
250 400* 800*
690 690 690
3/4 3/4 3/4
15/15 35/35 35/35
200/200 170/170 170/170
200/200 200/200 200/200
200/200 200/200 200/200
200/200 200/200 200/200
105/140x240x68 140/280x297/322x200 210/280x322x200
DSN250-SGV DSN400-SW DSN630-SW DSN800-SW DSN1000-SW DSN1250-SW DSN1600-SW
250 400 630 800 1000 1250 1600
690 690 690 690 660 660 660
690/300 690/250 690/250 690/250 660/250 660/250 660/250
3/4 3/4 3/4 3/4 3/4 3/4 3/4
2000/1000 3200/1600 5040/2520 6400/3200 8000/14000 10000/5000 12800/6400
105/140x165x68 140/185x257x103 140/185x257x103 210/280x275x103 210/280x406x140 210/280x406x140 210/280x406x140
* adjustable
39
MCCB - Specifications
AC
capacity [kA] (50/60 Hz) 440 V 2.5/2.5 7.5/7.5 10/8 36/36 36/36
IEC/EN 60947-2
400 V 5/5 7.5/7.5 10/8 36/36 36/36
230 V 7.5/7.5 15/15 25/19 85/85 85/85
(Icu/Ics)
DC 250 V 2.5/2.5 7.5/7.5 7.5/7.5d 20/20d —
Utilization category A A A A A
Rated impulse withstand voltage Uimp [kV] 8 8 8 8 8
Pollution degree 3 3 3 3 3
Reverse connection V V V V V
Suitable for isolation V V V V V
5 a
ca
c
a
b
75
130
75/100
130
75/100
130
105/140
165
105/140
165
Dimensions [mm]
b c 68 68 68 68 68
MCCB - Specifications
ca 90 90 90 92 92
Weight [kg] 0.65 0.75/1,0 0.75/1,0 1.6/2.0 1.7/2.2
Alarm switch (AL) V V V V V
Auxiliary switch (AX) V V V V V
Cassette-
type Shunt trip (SHT) V V V V V
accessories Under- Non-synchronous (UVT-N) — — — — —
Mechanical data
voltage closing
trip Synchronous closing (UVT-S) V V V V V
Accessories with terminal block (SLT) V V V V V
connection with internal terminal type V V V V V
Screw terminal (standard) V V V V V
Front Solderless terminal — — — V V
Installation Busbar terminal — — — — —
and Rear (B) V V V V V
connection
Rear (PM) V V V — —
Plug-in Rear front IP 20 (PM-IP) — — — V V
with auto trip
Built-in Pre-alarm-contact output a
(PAL) — — — — —
accessories Overcurrent trip alarm a (OAL) — — — — —
External operating Door mounting (V) V V V V V
handle Mounted on breaker (R) — — — V V
Electrical operation device (MDS) — — — V V
Handle lock for use (HL) V V V V V
Handle lock device with padlock (HL-S)
Externl accessories
V V V V V
Lock cover (LC) V V V V V
Large (TC-L) V V V V V
Terminal Small (TC-S) V V V V V
cover For rear connection (BTC) V V V V V
For plug-in (PTC) V V V V V
Mechanical interlock (MI) V V V V V
Insulating barrier Between phases (Standard) (BA-F) V V V V V
Adapter for IEC 35 mm rail V V V/— — —
CE marking Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration
CCC recognition Recognized Recognized Recognized Recognition in process Recognized
Others
40
MCCB - Specifications
MCCB - Specifications
92 92 92 92 92
1.6/2.0 1.6/2.0 1.7/2.2 1.8 1.5/1.9
V V V V V
V V V V V
V V V V V
V V V V V
— — — — —
V V V V V
V V V V V
V V V V V
V V V V V
— — — — —
V V V V V
— — — — —/V
V V V V V /—
— — V — —
— — — — —
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
— — — — —
Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration
Recognition in process Recognition in process Recognized Recognition in process —
Thermal-magnetic Thermal-magnetic Electronic Thermal-magnetic Thermal-magnetic
Equipped Equipped Equipped Equipped Equipped
Use of 3- and 4-pole
breakers for DC
3-pole 4-pole
xdfgb
N
41
MCCB - Specifications
AC
capacity [kA] (50/60 Hz) 440 V 36/36 50/50 65/65 36/36 36/36
IEC/EN 60947-2
400 V 36/36 50/50 75/75 36/36 36/36
230 V 85/85 90/90 100/100 85/85 85/85
(Icu/Ics)
DC 250 V 20/20d 20/20d 40/40d 20/20d —
Utilization category A A A A A
Rated impulse withstand voltage Uimp [kV] 8 8 8 8 8
Pollution degree 3 3 3 3 3
Reverse connection V V V V V
Suitable for isolation V V V V V
5 a
ca
c
a
b
105/140
165
105/140
165
105/140
165
105/140
165
105/140
165
Dimensions [mm]
b c 68 68 68 68 68
MCCB - Specifications
ca 92 92 92 92 92
Weight [kg] 1.6/2.0 1.6/2.0 1.6/2.0 1.6/2.0 1.7/2.2
Alarm switch (AL) V V V V V
Auxiliary switch (AX) V V V V V
Cassette-
type Shunt trip (SHT) V V V V V
accessories Under- Non-synchronous (UVT-N) — — — — —
Mechanical data
voltage closing
trip Synchronous closing (UVT-S) V V V V V
Accessories with terminal block (SLT) V V V V V
connection with internal terminal type V V V V V
Screw terminal (standard) V V V V V
Front Solderless terminal V V V V V
Installation Busbar terminal — — — — —
and Rear (B) V V V V V
connection
Rear (PM) V V V — —
Plug-in Rear front IP 20 (PM-IP) — — — V V
with auto trip
Built-in Pre-alarm-contact output a
(PAL) — — — — V
accessories Overcurrent trip alarm a (OAL) — — — — V
External operating Door mounting (V) V V V V V
handle Mounted on breaker (R) V V V V V
Electrical operation device (MDS) V V V V V
Handle lock for use (HL) V V V V V
Handle lock device with padlock (HL-S)
Externl accessories
V V V V V
Lock cover (LC) V V V V V
Large (TC-L) V V V V V
Terminal Small (TC-S) V V V V V
cover For rear connection (BTC) V V V V V
For plug-in (PTC) V V V V V
Mechanical interlock (MI) V V V V V
Insulating barrier Between phases (Standard) (BA-F) V V V V V
Adapter for IEC 35 mm rail — — — — —
CE marking Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration
CCC recognition Recognition in process Recognition in process Recognition in process Recognition in process Recognized
Others
a Both PAL and OAL is not available. Only one specified. b Others on request. c On request. d Use of 3- or 4-pole breaker for DC, see wiring diagram on the next page.
Missing specifications accord. to IEC/EN 60947-2 on request.
42
MCCB - Specifications
125–160, 140–200, 175–250 125–160, 140–200, 175–250 80–160, 125–250 125–160, 160–200, 200–250 125, 150, 175, 200, 225, 250
Adjustable Adjustable Adjustable Adjustable Fixed
MCCB - Specifications
92 92 92 92 92
1.6/2.0 1.6/2.0 1.7/2.2 1.8 2.7/3.7
V V V V V
V V V V V
V V V V V
— — — — —
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
— — — — —
V V V V V
— — — — —
V V V V V /—
— — V — —
— — — — —
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
V V V V V
— — — — —
Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration
Recognition in process Recognition in process Recognized Recognition in process —
Thermal-magnetic Thermal-magnetic Electronic Thermal-magnetic Thermal-magnetic
Equipped Equipped Equipped Equipped Equipped
Use of 3- and 4-pole
breakers for DC
3-pole 4-pole
N
43
MCCB - Specifications
(50/60 Hz)
400 V 50/50 (36/36) b 70/70 125/63
(Icu/Ics) 230 V 85/85 (65/65) b 100/100 150/75
Utilization category B B B
Rated short-time withstand current Icw [kA/s] 5/0.25 5/0.25 5/0.25
Rated impulse withstand voltage Uimp [kV] 8 8 8
Pollution degree 3 3 3
Reverse connection V V V
Suitable for isolation V V V
ca a 140/185 140/185 140
5
a c
b 257 257 257
Dimensions [mm]
b c 103 103 103
ca 155 155 155
Weight [kg] 6.0/7.8 6.0/7.8 6.0
MCCB - Specifications
V V
device
Handle lock for use (HL) V V V
Handle lock device with padlock (HL-S) V V V
Terminal Large (TC-L) V V V
cover For rear connection (BTC) V V V
Mechanical interlock (MI) V V V
Insulating barrier Between phases (Standard) (BA-F) V V V
Marine approval d for 3 pole breakers LR, GL, BV, DNV, AB LR, GL, BV, AB LR, GL, BV, AB
Others
44
MCCB - Specifications
MCCB - Specifications
V V V V
V V V V
V V V V
V V V V
V V V V
V V V V
V V V V
V V V V
V V V V
V/— V V V
V V V V
V V V V
— V V V
— V V V
— V V V
V V V V
V V V V
V V V V
V V V V
V V V V
V V V V
LR, GL, BV, AB LR, GL, BV, AB LR, GL, BV, AB LR, GL, BV, AB
Electronic Electronic Electronic Electronic
Equipped Equipped Equipped Equipped
45
MCCB - Specifications
(50/60 Hz)
400 V 50/50 70/70 125/63
(Icu/Ics) 230 V 85/85 100/100 150/75
Utilization category B B B
Rated short-time withstand current Icw [kA/s] 9.6/0.25 9.6/0.25 9.6/0.25
Rated impulse withstand voltage Uimp [kV] 8 8 8
Pollution degree 3 3 3
Reverse connection V V V
Suitable for isolation V V V
ca a 210/280 210/280 210
a c
5 Dimensions [mm]
b
b
c
275
103
275
103
275
103
ca 155 155 155
Weight [kg] 10.9/14.2 10.9/14.2 10.9
MCCB - Specifications
V V
device
Handle lock for use (HL) V V V
Handle lock device with padlock (HL-S) V V V
Terminal Large (TC-L) V V V
cover For rear connection (BTC) V V V
Mechanical interlock (MI) V V V
Insulating barrier Between phases (Standard) (BA-F) V V V
Marine approval d for 3 pole breakers LR, GL, BV, DNV, AB LR, GL, BV, AB LR, GL, BV, AB
Others
46
MCCB - Specifications
MCCB - Specifications
V V V V
V V V V
V V V V
V V V V
V V V V
V V V V
V V V V
V V V V
V — — —
— — — —
V V V V
V V V V
— V V V
— V V V
V V V V
V V V V
V — — —
V V V —
V — — —
V V V V
V V V V
— LR, GL, AB LR, GL, AB —
Electronic Electronic Electronic Electronic
Equipped Equipped Equipped Equipped
47
MCCB - Specifications
V V V V V
Lock cover (LC) V V V V V
Large (TC-L) V V V V V
Terminal Small (TC-S) V V V
cover V/— V/—
For rear connection (BTC) V V V/— V/— V
Mechanical interlock (MI) V V V V V
Insulating barrier Between phases (Standard) (BA-F) V V V V V
Adapter for IEC 35 mm rail V V — — —
Corresponding type of circuit breaker NF32-SV NF63-SV NF125-SGV NF160-SGV NF250-SGV
a This performance is accordance with IEC60947-2 clause 7.2.4.1. b On request. c Standard. d Assembly by factory. e TC-N.
Missing specifications accord. to IEC/EN 60947-2 on request.
48
MCCB - Specifications
MCCB - Specifications
140/185 140/185 210/280 210/280 210/280 210/280
257 275 275 406 406 406
103 103 103 140 140 140
155 155 155 190 190 190
5.7/7.5 6.2/8.0 10.9/14.2 23.0/30.2 23.0/30.2 34.0/40.7
V V V V V V
V V V V V V
V V V V V V
V V V V V V
V V V V V V
V V V V V V
— — — — — —
— — — — — —
Va Va Va Va Va Va
V V V Vd Vd Vd
V V V Vd Vd Vd
— — — — — —
V V V V V V
V V V V V V
V V V V V V
V V V V V V
V V V V V V
— — — — — —
V V V Ve Ve —
— — — — — —
V V V V V V
V V V V V V
V V V V V V
— — — — — —
NF400-SW NF630-SW NF800-SEW NF1000-SEW NF1250-SEW NF1600-SEW
49
MCCB - Specifications
5 6A
10 A
254742
254743
254755
254756
45–63 A
56–80 A
254940
254941
254948
254949
15 A 254744 254757 70–100 A 254942 254950
16 A 254745 254758 90–125 A 255195 254951
MCCB - Specifications
50
MCCB - Specifications
MCCB - Specifications
Order information for moulded-case circuit breakers 400–1600 A
51
MCCB – Accessories
Internal accessories
AC100-240V
98
ALa
T Ir 50/60Hz
ALARM SWITCH
Ip
5A
TEST Is
3A
0.4A
Ii
0.2A
Ii(X100A)
250V
AC
AC
DC
95
c
SHTA240-2GSWRS
DC
b
96
AX AL
a
98
a
14
ALAX-2GSWLS
14
AXa
MITSUBISHI ELECTRIC
b
12
11
c
11
AUXILIARY SWITCH
AXc
5A
3A
0.4A
0.2A
125V
250V
125V
250V
AC
AC
DC
DC
For the breakers of the Super Series, 1000 A up to 1600 A, please contact your Distributor.
52
MCCB – Accessories
AX (Auxiliary switch) The auxiliary switch AX indicates whether the breaker is ON or OFF. Page 54
The shunt trip SHT trips the breaker automatically by remote. A cut-off switch is integrated.
SHT (Shunt trip) Page 56
The allowable tripping voltage is 70 % to 110 % of the rated voltage for both AC and DC.
The undervoltage trip UVT trips the breaker automatically when the voltage drops. The tripping voltage is 35 % to 70 % of the
UVT (Undervoltage trip) Page 58
rated voltage. When the voltage recovers to 85 % of the rated voltage or above, the UVT can be reset and the breaker closed.
For the connection of the control wires zz Lead-wire terminal block (SLT)
Mitsubishi Electric offers you two ways: zz Internal terminal type for direct connection.
MCCB – Accessories
Lead-wire terminal block SLT
with screw terminals
Application
All cassette-type accessories are equipped zz Correspondent terminals are not
98
necessary.
96
ALb
standard.
98
ALa
The terminal cover for the lead-wire termi- is adopted for easier wiring.
125V
250V
125V
250V
AC
95
c
DC
AX AL
a
98
ALAX-2GSWLS
14
AXa
11
c
11
AUXILIARY SWITCH
AXc
Cassette-type accessory
Example:
ALAX, also for SHT, UVT
Application
Optional the cassette-type accessories are zz Quick install and de-install of the
available as internal terminal type without internal accessories is possible without
terminal block. demounting the breaker.
The internal connected control wires can zz Mounting of several breakers side-by-
be lead out of the breaker housing in line-
ALAX-2GSWLS
53
MCCB – Accessories
Application
The alarm switch AL indicates that the breaker
has tripped.
The auxiliary switch AX indicates whether the
breaker is ON or OFF.
The alarm and auxiliary switch ALAX is a
combination of the alarm switch AL and the
auxiliary switch AX in one housing.
b
12
12
AXb
11
c
AXc
5A
3A
0.4A
0.2A
125V
250V
125V
250V
AC
AC
DC
DC
TEST
Contact plans
TEST
98 14
96 12
6 95 11
(1 W) (1 W)
Figure shows Lead-wire terminal block type (SLT). Figure shows Internal terminal type.
MCCB – Accessories
Switching operation
Alarm switch (AL) operation Auxiliary switch (AX) operation
Main MCCB conditions Alarm contacts Main MCCB conditions Alarm contacts
OFF or ON ALa 98 (open) OFF or ON AXa 14 (open)
ALc 95 (DC+) a AXc 11 (DC+) a
ALb 96 (closed) AXb 12 (closed)
Trip ALa 98 (closed) Trip AXa 14 (closed)
ALc 95 (DC+) a AXc 11 (DC+) a
ALb 96 (open) AXb 12 (open)
a When DC use, polarity must be considered.
Type of Micro-switch for Voltage (V AC) Resistive loads (A) Inductive load (A) Voltage (V DC) a Resistive loads (A) Inductive load (A)
460 — — 250 0.2 0.2
AL/AX/ALAX-05–8 250 3 2 125 0.4 0.4
125 5 3 30 4 3
460 5 2 250 0.3 0.3
AL/AX/ALAX-10 250 10 10 125 0.6 0.6
125 10 10 30 10 6
a When DC use, polarity must be considered.
54
MCCB – Accessories
MCCB – Accessories
Auxiliary switch AX for direct connection
NF/DSN32–63
AX-05SV 1W 267236
NF/DSN125–250
Left side
NF/DSN32–63
AX2-05SVLS 2W 267246
NF/DSN125–250
Contacts
Type Breaker type Mounted on Art. no.
AL AX
Alarm switch and Auxiliary switch ALAX with lead-wire terminal block SLT
NF/DSN32–63
ALAX-05SVLS 1W+1W 146381
NF/DSN125–250
NF/DSN400–800
ALAX-4SWLS 1W+1W 205774
NF400-UEW 4P
Left side
NF/DSN400–800
AL2AX2-4SWLS 2W+2W 205775
NF400-UEW 4P
ALAX-10SWL 1W+1W NF/DSN1000–1600 205776
AL1AX2-10SWL 1W+2W NF/DSN1000–1600 205777
55
MCCB – Accessories
Application
The shunt trip device SHT trips the breaker
automatically by remote. A cut-off switch is
integrated.
The allowable tripping voltage range is 70 % to
110 % of the rated voltage for both AC and DC.
The SHT is mounted on the right side of the
breaker and equipped with lead-wire terminal
block SLT as standard.
Please specify, if left-side mounted type or
type with flying leads is needed (optional
available).
SHT
C1
S1
AC100-240V
Please consider, the shunt trip device SHT for
C2
AC100-240V
S2
50/60Hz 50/60Hz
T Ir T Ir
Ip Ip
Is Is
Ii Ii
TL TL
Ts Ts
Contact plans
Ii(X100A) Ii(X100A)
C1
SHT
C2
Figure shows Lead-wire terminal block type (SLT). Figure shows Internal terminal type.
MCCB – Accessories
Coil ratings
56
MCCB – Accessories
MCCB – Accessories
For direct connection, mounted on right-side
For 3-/4-pole breaker
Type Breaker type Rated voltage Art. no.
SHTA048-2GSWRN AC 24–48 V 139529
SHTA240-2GSWRN AC 100–240 V 139530
SHTA550-2GSWRN AC 380–550 V 139531
SHTD012-2GSWRN NF/DSN32–63 DC 12 V 139532
SHTD036-2GSWRN NF/DSN125–250 DC 24–36 V 139533
SHTD048-2GSWRN DC 36–48 V 139534
SHTD125-2GSWRN DC 100–125 V 139535
SHTD250-2GSWRN DC 220–250 V 139536
57
MCCB – Accessories
Application
The undervoltage tripping device UVT trips
the breaker automatically when the voltage
drops. The tripping voltage is 35 % to 70 % of
the rated voltage. When the voltage recovers
to 85 % of the rated voltage or above, the UVT
can be reset and the breaker closed.
The UVT is mounted on the right side of the
breaker and equipped with lead-wire terminal
block SLT as standard.
SOURCE
Hi Lo
D1
P1
T Ir T Ir
Ip Ip
Is Is
Ii Ii
TL TL
Ts Ts
Ii(X100A) Ii(X100A)
6
Figure shows Lead-wire terminal block type (SLT). Figure shows Internal terminal type.
MCCB – Accessories
Contact plans
J2 J2
MITSUBISHI
J1 J1
OFF
Breaker
Coil ratings
For synchro- Voltage (V) b Operating time c Making/breaking data
Breaker type a Input (VA)
nous closing Standard (msec) Breaker OFF Breaker ON
NF32-SV
NF63-SV AC 100–120
NF125-SGV/REV AC 200–240
NF125-HGV/HEV AC 220–240
NF125-RGV/UV AC 380–450
U 5 ≤30
NF160-SGV/REV AC 400–440
NF160-HGV/HEV (50/60 Hz)
NF250-SGV/REV
NF250-HGV/REV DC 24, DC 110
NF250-RGV/UV 35–70 % UN min. 85 % UN
AC 100–110/120–130
AC 200–220/230–250
NF400-SEW/HEW/REW/UEW AC 380–415/440–480 5–30
NF630-SEW/HEW/REW U 5
(50/60 Hz) (Instantaneous type)
NF800-CEW/SEW/HEW/REW/UEW
DC100/110
NF1000-SEW AC 100–120/200–240/380–450 5–35
NF1250-SEW Ud AC 200–250/380–450/460–550 5 (Time delay type with
NF1600-SEW (50/60 Hz) 3 voltage inputs)
58
MCCB – Accessories
Types of UVTs
MCCB – Accessories
No. Rated voltages
Breaker type of
Poles AC 24/48 V AC 120/240/450 V AC 250/450/550 V AC 450/550/690 V DC 24/48 V DC 100 –110 V
Long-time delay type, with lead-wire terminal block SLT, long-time delay adjustable in steps 0.5–1.0–3.0 sec
NF/DSN32–63 3 UVTSA048-05SVRSU30 UVTSA450-05SVRSU30 UVTSA550-05SVRSU30 UVTSA690-05SVRSU30 UVTSD048-05SVRSU30 UVTSD110-05SVRSU30
NF/DSN125–250 4 UVTSA048-05SVRFSU30 UVTSA450-05SVRFSU30 UVTSA550-05SVRFSU30 UVTSA690-05SVRFSU30 UVTSD048-05SVRFSU30 UVTSD110-05SVRFSU30
59
MCCB – Accessories
Undervoltage tripping device UVT, instantaneous trip type, synchronous and non-synchronous closing, mounted on right-side
with lead-wire terminal block SLT, for 3-pole breakers with lead-wire terminal block SLT, for 4-pole breakers
Type Breaker type Rated voltage Art. no. Type Breaker type Rated voltage Art. no.
AC 24 V AC 24 V
UVTSAD024-05SVRS NF/DSN32–250 267615 UVTSAD024-05SVRFS NF/DSN63–250 267616
DC 24 V DC 24 V
AC 48 V AC 48 V
UVTSAD048-05SVRS NF/DSN32–250 267620 UVTSAD048-05SVRFS NF/DSN63–250 267621
DC 48 V DC 48 V
AC 100–130 V AC 100–130 V
UVTSAD130-05SVRS NF/DSN32–250 267625 UVTSAD130-05SVRFS NF/DSN63–250 267626
DC 100–130 V DC 100–130 V
AC 200–220 V/ AC 200–220 V/
UVTSA250-05SVRS NF/DSN32–250 267600 UVTSA250-05SVRFS NF/DSN63–250 267601
AC 230–250 V AC 230–250 V
AC 380–415 V/ AC 380–415 V/
UVTSA480-05SVRS NF/DSN32–250 267605 UVTSA480-05SVRFS NF/DSN63–250 267606
AC 440–480 V AC 440–480 V
AC 500–550 V/ AC 500–550 V/
UVTSA600-05SVRS NF/DSN32–250 267610 UVTSA600-05SVRFS NF/DSN63–250 267611
AC 600 V AC 600 V
Undervoltage tripping device UVT, short-time delay type, non-synchronous closing, mounted on right-side
with lead-wire terminal block SLT, for 3-pole breakers with lead-wire terminal block SLT, for 4-pole breakers
Type Breaker type Rated voltage Art. no. Type Breaker type Rated voltage Art. no.
UVTSA048-05SVRSU05 NF/DSN32–250 AC 24/48 V 267690 UVTSA048-05SVRFSU05 NF/DSN63–250 AC 24/48 V 267691
UVTSA450-05SVRSU05 NF/DSN32–250 AC 120/240/450 V 267695 UVTSA450-05SVRFSU05 NF/DSN63–250 AC 120/240/450 V 267696
UVTSA550-05SVRSU05 NF/DSN32–250 AC 250/450/550 V 267700 UVTSA550-05SVRFSU05 NF/DSN63–250 AC 250/450/550 V 267701
UVTSA690-05SVRSU05 NF/DSN32–250 AC 450/550/690 V 267705 UVTSA690-05SVRFSU05 NF/DSN63–250 AC 450/550/690 V 267706
UVTSD048-05SVRSU05 NF/DSN32–250 DC 24/48 V 267710 UVTSD048-05SVRFSU05 NF/DSN63–250 DC 24/48 V 267711
UVTSD110-05SVRSU05 NF/DSN32–250 DC 100–110 V 267715 UVTSD110-05SVRFSU05 NF/DSN63–250 DC 100–110 V 267716
Undervoltage tripping device UVT, long-time delay type, non-synchronous closing, mounted on right-side
with lead-wire terminal block SLT, for 3-pole breakers with lead-wire terminal block SLT, for 4-pole breakers
Type Breaker type Rated voltage Art. no. Type Breaker type Rated voltage Art. no.
UVTSA048-05SVRSU30 NF/DSN32–250 AC 24/48 V 267720 UVTSA048-05SVRFSU30 NF/DSN63–250 AC 24/48 V 267721
UVTSA450-05SVRSU30 NF/DSN32–250 AC 120/240/450 V 267725 UVTSA450-05SVRFSU30 NF/DSN63–250 AC 120/240/450 V 267726
UVTSA550-05SVRSU30 NF/DSN32–250 AC 250/450/550 V 267730 UVTSA550-05SVRFSU30 NF/DSN63–250 AC 250/450/550 V 267731
UVTSA690-05SVRSU30 NF/DSN32–250 AC 450/550/690 V 267735 UVTSA690-05SVRFSU30 NF/DSN63–250 AC 450/550/690 V 267736
UVTSD048-05SVRSU30 NF/DSN32–250 DC 24/48 V 267740 UVTSD048-05SVRFSU30 NF/DSN63–250 DC 24/48 V 267741
UVTSD110-05SVRSU30 NF/DSN32–250 DC 100–110 V 267745 UVTSD110-05SVRFSU30 NF/DSN63–250 DC 100–110 V 267746
60
MCCB – Accessories
If no connection method is specified with the The front-connection model can be modified More details on request.
order, we deliver the standard fixed-installation to other types (excluding plug-in) with special
type with front connection. purchase options.
Connection Types
Installation Fixed Plug-in
Connection Front (F) Rear (B) Rear (PM)
IEC60947-2 EN60947-2
Appearance
8/8kA
690VAC
MODEL 22/22kA
525VAC
30/30kA
500VAC
36/36kA
440VAC
36/36kA
In 100A 380/415VAC
IEC60947-2 EN60947-2
MITSUBISHI
85/85kA
230VAC
OFF
40°C
300VAC
20/20kA JIS C 8201-2
Icu/Ics
Ir 63-100A
3P NO-FUSE BREAKER Ue
690VAC
8/8kA
POLE 22/22kA
Uimp 8kV MODEL 525VAC
Ui690V 30/30kA
Cat.A ON 500VAC
440VAC
36/36kA
36/36kA EN60947-2
100A
IEC60947-2
MITSUBISHI
380/415VAC
MITSUBISHI ELECTRIC
In OFF
40°C
PUSH TO TRIP 85/85kA JIS C 8201-2
230VAC Icu/Ics
300VAC
20/20kA NO-FUSE BREAKER Ue
8/8kA
Ir 63-100A MODEL
690VAC
525VAC
22/22kA
3P 500VAC
30/30kA
POLE 36/36kA
440VAC
Uimp 8kV 36/36kA
100A
T Ir
Ui690V 380/415VAC
TEST Ip
TL
Is
Ii Cat.A ON In
Ir 63-100A
230VAC
300VAC
85/85kA
20/20kA
Ts
3P
Ii(X100A)
PUSH TO TRIP
MITSUBISHI ELECTRIC POLE
Ui690V Uimp 8kV
Cat.A ON
PUSH TO TRIP
MITSUBISHI ELECTRIC
T Ir
TEST Ip
Is
Ii
TL
Ts T Ir
TEST Ip
Ii(X100A) Is
Ii
TL
Ts
Ii(X100A)
MCCB – Accessories
a Only for frame sizes 125/160/250 A b On request, modified at factory.
Connection accessories
61
MCCB – Accessories
Application
The V-type operating handle is used to operate the breaker which is
installed in a cabinet. With the installed V-type operating handle the
breaker can be locked (with up to 3 padlocks, Ø 8 mm max., padlocks are
not included) in OFF position only.
MITSUBISHI
NO-FUSE BREAKER
OFF
IEC60947-2
JIS C 8201-2
Ue
EN60947-2
40°C
Icu/Ics
The door is locked when the breaker is ON and can only be opened when
the breaker is in OFF position.
8/8kA
690VAC
22/22kA
MODEL
NF125-SGW 525VAC
30/30kA
500VAC
36/36kA
440VAC
36/36kA
In 100A 380/415VAC
230VAC
85/85kA
20/20kA
300VAC
Ir 63-100A
Cat.A ON
PUSH TO TRIP
MITSUBISHI ELECTRIC
MODEL
RE100 In 100A
50/60Hz
T
Ip
TL
Ir
Ts
Is
Ii
70% PAL OVER
tions:
Ip(xIr)
IS(xIr) TS(S) Ii(X100A)
Handle and front in black/black and handle and front in red/yellow, or red/
Ir(A) TL(S) 8 10
4 5 6 .1 .2 6 12
80 3.5
60 80 7
3
8 .10
2.5 .3 4 14 .07
100 2 10 .06
63 100 12
F
F
O
T
E
S
E
R
Example:
PUSH
TO
TRIP
cabinet door
6 Specifications
V-type operating handle
V-05SV V-05SVE V-2SV V-2SVE V-2UV V-2UVE V-4S V-4SE V-8S V-8SE
Breaker type NF/DSN32-63 NF/DSN125-250 NF/DSN125-250-UV NF/DSN400-630 NF/DSN800
MCCB – Accessories
Colour: handle/front black red/yellow black red/yellow black red/yellow black red/yellow black red/yellow
Order information Art. no. 267747 267749 267755 267756 267757 267758 225420 225421 225424 225425
Adjustment unit
Spcifications
V-AD3S V-AD3L V-AD5S V-AD5L
Breaker type NF/DSN32-250 NF/DSN400-800
Length (mm) 318 518 300 539
62
MCCB – Accessories
Application
The F-type operating handles are to be mounted directly on the breaker.
With the installed operating handle the breaker can be locked (with up to
3 padlocks, Ø 8 mm max., padlocks are not included) in OFF position only.
The operating handle is available in the following colour combinations:
Handle and front in black/black and handle and front in red/yellow, or red/
ON
black, see also the following table.
EN60947-2
MITSUBISHI
IEC60947-2
40°C
NO-FUSE BREAKER
OFF JIS C 8201-2
Ue
Icu/Ics
8/8kA
690VAC
22/22kA
MODEL
NF125-SGW 525VAC
30/30kA
D
500VAC
36/36kA
E 100A
440VAC
36/36kA
380/415VAC
In 85/85kA
P
230VAC
20/20kA
300VAC
P
Ir 63-100A
I
3P
POLE
R
Cat.A ON
F
MITSUBISHI ELECTRIC
F
PUSH TO TRIP
O
T
E
S
E T Ir
MODEL Ip
In 100A 70% PAL OVER
R Is
RE100 50/60Hz TL
Ii
Ts
PU Ip(xIr)
IS(xIr) TS(S)
SH Ii(X100A)
Ir(A) TL(S) TO 8 10
80
4 5 6 TRIP .2
.1 6 12
60 80 3.5 7
3
8 .10
2.5 .3 4 14 .07
100 2 10 .06
63 100 12
MCCB – Accessories
F-05SV LF DF Z Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is right NF/DSN32-63 267265
F-05SV LF DR Operating handle Type F. OFF position lock, RESET position open, ON side of breaker is upper 3P / 4P 267266
F-05SV LF DR Y Operating handle Type F. OFF position lock, RESET position open, ON side of breaker is left 267267
F-05SV LF DR Z Operating handle Type F. OFF position lock, RESET position open, ON side of breaker is right 267268
F-05SVE LF DF Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is upper 267287
F-05SVE LF DF Y Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is left 267288
F-05SVE LF DF Z Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is right NF/DSN32-63 267289
F-05SVE LF DR Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is upper 3P / 4P 267290
F-05SVE LF DR Y Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is left 267291
F-05SVE LF DR Z Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is right 267292
F-2SV LF DF Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is upper 267359
F-2SV LF DF Y Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is left 267360
F-2SV LF DF Z Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is right NF/DSN125-250 267361
F-2SV LF DR Operating handle Type F. OFF position lock, RESET position open, ON side of breaker is upper 3P / 4P 267362
F-2SV LF DR Y Operating handle Type F. OFF position lock, RESET position open, ON side of breaker is left 267363
F-2SV LF DR Z Operating handle Type F. OFF position lock, RESET position open, ON side of breaker is right 267364
F-2SVE LF DF Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is upper 267371
F-2SVE LF DF Y Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is left 267372
F-2SVE LF DF Z Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is right NF/DSN125-250 267373
F-2SVE LF DR Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is upper 3P / 4P 267374
F-2SVE LF DR Y Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is left 267375
F-2SVE LF DR Z Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is right 267376
F-4S LF DF Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is upper NF/DSN400-630 225402
F-4SE LF DF Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is upper 3P / 4P 225403
F-8S LF DF Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is upper NF/DSN800 225404
F-8SE LF DF Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is upper 3P / 4P 225405
F-RCS Release protection for operating handle Type F All F-types handles 267385
63
MCCB – Accessories
Application
The handle lock device HL is used to lock the handle of the breaker against
switching by not-allowed persons. The function of protection is given
every time.
Different types are available.
zz All handle lock devices can be mounted regardless of the number of
poles.
LC-05SV zz Padlocks are not included.
zz More details on request.
HLF-05SV
zz The handle lock can be used without padlock as a lock cover.
6 Handle lock device HL type
zz The handle lock HL type can be used for 3- and 4-pole breaker types.
MCCB – Accessories
HLS-05SW
HL-4SW
64
MCCB – Accessories
EN60947-2
MITSUBISHI
IEC60947-2
OFF
40°C
JIS C 8201-2
Icu/Ics
NO-FUSE BREAKER Ue
690VAC
8/8kA
MODEL 22/22kA
525VAC
30/30kA
500VAC
MITSUBISHI
JIS
36/36kA Icn
440VAC Ue
OFF
36/36kA 35kA
Ui690V 10/10kA
ON
ON
S2
K1 K1 S1
30/30kA
K1
K2
K2
P2 Uc
42/42kA
K3 Supply
Cat.A
P1 Power
Uc SW1
K2
45/45kA
K3 Operating
K3
3P
Circuit
S4
400
S1 S2
POLE 85/85kA
MITSUBISHI ELECTRIC 40°C
P2
PUSH TO TRIP 690VAC
P1
Ui
50 - 60Hz
50kA
8kV 500VAC 85kA
Uimp 250VAC
TEST
T
Ip
Ir
Is Control circuit
ON
Ii voltage should be
supplied to P1
TL
Ts
Ii(X100A)
and P2 terminals.
PUSH TO TRIP
MITSUBISHI ELECTRIC
P2 S1 S2 S4
P1 300 4 5 6
8 10
250
350 3.5 7 6 12
220 3 14
2.5 8
10 4 16
200 400 2
Ii(X400A)
Ir(A) IS(xIr)
TEST .1 .2
60 80
T Ir .10
100 .06 .3 .07
Ip 12
Is Ip(xIr)
Ii TL(sec) TS(sec)
TL
Ts
MODEL MSDBA-NF25GSW
MITSUBISHIMODULE A0106
POWER SUPPLY SERIAL:
NO-FUSE BREAKER ON
MODEL NF250-SGW
50/60Hz
Uimp 8kV
Ui 690V
Push to Cat.A
EN60947-2
IEC60947-2
40°C
JIS C 8201-2 (MANU)
ON Ue
Icu/Ics
8/8kA
690VAC Dis-
22/22kA
525VAC charge
30/30kA
500VAC
36/36kA
AUTO 440VAC
36/36kA
380/415VAC Push
Push to 230VAC
85/85kA
OFF
MCCB – Accessories
Specifications MDSD.../MDSA... MDS-4.../8... MDS-16...
NF400-SEW/HEW/REW NF1000-SEW
NF125-SGV/LGV/HGV
NF-S/H series NF630-SEW/HEW/REW NF1250-SEW
NF125-SEV/LEV/HEV
Breaker type a NF800-SEW/HEW/REW NF1600-SEW
NF125-RGV/REV/UV
NF-R/U series NF400-UEW, NF800-UEW —
NF250-RGV/REV/UV
DC 24 V
Rated operating voltage (V) Compatible with 100–240 V AC/ AC 100/110 V, 200/220 V (AC 240 V) AC 100/110 V, 200/220 V (AC 240 V)
(allowable voltage range 85–110 %) b 100–250 V DC DC 100/110 V (DC 125 V) DC 100/110 V (DC125 V)
DC 100/110 V OFF: 1.0 (3.0) ON: 8.0 OFF: 1.0 (3.0) ON: 9.0
Operating current
(A, eff.) c 100/110 V OFF: 1.0 (3.0) ON: 10.0 OFF: 1.0 (3.0) ON: 10.0
AC
200/200 V OFF: 0.5 (1.5) ON: 8.0 OFF: 0.5 (1.5) ON: 8.0
ON operating 0.05–0.1 (self holding) 0.05 0.07
Operating time (sec.) OFF operating 0.6 and less (self holding) 3 and less (self holding) 3 and less (self holding)
Spring charging 1.2 and less — —
Transformer capacity required (VA) 150 700 700
Endurance voltage (V) 1500 1500
65
MCCB – Accessories
OFF
S4
ON
S2
K1 K1
K1 S1
K2
K2
P2 Uc
K3
P1 Supply
SW1 Power
Uc K2
K3 Operating
K3
Circuit
S2 S4
S1
P1 P2
Control circuit be
voltage should
supplied to P1
and P2 terminals.
MITSUBISHI
IEC60947-2
40°C
NO-FUSE BREAKER
OFF JIS C 8201-2
Ue
Icu/Ics MITSUBISHI
JIS
Ue
Icn
OFF
35kA
8/8kA 550VAC
690VAC NO-FUSE BREAKER 460VAC
50kA
22/22kA 85kA
NF125-SGW
MODEL 220VAC
525VAC GSW
MODEL MSDBA-NF25 NF400-SEP
MITSUBISHIMODULE 30/30kA MODEL
OFF
500VAC IEC 60947-2
POWER SUPPLY SERIAL: A0106
36/36kA EN 60947-2
440VAC
400A
Icu/Ics
MDSPSA240-SW
36/36kA
100A Pull 10/10kA
380/415VAC
In MODEL 30/30kA
85/85kA 42/42kA
VOLTAGE 230VAC
CONTROLL CIRCUIT 20/20kA 3P
45/45kA
300VAC
400
85/85kA
Ir 63-100A 50V POLE
AC100-240V/DC100-2
40°C
Ui 690VAC
3P 50 - 60Hz
50kA
POLE 8kV 500VAC
ON
Ui690V Uimp 8kV
T Ir 690VAC Dis-
22/22kA
MODEL charge 8 10
Is 525VAC
Ip 300 4 5 6
RE100 In 100A Ii
70% PAL OVER
30/30kA 250
350 3.5 7 6 12
50/60Hz TL 500VAC 220 3
8 14
Ts 36/36kA 2.5
16
AUTO 440VAC Ip(xIr) 200 400 2 10 4
36/36kA
IS(xIr) TS(S) Ii(X100A)
380/415VAC Push Ii(X400A)
OFF
IS(xIr)
Push to
TL(S) Ir(A)
Ir(A) 8 10 85/85kA TEST 60 80 .1 .2
80
4 5 6 .1 .2 6 230VAC
12
3.5
OPEN
60 80 7
MITSUBISHI ELECTRIC
T Ir .10
3 100 .06 .3 .07
8 .10 Ip 12
2.5 .3 4 14 .07 Is Ip(xIr)
100 12 100 2 10 .06 (TRIP) TL
Ii TL(sec) TS(sec)
63 RATED CURRENT Ts
MANU
250 A
6 P2
(DC-)
P1 S1 S4
Alarm switch
P2
(DC-)
P1 S1 S4
Alarm switch
AL (AL-a contact) AL (AL-a contact)
for automatic reset for automatic reset
MCCB – Accessories
ON OFF ON OFF
Reset Reset
Automatic reset type requires the Automatic reset type requires the
Control power supply additional wiring shown by the Control power supply additional wiring shown by the
dotted lines. dotted lines.
Spring-charged type
Electrical operation OFF operation (RESET operation) Since it takes 3 sec to switch off a breaker pro-
When the ON switch is closed, the coil is releas- The circuit breaker can be set to OFF (RESET) by vided with this device, if the breaker needs to be
ing the latch mechanism, and the breaker is pressing the leaf spring, pulling out the manual opened urgently by remote control, a breaker
turned to ON. handle and moving it back and forth more than fitted with an SHT or UVT should be used.
When the OFF switch is closed. a relay operates ten times. This charges the spring at the same The breaker is equipped with a relay for the
to start a motor which turns the breaker OFF time. prevention of pumping.
(RESET) and charges the spring at the same Cautions during electrical operation Control circuit
time. When an electrical-operation device is mounted For breakers with automatic resetting capability,
Manual operation in a breaker or removed from an breaker, this add the connection indicated by the dotted line
When the ON button (on the front of the spring- device must be returned to the discharged state in the diagrams.
charged type) is pressed, the latch mechanism is after tripping of the breaker.
cancelled and the circuit breaker set momentar- A MCCB with an electrical-operation device will zz More details on request.
ily to ON by the force of spring. not trip in the OFF state “PUSH TO TRIP” is used.
This does not indicate that the breaker is faulty. zz Control power supply modules on request.
66
MCCB – Accessories
Terminal covers
Application
The terminal covers are used to avoid exposure of charged parts.
TCS type terminal covers
Different types are available:
zz for front connection as small terminal covers TCS or large terminal cov-
ers TCL, TTC (see figures below)
zz for rear connection as closed type BTC
zz for plug-in as PTC
zz One set includes two pieces of terminal covers.
zz Colour: black, white or transparent
MITSUBISHI OFF
IEC60947-2
JIS C 8201-2
EN60947-2
40°C
Icu/Ics
zz More types/details on request.
NO-FUSE BREAKER Ue
690VAC
8/8kA
MODEL 22/22kA
525VAC
30/30kA
500VAC
36/36kA
440VAC
36/36kA
100A 380/415VAC
Circuit breaker
In 230VAC
85/85kA
20/20kA
300VAC
Ir 63-100A
3P
POLE
NF250-SGW
Ui690V Uimp 8kV
Cat.A ON
PUSH TO TRIP
MITSUBISHI ELECTRIC
T Ir
TEST Ip
Is
Ii
TL
Ts
Ii(X100A)
MCCB – Accessories
Small terminal covers TCS Large terminal covers TTC
(1 set = 2 pieces) (1 set = 2 pieces)
No. of Protection No. of Protection
Type Breaker type Colour Art. no. Type Breaker type Colour Art. no.
poles degree poles degree
TCS-05SV3 3 267552 TTC-05SV3 3 267560
NF/DSN32–250 W75 NF/DSN32–250 W75
TCS-05SV4 4 267553 TTC-05SV4 4 267561
TCS-1SV3 3 267555 TTC-1SV3 3 267563
NF/DSN32–250 W90 NF/DSN32–250 W90 transparent
TCS-1SV4 4 267556 TTC-1SV4 4 267564
TCS-2SV3 3 267557 TTC-2SV3 3 267565
NF/DSN32–250 W105 NF/DSN32–250 W105
TCS-2SV4 4 267558 TTC-2SV4 4 267566
Large terminal covers TCL Terminal covers rear for connection studs BTC
(1 set = 2 pieces) (1 set = 2 pieces)
No. of Protection No. of Protection
Type Breaker type Colour Art. no. Type Breaker type Colour Art. no.
poles degree poles degree
TCL-05SV3 3 NF/DSN32–250 W75 267543 BTC-05SV3 3 NF/DSN32/63 3P W75 267254
TCL-05SV4 4 NF/DSN32–250 W75 267544 BTC-05SV4 4 NF/DSN32/63 4P W75 267255
TCL-1SV3 3 NF/DSN32–250 W90 267546 BTC-1SV3 3 NF/DSN125 3P W90 267257
TCL-1SV4 4 NF/DSN32–250 W90 267547 BTC-1SV4 4 NF/DSN125 4P W90 267258
NF/DSN32–250 W105 3-pole up to NF/DSN125/160/250
TCL-2SV3 3 267548 BTC-2SV3 3 267259
200A max 100 mm² 2,3P W105
NF/DSN32–250 W105 3-pole up to NF/DSN125/160/250
TCL-2SV3L 3 267549 BTC-2SV4 4 267260
250A max 150 mm² 4P W105
TCL-2SV4 4 NF/DSN32–250 W105 267550 BTC-4SW3 3 205985
NF/DSN400–630 transparent IP20
TCL-4SW3 3 black 205977 BTC-4SW4 4 205986
NF/DSN400–630 IP20
TCL-4SW4 4 transparent 205978 BTC-8SW3 3 205987
NF/DSN800 transparent IP20
TCL-8SW3 3 205979 BTC-8SW4 4 205988
NF/DSN800 transparent IP20
TCL-8SW4 4 205980
TCL-8UW3 3 205981
Terminal covers for plug-in type PTC
TCL-8UW4 4
NF/DSN800 transparent IP20
205982
(1 set = 2 pieces)
TCL-10SW3 3 NF/DSN1000–1250 205983 No. of Protection
transparent IP20 Type Breaker type Colour Art. no.
(fixed with screws) poles degree
TCL-10SW4 4 205984
PTC-O5SV3 3 NF/DSN32–250 W75 267469
PTC-O5SV4 4 NF/DSN32–250 W75 267470
PTC-1SV3 3 NF/DSN32–250 W90 267472
PTC-1SV4 4 NF/DSN32–250 W90 267473
W75 = Breaker width 75 mm
W90 = Breaker width 90 mm PTC-2SV3 3 NF/DSN32–250 W105 267474
W105 = Breaker width 105 mm PTC-2SV4 4 NF/DSN32–250 W105 267475
67
MCCB – Accessories
Mechanical interlock MI
(Front side installation)
Application
With two breakers, use a panel-mounted A breaker-mounting mechanical to mount on
mechanical interlock for one-way only input. the breaker main unit can be made to order.
It is usable for front, rear, and plug-in types. zz More details on request.
100A 100A
In In
MI-05SV3 3 For W75, W90 und W105; 3 poles. Panel mounting. 267418
440VAC 36/36kA 440VAC 36/36kA
380/415VAC 36/36kA 380/415VAC 36/36kA
230VAC 85/85kA
Ir 63-100A 230VAC 85/85kA Ir 63-100A 300VAC 20/20kA
300VAC 20/20kA
POLE 3P POLE 3P
Ui690V
Cat.A
Uimp 8kV Ui690V
Cat.A
Uimp 8kV
Application
The isolation barriers are used to avoid short- Every breaker is equipped with isolation barriers
circuits between the terminals of the breaker as standard.
due to dust or leakage current.
MITSUBISHI
IEC60947-2 EN60947-2
OFF
40°C
JIS C 8201-2
Icu/Ics
NO-FUSE BREAKER Ue
690VAC
8/8kA
MODEL 22/22kA
525VAC
30/30kA
500VAC
36/36kA
440VAC
36/36kA
In 100A 380/415VAC
230VAC
85/85kA
20/20kA
300VAC
Ir 63-100A
3P
POLE
Cat.A ON
PUSH TO TRIP
MITSUBISHI ELECTRIC
Application
The IEC 35 mm rail mounting adapter is used to It is available for 3-pole breakers NF/DSN32–63.
mount the breaker on a IEC 35 mm mounting rail.
Specifications DIN-05SW
For 3-pole breakers NF/DSN32–63
68
MCCB – Accessories
Application
The portable tester unit can be used to check the tripping characteristics
of the electronic breakers from 125 A up to 1600 A.
zz More details on request.
MITSUBISHI
IEC60947-2 EN60947-2 Specifications Y-250 Y-350
OFF
40°C
JIS C 8201-2
Icu/Ics
NO-FUSE BREAKER Ue
Cat.A ON
PUSH TO TRIP
MITSUBISHI ELECTRIC
T Ir
Ip
T
TEST Is
Ii
TL
Ts
Ii(X100A)
000
L 30
POWER
ON
MCCB – Accessories
69
MCCB – Characteristics & Dimensions
Operating characteristics
4h 4h 4h
Operating characteristics
2h NF32-SV 3–6 A 2h Operating characteristics 2h Operating characteristics
1h NF63-CV 3–6 A 1h NF32-SV 10–32 A 1h NF63-CV 40–63 A
NF63-SV 3–6 A NF63-CV 10–30 A NF63-SV 40–63 A
30min 30min NF63-SV 10–32 A 30min NF63-HV 40–63 A
20min 20min NF63-HV 10–30 A 20min
14min 14min 14min
10min 10min 10min
6min 6min 6min
4min 4min 4min
7
Max. (60–63 A)
2min 2min Instantaneous trip current is 2min
Max. (3–5 A) fixed to AC 600 A ±120A Max. (40–50 A)
1min 1min and DC 850 A ±170A. 1min
Max. (7.1–8 A) Max.
Operating time
Operating time
30s
Operating time
30s 30s
20s 20s 20s
10s 10s 10s
MCCB – Characteristics & Dimensions
5s 5s 5s
Min.
Min. Min.
2s 2s 2s
1s 1s 1s
0.5s 0.5s 0.5s
AC
AC
0.2s 0.2s DC Max. total 0.2s
AC Max. total breaking DC Max. total
0.1s breaking 0.1s time 0.1s breaking
DC time time
0.05s 0.05s 0.05s
120
Current rating (%)
2-pole 110
100
3, 4-pole 90
(Rated ambient 80
–10 0 10 20 30 40 50 60
temperature 40 °C)
External accessories
Accessories Type name Reference page Accessories Type name Reference page
Operating handle F 3, 4P F-1SV 63 3P MI-05SV3
Mechanical interlock MI 68
V 3, 4P V-1SV 62 4P MI-05SV4
LC LC-05SV Small TC-S 3P TCS-1SV3
HLF-05SV 3P TCL-1SV3
Handle lock device HL (*1) 64 Large TC-L
HLN-05SV Terminal 4P TCL-1SV4
62
HL-S HLS-1SV cover Skeleton TTC 3P TTC-1SV3
Notes * 1 HLF types are used for OFF-lock and HLN types for ON-lock. Rear BTC 3P BTC-1SV3
*2 Specify the working voltage. Refer to the reference page for type name. Plug-in PTC 3P PTC-1SV3
Electrical operation device MDS (2*) 66
70
MCCB – Characteristics & Dimensions
Front connection
Insulation barrier
Mounting hole (removable) Solderless terminal
M8 screw for wire size
24 Breaker
14~2/0AWG CU/AL
50
Wire connection
111
112
130
84
50
ø4.5
ø8.5
Trip
8
button 30 30
ø8.5
30 22 30 45
61 M4×0.7 taps
60 60 90
Neutral pole 68 or ø5
19 max.
90 120 4 72 Comb conductor 2-pole 3-pole 4-pole
16.5 max.
90
(Conductor thickness t
2-pole 3-pole 4-pole = 5 max.)
Rear connection
4-pole 4-pole
R1
R1
111
112
52
8
15 connection
allowance
16
30 28
30 30 ø18 30 57 86
8.5
5 60 90
2.5 M8 bolt M4×0.7 breaker
mounting screw
60 M4×0.7 taps 1.0 mm clearance on each side
15 2.5 or ø5
Insulation of the handle frame
90
68 54.5 15 tube 2-pole 3-pole 4-pole
72 104.5
Plug-in
3-pole 4-pole
Mounting M5×0.8 95 125
plate Terminal block mounting nut Breaker (plug-in terminal block)
Plug-in 60 90
or screw mounted directly
terminal block
30
56
11
83.5
170
116
54
80
20 max.
5.5
85
12
56
30
M8 screw 67 97 127
21 ø8.5
65 Ø6 hole
89 30 2-pole 3-pole 4-pole or M5×0.8 tabs
Details of 2-pole
Conductor drilling
terminal
Drilling plan
Remarks: 1. The two-pole models of NF125-HV are three-pole models with the central pole removed.
2. Only two- and three-pole models are available for NF125-CV.
[mm]
71
MCCB – Characteristics & Dimensions
[kA]
60947-2 400 V 36/36 36/36 36/36 50/50 50/50 50/50
(Icu/Ics) 380 V 36/36 36/36 36/36 50/50 50/50 50/50
230 V 85/85 85/85 85/85 90/90 90/90 90/90
200 V 85/85 85/85 85/85 90/90 90/90 90/90
DC *1 300 V 20/20 20/20 20/20 20/20 20/20 20/20
NF250-SGV Standard attached parts Mounting screw: M4×0.7×55 (3P: 2pcs, 4P: 4pcs)
(front connection) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
Note: *1 When wired as shown at the bottom of page 41, three-pole models can be used for up to 500VDC, and 4-pole models for up to
600 V DC.
Operating characteristics
4h 4h 4h 4h
Operating characteristics Operating characteristics Operating characteristics Operating characteristics
2h 2h 2h 2h
Thermal-Adjustable types Thermal-Adjustable types Thermal-Adjustable types Thermal-Adjustable types
1h 1h 1h 1h NF125-SGV NF125-LGV
NF125-SGV NF125-LGV NF125-SGV NF125-LGV NF125-SGV NF125-LGV
30min Current setting Ir = 16-20A(Rated current In=20A) 30min Current setting Ir = 32-40A(Rated current In=40A) 30min Current setting Ir = 45–63 A (Rated current In=63 A) 30min Current setting Ir = 70–100 A (Rated current In=100 A)
Current setting Ir = 20-25A(Rated current In=25A) Current setting Ir = 35-50A(Rated current In=50A) Current setting Ir = 56–80 A (Rated current In=80 A) Current setting Ir = 90–125 A (Rated current In=125 A)
20min 20min 20min 20min NF160-SGV NF160-LGV
14min Current setting Ir = 25-32A(Rated current In=32A) 14min 14min 14min
10min Current setting Ir = 125–160 A (Rated current In=160 A)
10min 10min 10min NF250-SGV NF250-LGV
Instantaneous trip Current setting Ir = 125–160 A (Rated current In=160 A)
6min current 6min 6min 6min Current setting Ir = 140–200 A (Rated current In=200 A)
4min AC DC 4min Instantaneous trip
current 4min 4min Current setting Ir = 175–250 A (Rated current In=250 A)
600A ± 120A 850A ± 170A Instantaneous trip
AC DC current ratio
2min 2min 2min 2min
Max. 600A ± 120A 850A ± 170A Max. AC DC
7
×In (%) ×In (%)
1min 1min 1min 1000 ±200 1300 ±260 1min
Operating time
Operating time
Operating time
Operating time
Max. Instantaneous trip
current ratio
30s 30s 30s 30s AC DC
20s 20s 20s 20s ×In (%) ×In (%)
1000 ±200 1300 ±260
10s 10s 10s 10s
Max. Max. total Min. Max. total Min. Min.
5s breaking 5s breaking 5s 5s
Min. time time
2s 2s 2s 2s
1s
MCCB – Characteristics & Dimensions
1s 1s 1s
0.5s 0.5s 0.5s 0.5s
AC AC Max. total AC Max. total
0.2s 0.2s 0.2s breaking 0.2s breaking
AC DC DC time DC time
0.1s 0.1s 0.1s 0.1s
DC
0.05s 0.05s 0.05s 0.05s
AL AX
mounting mounting 120
Current rating (%)
100
90
80
–10 0 10 20 30 40 50 60
External accessories
Accessories Type name Reference page Accessories Type name Reference page
F F-2SV 63 3P MI-05SV3
Operating handle Mechanical interlock MI 68
V V-2SV 62 4P MI-2SV4
LC LC-05SV Small TC-S 3P TCS-2SV3
HLF-05SV TCL-2SV3
Handle lock device HL (*1) 64 3P
HLN-05SV Large TC-L TCL-2SV3L
Terminal
HL-S HLS-2SV 4P TCL-2SV4 67
cover
Notes * 1 HLF types are used for OFF-lock and HLN types for ON-lock. Skeleton TTC 3P TTC-2SV3
*2 Specify the working voltage. Refer to the reference page for type name. Rear BTC 3P BTC-2SV3
Plug-in PTC 3P PTC-2SV3
Electrical operation device MDS (*2) 66
72
MCCB – Characteristics & Dimensions
Front connection
30
Insulation barrier 24
M8 bolt
(removable) Breaker
(hex-socket)
Mounting hole
Solderless terminal for wire size
100
125~175 A 14~95 mm²
200 ~250 A 70~125 mm²
Wire connection
144
165
102
126
50
.5
ø8
ø4.5
10
C1
C1
Trip button
25 max.
ø8.5
100
45 35
Or 35
22 35 61
ø 8.5 M4×0.7 taps
Neutral pole 68 or ø5
70 105
4 72 3-pole 4-pole
9
105 140 25 max.
92
(Conductor thickness t = 7 max.)
3-pole 4-pole
Conductor drilling for Drilling plan
direct connection
Rear connection
4-pole
7
8
126
R1
52
Connection
22 allowance
20
M4×0.7 breaker
mounting screw
ø24 32.5
6 35
15
Ø9 35 35
15 70 Insulation tube 100
M8 bolt M4×0.7 taps
or ø5
105 70 105
68 71 1.0 mm clearance on each side
3-pole 4-pole of the handle frame
72 106
Plug-in
4-pole 145
3-pole 110
24 connection allowance
Plug-in
terminal block
34.5
165
80
54
11
144
70
6
151
56.5
15
20
28
Ø9
21 M5 70 105
M8 bolt Ø6 hole
terminal block mount-
3-pole 70 or M5×0.8 tabs
31 ing screw 107 142
Insulating 4-pole 105 Stud attachable in this
89 30
barrier direction only
3-pole 105 3-pole 4-pole
112
4-pole 140
Drilling plan
Remark: 1. Two-pole models are three-pole models with the central pole removed.
[mm]
73
MCCB – Characteristics & Dimensions
Number of poles 3 4 3 4 3 4 3 3
Rated insulation voltage Ui [V] 690 690 690 690 690
690 V 10/8 10/8 10/8 — —
[kA]
60947-2 400 V 75/75 75/75 75/75 150/150 150/150
(Icu/Ics) 380 V 75/75 75/75 75/75 150/150 150/150
230 V 100/100 100/100 100/100 150/150 150/150
200 V 100/100 100/100 100/100 150/150 150/150
DC *1 300 V 40/40 40/40 40/40 — —
NF250-HGV Standard attached parts Mounting screw: M4×0.7×55 (3P: 2pcs, 4P: 4pcs)
(front connection) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
Note: *1 When wired as shown at the bottom of page 41, three-pole models can be used for up to 500 V DC, and 4-pole models for up to
Operating characteristics
4h 4h 4h 4h
Operating characteristics Operating characteristics Operating characteristics Operating characteristics
2h 2h 2h 2h Thermal-Adjustable types
Thermal-Adjustable types Thermal-Adjustable types Thermal-Adjustable types
1h 1h 1h 1h NF125-HGV
NF125-HGV NF125-RGV NF125-HGV NF125-HGV Current setting Ir = 70–100 A (Rated current In=100 A)
30min Current setting Ir = 16-20A(Rated current In=20A) 30min Current setting Ir = 32-40A(Rated current In=40A) 30min Current setting Ir = 45–63 A (Rated current In=63 A) 30min Current setting Ir = 90–125 A (Rated current In=125 A)
Current setting Ir = 35-50A(Rated current In=50A) Current setting Ir = 56–80 A (Rated current In=80 A) NF160-HGV
20min Current setting Ir = 20-25A(Rated current In=25A) 20min 20min 20min Current setting Ir = 125–160 A (Rated current In=160 A)
Current setting Ir = 25-32A(Rated current In=32A) NF125-RGV 14min NF125-RGV NF250-HGV
14min 14min Current setting Ir = 32-40A(Rated current In=40A) Current setting Ir = 50–63 A (Rated current In=63 A) 14min Current setting Ir = 125–160 A (Rated current In=160 A)
10min 10min Current setting Ir = 40-50A(Rated current In=50A) 10min Current setting Ir = 63–80 A (Rated current In=80 A) 10min Current setting Ir = 140–200 A (Rated current In=200 A)
Instantaneous trip Current setting Ir = 175–250 A (Rated current In=250 A)
6min current 6min 6min 6min NF125-RGV
4min Current setting Ir = 80–100 A (Rated current In=100 A)
4min AC DC 4min Instantaneous trip
current 4min Current setting Ir = 100–125 A (Rated current In=125 A)
600A ± 120A 850A ± 170A Instantaneous trip NF250-RGV
AC DC current ratio
2min 2min 2min 2min Current setting Ir = 125–160 A (Rated current In=160 A)
Max. 600A ± 120A 850A ± 170A Max. AC DC Current setting Ir = 160–200 A (Rated current In=200 A)
7
×In (%) ×In (%) Current setting Ir = 200–250 A (Rated current In=250 A)
1min 1min 1min 1000 ±200 1300 ±260 1min
Operating time
Operating time
Operating time
Operating time
Max. Instantaneous trip
30s 30s 30s 30s current ratio
AC DC
20s 20s 20s 20s ×In (%) ×In (%)
1000 ±200 1300 ±260
10s 10s 10s 10s
Max. Max. total Min. Max. total Min. Min.
5s breaking 5s breaking 5s 5s
Min. time time
2s 2s 2s 2s
1s 1s
MCCB – Characteristics & Dimensions
1s 1s
0.5s 0.5s 0.5s 0.5s
AC AC Max. total AC Max. total
0.2s 0.2s 0.2s breaking 0.2s breaking
AC DC DC time DC time
0.1s 0.1s 0.1s 0.1s
DC
0.05s 0.05s 0.05s 0.05s
AL AX
mounting mounting 120
Current rating (%)
100
90
80
–10 0 10 20 30 40 50 60
External accessories
Accessories Type name Reference page Accessories Type name Reference page
F F-2SV 63 3P MI-05SV3
Operating handle Mechanical interlock MI 68
V V-2SV 62 4P MI-2SV4
LC LC-05SV Small TC-S 3P TCS-2SV3
HLF-05SV TCL-2SV3
Handle lock device HL (*1) 64 3P
HLN-05SV Large TC-L TCL-2SV3L
Terminal
HL-S HLS-2SV 4P TCL-2SV4 67
cover
Notes * 1 HLF types are used for OFF-lock and HLN types for ON-lock. Skeleton TTC 3P TTC-2SV3
*2 Specify the working voltage. Refer to the reference page for type name. Rear BTC 3P BTC-2SV3
Plug-in PTC 3P PTC-2SV3
Electrical operation device MDS (*2) 66
74
MCCB – Characteristics & Dimensions
Front connection
30
Insulation barrier 24
M8 bolt
(removable) Breaker
(hex-socket)
Mounting hole
Solderless terminal for wire size
100
125~175A 14~95 mm²
200 ~250A 70~125 mm²
Wire connection
144
165
102
126
50
.5
ø8
ø4.5
10
C1
C1
Trip button
25 max.
ø8.5
100
45 35
Or 35
22 35 61
ø 8.5 M4×0.7 taps
Neutral pole 68 or ø5
70 105
4 72 3-pole 4-pole
9
105 140 25 max.
92
(Conductor thickness t = 7 max.)
3-pole 4-pole
Conductor drilling for Drilling plan
direct connection
Rear connection
4-pole
7
8
126
R1
52
Connection
22 allowance
20
M4×0.7 breaker
mounting screw
ø24 32.5
6 35
15
Ø9 35 35
15 70 Insulation tube 100
M8 bolt M4×0.7 taps
or ø5
105 70 105
68 71 1.0 mm clearance on each side
3-pole 4-pole of the handle frame
72 106
Plug-in
4-pole 145
3-pole 110
24 connection allowance
Plug-in
terminal block
34.5
165
80
54
11
144
70
6
151
56.5
15
20
28
Ø9
21 M5 70 105
M8 bolt Ø6 hole
terminal block mount-
3-pole 70 or M5×0.8 tabs
31 ing screw 107 142
Insulating 4-pole 105 Stud attachable in this
89 30
barrier direction only
3-pole 105 3-pole 4-pole
112
4-pole 140
Drilling plan
Remark: 1. Two-pole models are three-pole models with the central pole removed.
[mm]
75
MCCB – Characteristics & Dimensions
capacity [kA]
IEC/EN AC 415 V 36/36 70/70 36/36 70/70
60947-2
(Icu/Ics) 400 V 36/36 75/75 36/36 75/75
380 V 36/36 75/75 36/36 75/75
230 V 85/85 100/100 85/85 100/100
DC *1 300 V — — — —
Standard attached parts Mounting screw: M4×0.7×55 (3P: 2pcs, 4P: 4pcs)
(front connection) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
NF125-SEV
Operating characteristics
10h 10h
5h 5h
Operating characteristics Operating characteristics
2h NF125-SEV NF125-HEV 2h NF250-SEV NF250-HEV
1h Current setting Ir Rated current In 1h Current setting Ir Rated current In
16–32 32 A 80–160 160 A
30min LTD operating time at 125 % (I6t ON) 32–63 63 A 30min LTD operating time at 125% (I6t ON) 125–250 250 A
20min 63–125 125 A 20min 670s (TL = 100s set)
14min 670 s (TL = 100 s set) 14min
10min 540 s (TL = 80 s set) 10min 540s (TL = 80s set)
6min 400 s (TL = 60 s set) 6min 400s (TL = 60s set)
4min 80 s (TL = 12 s set) 4min 80s (TL = 12s set)
2min 2min
1min LTD operating time TL 1min LTD operating time TL
Operating time
Operating time
7
30s (at 200 %) 30s (at 200 %)
20s 20s
I t OFF
6
I t OFF
6
10s 10s
STD pickup current Is STD pickup current Is
5s Ir × (2–2.5–3–3.5–4 5s Ir × (2–2.5–3–3.5–4
–5–6–7–8–10) ±15 % –5–6–7–8–10) ±15 %
2s 2s
1s 1s
MCCB – Characteristics & Dimensions
130
Rated ambient
temperature
External accessories
Accessories Type name Reference page Accessories Type name Reference page
F F-2SV 63 3P MI-05SV3
Operating handle Mechanical interlock MI 68
V V-2SV 62 4P MI-2SV4
LC LC-05SV Small TC-S 3P TCS-2SV3
HLF-05SV TCL-2SV3
Handle lock device HL (*1) 64 3P
HLN-05SV Large TC-L TCL-2SV3L
Terminal
HL-S HLS-2SV 4P TCL-2SV4 67
cover
Notes * 1 HLF types are used for OFF-lock and HLN types for ON-lock. Skeleton TTC 3P TTC-2SV3
*2 Specify the working voltage. Refer to the reference page for type name. Rear BTC 3P BTC-2SV3
Plug-in PTC 3P PTC-2SV3
Electrical operation device MDS (*2) 66
76
MCCB – Characteristics & Dimensions
Front connection
30
Insulation barrier M8 bolt
(removable) (hex-socket) 24
Solderless terminal for wire size
Breaker
Mounting hole 125~175A 14~95 mm²
100
200 ~250A 70~125 mm²
Wire connection
Trip button
.5
ø8
10
144
165
102
126
50
C1
ø4.5
C1
25 max.
Trip characteristics Or
Or
100
selector 45 35
ø8.5
ø8.5 35
22 35
9
61
Neutral pole M4×0.7 taps
70 105 68 or ø5
4 72 25 max.
105 140 3-pole 4-pole
92 (Conductor thickness t = 7 max.)
3-pole 4-pole
Conductor drilling
for direct connection Drilling plan
Rear connection
4-pole
Mounting plate Insulation Stud can be 4-pole 3-pole
t = 3.2 max. tube rotated 90° Breaker Breaker
3-pole
7
8
144
126
144
22 connection
R1
52
M4×0.7 breaker
mounting screw 35 32.5
15 6 ø24
35 35
15 Ø9 70 M4×0.7 taps 100
Insulation
M8 bolt 70 or ø5
68 71 tube 105
105 1.0 mm clearance on each side
72 106 3-pole 4-pole of the handle frame
Plug-in
24 connection allowance
4-pole 145
Plug-in 3-pole 110
Mounting
34.5
terminal block
plate
56.5
190
165
11
54
80
144
70
6
151
56.5
15
20
28
21 M5 Ø9 70 105
M8 bolt Ø6 hole
terminal block 3-pole 70
31 107 142 or M5×0.8 tabs
mounting screw
Insulation 4-pole 105
89 30 barrier Stud attachable in this
3-pole 105
112 direction only 3-pole 4-pole
4-pole 140
Drilling plan
Remark: 1. Products with data parenthesized come with PAL; built-in models with PAL have different external dimensions from the standard models.
[mm]
77
MCCB – Characteristics & Dimensions
NF125-UV, NF250-UV
[kA]
60947-2 400 V 200/200 200/200
(Icu/Ics) 380 V 200/200 200/200
230 V 200/200 200/200
200 V 200/200 200/200
DC *1 300 V — —
Mounting screw: M4×0.7×55 (3P: 2pcs, 4P: 4pcs)
NF125-UV Standard attached parts M4×0.7×73 (3P: 2pcs)
(front connection) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
Operating characteristics
4h 4h 4h
2h 2h 2h
Operating characteristics Operating characteristics
1h 1h Operating characteristics 1h NF125-UV
NF125-UV 15–30 A
NF125-UV 15A–30A 30min NF125-UV 40A–100A
NF125-UV 30min NF125-UV
125 125A
A
30min
20min 20min 40–100 A 20min
14min 14min 14min
10min 10min 10min
6min 6min 6min
4min 4min 4min
Max. (60–100 A)
(60A‒100A) Max.
2min 2min 2min
Instantaneous
Instantaneous triptripcurrent
current Max. (40–50 A)
(40A‒50A)
1min 1min 1min
Max. isisfixed
fixedtoto600A
600 ±A 120A.
±120 A
30s 30s 30s
20s 20s 20s
Operating time
Operating time
7
2s 2s 2s
1s 1s 1s
0.5s 0.5s 0.5s
Max. total
0.2s breaking 0.2s 0.2s
time Max. total Max. total
0.1s 0.1s breaking 0.1s breaking
time time
0.05s 0.05s 0.05s
MCCB – Characteristics & Dimensions
4h 4h
2h 2h
Operating characteristics
1h 1h Operating characteristics
NF250-UV 125–225 A
NF250-UV 125A‒225A NF250-UV 250A
NF250-UV 250 A
30min 30min
20min 20min
14min 14min
10min 10min
6min 6min
4min 4min
2min 2min
Max. Max.
1min 1min
30s 30s
Operating time
Operating time
20s 20s
10s 10s
5s 5s
Min. Min.
2s 2s
1s 1s
0.5s 0.5s
0.2s 0.2s
Max. total Max. total
0.1s breaking 0.1s breaking
time time
0.05s 0.05s
0.02s 0.02s
Time-delay trip Instantaneous trip Time-delay trip Instantaneous trip
0.01s 0.01s
100 125 200 300 500 700 1000 1500 2000 3000 4000 100 125 200 300 500 700 1000 1500 2000 3000 4000
400 600 400 600
× 100 % of rated current × 100 % of rated current
AL AX
mounting mounting 120
Current rating (%)
100
90
80
–10 0 10 20 30 40 50 60
Ambient temperature (°C)
(Rated ambient temperature 40 °C)
External accessories
Accessories Type name Reference page Accessories Type name Reference page
F F-1UV 63 3P MI-05SV3
Operating handle Mechanical interlock MI 68
V V-1UV 62 4P MI-05SV4
LC LC-05SV Small TC-S 3P TCS-1SV3
HLF-05SV 3P TCL-1SV3
Handle lock device HL (*1) 64 Large TC-L
HLN-05SV Terminal 4P TCL-1SV4
67
HL-S HLS-05SV cover Skeleton TTC 3P TCL-1SV3
Notes * 1 HLF types are used for OFF-lock and HLN types for ON-lock. Rear BTC 3P BTC-1SV3
*2 Specify the working voltage. Refer to the reference page for type name. Plug-in PTC 3P PTC-1SV3
Electrical operation device MDS (*2) 66
78
MCCB – Characteristics & Dimensions
Front connection
M8
M8 bolt
30
bolt
Insulation
Insulationbarrier
barrier (hex-socket)
(hex-socket) 24
(removable)
(removable) Breaker
Breaker
Mounting hole Solderless terminal
Solderless terminal
100
for wiresize
for wire size
2
125-175A 14-95mm
125~175 A 14~95 mm² 2
200-250A
200 ~250 70-125mm
A 70~125 mm²
Wire connection
Wire connection
144
165
102
126
.5
50
Øf 8
f 4.5
10
C1
C1
Trip button 25 max.
max.
Ø8.5
f 8.5
100
45 or Or 35 35
5.5
fØ88
22 35 .
61
M4 0.7taps
M4×0.7 taps
Neutral pole or ø5
f5
70 68 or
105
9
105
4 72 25 max.
25 max. 3-pole
3-pole 4-pole
4-pole
140
92 (Conductor thickness
(Conductor thickness
3-pole
3-pole 4-pole
4-pole tt=7
= 7max.)
max.)
Conductor drilling
Conductor drilling Drilling
Drilling plan
plan
for direct
for direct connection
connection
Rear connection
4-pole
Mounting base
4-pole 3-pole
Mounting plate Stud can be
rotated 90° Breaker Breaker
t = 3.2 max. 3-pole
7
8
144
144
126
R1
52
M4 0.7breaker
M4×0.7 breaker
mounting screw 32.5
6 fØ24
24 35
15
35 35 100
15 f9
Ø9 70 M4 0.7taps
M4×0.7 taps
Insulation
Insulation
M8 bolt
bolt tube
tube or ø5
f5
105 70 105
68 71 1.0 mm clearance
1.0mm clearance on
on each
each side
side
of the handle frame
72 106 3-pole
3-pole 4-pole
4-pole
Drillingplan
Drilling plan Front-panel cutout
Front-panel cutout
Plug-in
4-pole
4-pole 145
24 connection allowance
3-pole 110
110
Plug-in
Mounting terminal block
34.5
Breaker
Breaker (plug-in
(plug-in terminal
terminal block)
block)
plate
Connection
56.5
allowance
190
165
80
54
11
144
70
6
151
56.5
15
20
28
Ø9
f9
21 M5 terminal block 70 105
M8 bolt Ø6
f 6 hole
hole
mountingblock
terminal screw 3-pole 70
31 or
orM5
M5screw
0.8 taps
mounting screw 107 142
Insulation
Insulation
4-pole 105 Stud attachable
attachablein
inthis
this
89 30 barrier
barrier
direction only
only
112 3-pole 105 3-pole
3-pole 4-pole
4-pole
4-pole 140
Drillingplan
Drilling plan
Remark: 1. Two-pole models are three-pole models with the central pole removed.
[mm]
79
MCCB – Characteristics & Dimensions
[kA]
60947-2 400 V 50/50 70/70 125/63
(Icu/Ics) 380 V 50/50 70/70 125/63
230 V 85/85 100/100 150/75
200 V 85/85 100/100 150/75
DC 250 V — — —
Standard attached parts Mounting screw: M6×72 (4pcs)
NF400-SEW (front connection) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
Operating characteristics
10h
Operating characteristics
5h
NF400-SEW NF400-HEW
NF400-REW
2h
Current Rated
1h setting Ir current In
200, 225, 250, 400 A
30min
20min LTD operating time at 125 % (I6t ON) 300, 350, 400 A
14min 1000 s (TL = 150 s set) Adjustable
10min 670 s (TL = 100 s set)
6min 400 s (TL = 60 s set)
4min 80 s (TL = 12 s set)
長限時動作時間
LTD operating time TLL
2min 12–60–80–100 s ±20 %
7 1min
(at 200%)
(at 200 %)
Operating time
動 30s
20s
作
10s Pre-alarm pickup
時 current Ip STD pickup current Is
MCCB – Characteristics & Dimensions
5s Ir x ( 0.70-0.75-0.80- In × (2–2.5–3–3.5–4
間 0.85-0.90-0.95-1.0) –5–6–7–8–10) ±15 %
2s ±10 %
1s
0.5s Pre-alarm operating STD operating time Ts
time Tp 0.3 ±0.06 s
TL
0.2s Tp = Tl ±20 % 0.2 ±0.04 s
2
0.1s (at 200 %) 0.1 ±0.03 s
0.06 ±0.02 s
0.05s
INST pick up current li i
0.02s Note x4 – x16 ±15 %
(Magnification to reference current) Max. total interrupting time
最大全遮断時間
0.01s
60 70 100 125 200 300 400 500 600 1000 1500 2000 3000 4000
Current setting (% of Ir)
Instantaneous tripping current (% of In)
130
Rated ambient
Operating handle AL
AL AX
AX SHT or UVT MG
MG Lead-wire direction
temperature
100
External accessories
Accessories Type name Reference page Accessories Type name Reference page
F F-4S 63 3P MI-4SW3
Operating handle Mechanical interlock MI 68
V V-4S 62 4P MI-4SW4
HL (*1) HLF-4SW 3P TCL-4SW3
Large TC-L
Handle lock device HLN-4SW 64 4P TCL-4SW4
HL-S
HLS-4SW 3P TTC-4SW3
Skeleton TTC 67
Notes * 1 HLF types are used for OFF-lock and HLN types for ON-lock. 4P TTC-4SW4
*2 Specify the working voltage. Refer to the reference page for type name. 3P BTC-4SW3
Rear BTC
4P BTC-4SW4
Electrical operation device MDS (*2) 66
80
MCCB – Characteristics & Dimensions
Front connection
16
3-pole
3-pole
110
Breaker
Breaker
Breaker
Breaker
43
39
Mounting hole
Mounting hole
194
102
12
257
R6
59
92
Ø12.5
f 12.5
fØ7
7
Trip button
Trip button
25
39
fØ10.5
10.5
44 M6 tapsororf 7
M6 tap 44
Neutral pole
Neutral pole ø7 hole
44 (Conductor thicknesst=8
Conductor thickness t =max.
8 max.)
118
f 14 for 97 Conductor drilling
Ø14 Conductor drilling for
M12 bolt
M12 bolt 56 103 for direct connection
direct connection
51 168 5 107 1.01.0mm
mm clearance
3-pole 4-pole
4-pole clearance on eachside
on each sideof
3-pole ofthe
thehandle
handleframe.
frame
112 185 155
140 196
Drilling plan
Drilling plan Front-panel cutout
Front-panel cutout
3-pole
3-pole 4-pole
4-pole
Boring dimensions
Boring dimensions forforrear
rearconnection
connection
Rear connection type
type barriers barriers (3-pole)
(3-pole)
4-pole
4-pole Groove forreducing
Groove for reducing Line side
Line side
Stud canbe
Stud can be Breaker
Breaker heat byovercurrent
heat by overcurrent
Mounting plate
Mounting plate
rotated 90°
rotated 90° 3-pole
3-pole 6 ×35
6-f Ø35
24 24
8
Connection
Connection
allowance
allowance
M6M6
taptaps
or for
ø7 hole
7
44-M6
× M6 taps
tap or or
f 7 ø7 7
194
225
225
225
194
265
14
25 20 20
26
83
24 24
screwfor
M6 screw for
mounting breaker
mounting breaker Ø35
f 35
44 44 11 11
10 8 8-M4 screw
8-M4 screw
Ø13
f 13 for Add these tapped holes in in
113 87 Insulationtube
Insulation 87 43.5 44 Add these tapped holes
M12 bolt
bolt
tube 8 positions
8 positions to to
standard boring.
standard
130.5 130.5 87 boring.
3-pole
3-pole 4-pole
4-pole
Load side
Load side
Drilling
Drillingplan
plan
Plug-in
Plug-in 4-pole
4-pole
terminal
Plug-in block
terminal block Mounting plate
Mounting plate 3-pole
3-pole
Breaker
Breaker
35
55
M8 terminal
terminalblock
block Connection
Connection
allowance
allowance
280
225
mounting screw
mounting screw
135
163
24
24
8
79
55
160
Ø10
f 10
15
28
28
18 Studattachable
Stud attachableinin 44 87
this
this direction
directiononly
only
121 136 181
87
fØ13
13 for Insulating
Insulationbarrier
M12
M12 bolt
bolt 130.5 barrier 3-pole
3-pole 4-pole
4-pole
Drilling
Drilling plan
plan
[mm]
81
MCCB – Characteristics & Dimensions
NF400-UEW
[kA]
60947-2 400 V 200/200
(Icu/Ics) 380 V 200/200
230 V 200/200
200 V 200/200
DC 250 V —
Standard attached parts Mounting screw: M6×65 (2pcs), M6×174 (2pcs)
(front connection) Insulation barrier: (3P: 4pcs)
NF400-UEW
Operating characteristics
10h
Operating characteristics
5h
NF400-UEW
2h
Current Rated
1h setting Ir current In
200, 225, 250, 400 A
30min
20min LTD operating time at 125 % (I6t ON) 300, 350, 400 A
14min 1000 s (TL = 150 s set) Adjustable
10min 670 s (TL = 100 s set)
6min 400 s (TL = 60 s set)
4min 80 s (TL = 12 s set)
長限時動作時間
LTD operating time TLL
2min 12–60–80–100 s ±20 %
7 1min
(at 200%)
(at 200 %)
Operating time
動 30s
20s
作
10s Pre-alarm pickup
時 current Ip STD pickup current Is
MCCB – Characteristics & Dimensions
5s Ir x ( 0.70-0.75- In × (2–2.5–3–3.5–4
間 0.80-0.85-0.90- –5–6–7–8–10) ±15 %
2s 0.95-1.0) ±10 %
1s
0.5s Pre-alarm operating STD operating time Ts
time Tp 0.3 ±0.06 s
TL
0.2s Tp = Tl ±20 % 0.2 ±0.04 s
2
0.1s (at 200 %) 0.1 ±0.03 s
0.06 ±0.02 s
0.05s
INST pick up current li i
0.02s Note x4 – x16 ±15 %
(Magnification to reference current) Max. total interrupting time
最大全遮断時間
0.01s
60 70 100 125 200 300 400 500 600 1000 1500 2000 3000 4000
Current setting (% of Ir)
Instantaneous tripping current (% of In)
130
Rated ambient
Operating handle AL
AL AX
AX SHT or UVT MG
MG Lead-wire direction
temperature
100
External accessories
Accessories Type name Reference page Accessories Type name Reference page
F F-4U 63 Mechanical interlock MI 3P MI-4SW3 68
Operating handle
V V-4U 62 Large TC-L 3P TCL-4SW3
Terminal Skeleton
HLF-4SW TTC 3P TTC-4SW3 67
HL (*1) cover
Handle lock device HLN-4SW 64 Rear BTC 3P BTC-4SW3
HL-S HLS-4SW Electrical operation device MDS (*2) 66
Notes * 1 HLF types are used for OFF-lock and HLN types for ON-lock.
*2 Specify the working voltage. Refer to the reference page for type name.
82
MCCB – Characteristics & Dimensions
Front connection
Insulation barrier
Insulating barrier (removable)
(removable) 127.5
(Conductor
Conductor thickness 78 Breaker
Breaker
t=8 max. thickness
110
8
Breaker
Breaker
t = 8 max.)
43
Ø7
26
Mounting hole
Mounting hole
Ø12.5
R6
47
31
297
234
11.5
257
102
92
156
Ø12.5
Ø7
Trip Trip button
button
25
39
Ø10.5
Ø10.5
43
(Conductor thickness
Conductor thickness t=8 max.
44 M6 taps
M6 tap or for
7
141 118
ø7 hole
16
191.5
t = 8 max.)
Ø14 for
Ø14 Conductor drilling
51 M12 bolt 194 Conductor drilling
for direct connection
M12 bolt 1.01.0mm
mm clearance
clearance onon
eacheach
side side
28 200 for direct connection of the handle frame.
112 5 3-pole
3-pole of the handle frame
204
140 3-pole 252 Front-panel cutout
Front-panel cutout
Drilling plan
Drilling plan
3-pole
Boring dimensions
Boring dimensionsforforrear
rearconnection
connection
Rear connection type
type barriers barriers (3-pole)
(3-pole)
Groove Line
Lineside
Stud can be Groove forfor reducing
reducing side
Mounting plate
Mounting plate Breaker
Breaker heat
heat byby overcurrent
overcurrent
rotated
Stud 90°
can be rotated 90° 66-Ø35
× Ø35
24 24
8
M6
M6 taps
screw or or
f7
7
Connection
Connection ø7 hole 4 × M6
4-M6 taptaps or ø7
or Ø7
allowance
234
265
allowance
305
265
234
265
25 20 20
14
24 24
26
11 11
128
8-M4
8-M4screw
screw
10 M6screw
M6 screwfor for Ø35 Add
Addthese
thesetapped holesholes
tapped in in
mounting breaker 44
Ø13
Ø13 for
8
mounting breaker 44 88 positions
positions to standard boring.
to standard
210
M12 bolt 87 boring.
M12 bolt 87 Insulation
Insulation tube
87
tube Loadside
side
Load
3-pole
3-pole Drilling plan
Drilling plan
Note
NoteThe
Thebore
boredimensional
dimensionaldrawing
drawingshows
shows
thebreaker
the breakerviewed
viewedfrom
fromthe
therear.
rear.
Plug-in
Plug-in
terminal block
Plug-in terminal block
Breaker
Breaker
Mounting
Mounting angle
angle
35
Mounting angle
Mounting angle
max.max.
Connection
Connection
203
M8M8
terminal block
320
297
terminal block
265
175
allowance
allowance
24 mounting
mountingscrew
screw
203
24
79
8
160
28
attachable in Ø10
Studattachable
15
28 Stud
18 in this direction only
this direction only 44
218 87
Ø13 for
Ø13 Insulating
Insulation barrier 3-pole
3-pole
M12 bolt
M12 bolt barrier
3-pole
3-pole Drilling plan
Drilling plan
[mm]
83
MCCB – Characteristics & Dimensions
[kA]
60947-2 400 V 50/50 70/70 125/63
(Icu/Ics) 380 V 50/50 70/70 125/63
230 V 85/85 100/100 150/75
200 V 85/85 100/100 150/75
DC 250 V — — —
Standard attached parts Mounting screw: M6×72 (4pcs)
NF630-SEW (front connection) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
Operating characteristics
10h
Operating characteristics
5h
NF630-SEW NF630-HEW
NF630-REW
2h
Current Rated
1h setting Ir current In
300, 350, 400, 630 A
30min
20min LTD operating time at 125 % (I6t ON) 500, 600, 630 A
14min 1000 s (TL = 150 s set) Adjustable
10min 670 s (TL = 100 s set)
6min 400 s (TL = 60 s set)
4min 80 s (TL = 12 s set)
長限時動作時間
LTD operating time TLL
2min 12–60–80–100 s ±20 %
7
(at 200%)
(at 200 %)
1min
Operating time
動 30s
20s
作
10s Pre-alarm pickup
時 current Ip STD pickup current Is
5s
MCCB – Characteristics & Dimensions
Ir x ( 0.70-0.75-0.80- In × (2–2.5–3–3.5–4
間 0.85-0.90-0.95-1.0) –5–6–7–8–10) ±15 %
2s ±10 %
1s
0.5s Pre-alarm operating STD operating time Ts
time Tp 0.3 ±0.06 s
TL
0.2s Tp = Tl ±20 % 0.2 ±0.04 s
2
0.1s (at 200 %) 0.1 ±0.03 s
0.06 ±0.02 s
0.05s
INST pick up current li i
0.02s Note x4 – x15 ±15 %
(Magnification to reference current) Max. total interrupting time
最大全遮断時間
0.01s
60 70 100 125 200 300 400 500 600 1000 1500 2000 3000 4000
Current setting (% of Ir)
Instantaneous tripping current (% of In)
130
Rated ambient
Operating handle AL
AL AX
AX SHT or UVT MG
MG Lead-wire direction
temperature
100
External accessories
Accessories Type name Reference page Accessories Type name Reference page
F F-4S 63 3P MI-4SW3
Operating handle Mechanical interlock MI 68
V V-4S 62 4P MI-4SW4
Handle lock device HL (*1) HLF-4SW Large TC-L 3P TCL-4SW3
64
HL-S HLS-4SW 3P TTC-4SW3
Terminal Skeleton TTC
4P TTC-4SW4
Notes * 1 HLF types are used for OFF-lock and HLN types for ON-lock. 67
cover
*2 Specify the working voltage. Refer to the reference page for type name. 3P BTC-4SW3
Rear BTC
4P BTC-4SW4
Electrical operation device MDS (*2) 66
84
MCCB – Characteristics & Dimensions
Front connection
12
Insulation barrier
Insulating barrier
(removable)
(removable) 94.5
CL (Conductor
Conductor 4-pole
4-pole
28 thickness
thickness 44
t = 10
t=10 max.)
max. 8 30 Ø10.5 3-pole
3-pole
CL
Breaker
Breaker
110
(Conductor thickness
16
Conductor thickness t=10 max. CL
t = 10 max.)
Conductor drilling
43
Conductor
for drilling
direct connection
39
for direct connection
Mounting hole
Mounting hole CL Breaker
Breaker CL
R6
CL
257
CL
102
92
59
Trip
Ø12.5
Trip button
Ø7
button
39
CL
194
Neutral pole
Neutral pole 44 118
97
Ø14
f 14 for 1.0 mm1.0mm
clearance on
clearance oneach
each side
M12 bolt
M12 bolt 56 103 of the handle frame
side of handle.
M6 screw
M6 taps or
51 44 or f 7 44
168 5 107 ø7 hole Front-plate cutout
Front-panel cutout
112 185 155 3-pole
3-pole 4-pole
4-pole
140 196
Drilling
Drilling plan plan
3-pole
3-pole 4-pole
4-pole
Boring
Boringdimensions
dimensions for
for rear
rear connection
connection
Rear connection type(3-pole)
type barriers barriers (3-pole)
4-pole
4-pole Groove for reducing Line side
Line side
Mounting plate Breaker
Breaker Eddy-current
heat by overcurrent
Mounting plate Studcancan
Stud be be
3-pole
3-pole heat-reducing slit
rotated 90°90° 6 × Ø35
rotated CL CL
24 24
8
Connection
Connection M6M6taps or
screw
allowance
allowance
ø7orhole
f7 4-M6
4 × M6 taptaps
7
or
or fø7
7
225
CL
265
194
225
CL
225
194
25 20 20
14
83
32
128
24 24
M6breaker
M6 screw
Drilling plan
Drilling plan
Note The
Thebore
boredimensional
dimensional drawing
drawing shows
thebreaker
the breakerviewed
viewedfrom
from the
the rear.
rear.
Plug-in
55
M8 terminal block
Connection
Connectionallowance
allowance
CL mounting
M8 terminalscrew CL
225
280
block
163
135
25
mounting screw
25
10
93
55
28
160
Ø10
Stud attachable in
20
30 Stud attachable in
18 44 87
this direction only
this direction only
121 136 181
110
Ø13f 13
for Insulation barrier
Insulating barrier
M12M12 bolt
bolt 165.5
3-pole
3-pole 4-pole
4-pole
Drilling plan
Drilling plan
[mm]
85
MCCB – Characteristics & Dimensions
[kA]
60947-2 400 V 50/50 70/70 125/63
(Icu/Ics) 380 V 50/50 70/70 125/63
230 V 85/85 100/100 150/75
200 V 85/85 100/100 150/75
DC 250 V — — —
Standard attached parts Mounting screw: M6×35 (4pcs)
NF800-SEV (front connection) Insulation barrier: (3P: 2pcs, 4P: 3pcs)
Operating characteristics
10h
Operating characteristics
5h
NF800-SEW NF800-HEW
NF800-REW
2h
Current Rated
1h setting Ir current In
400, 450, 500, 800 A
30min
20min LTD operating time at 125 % (I6t ON) 600, 700, 800 A
14min 1000 s (TL = 150 s set) Adjustable
10min 670 s (TL = 100 s set)
6min 400 s (TL = 60 s set)
4min 80 s (TL = 12 s set)
長限時動作時間
LTD operating time TLL
7 2min
1min
12–60–80–100 s ±20 %
(at 200%)
(at 200 %)
Operating time
動 30s
20s
作
10s Pre-alarm pickup
MCCB – Characteristics & Dimensions
130
Rated ambient
100
External accessories
Accessories Type name Reference page Accessories Type name Reference page
F F-8S 63 3P MI-8SW3
Operating handle Mechanical interlock MI 68
V V-8S 62 4P MI-8SW4
HLF-4SW 3P TCL-8SW3
HL (*1) Large TC-L
Handle lock device HLN-4SW 64 4P TCL-8SW4
HL-S HLS-8SW Terminal 3P TTC-8SW3
cover Skeleton TTC 67
Notes * 1 HLF types are used for OFF-lock and HLN types for ON-lock. 4P TTC-8SW4
*2 Specify the working voltage. Refer to the reference page for type name. 3P BTC-8SW3
Rear BTC
4P BTC-8SW4
Electrical operation device MDS (*2) 66
86
MCCB – Characteristics & Dimensions
Front connection
Auxiliary Breaker
Breaker
87
32
handle
Auxiliary handle
(removable)
(removable) Terminal dimension
R6
forTerminal
directly connect-
dimension for
ingdirectly connecting
conductor
conductor
243
102
275
15
92
32
Ø8
Ø8.5
Ø14
8
14
87
32
51
12
46
22
70 M6 taps or
M6 tap 70
Trip or f hole
7 172
Trip button ø7
15
51 70 97
button 40
40 210 103
Neutral
Neutral pole
pole 1.0 1.0mm
mm clearance
clearance onon each side
each
140 (Conductor thickness 3-pole
3-pole 4-pole
210 280 5 107 (Conductor thickness t=10 max.)
t = 10 max.) 4-pole of the
sidehandle frame
of the handle frame.
fØ14
14 for
155 Conductor drilling Drillingplan
plan Front-panel cutout
M12 bolt
M12 bolt Conductor drilling Drilling Front-panel cutout
3-pole
3-pole 4-pole
4-pole 217 for direct
for direct connection
connection
Boring
Boringdimensions
dimensionsfor
forrear
rearconnection
connection
Rear connection type(3-pole)
type barriers barriers (3-pole)
24 24
10
7
Ø13 for
10
44-M6 tap or f 7
× M6 taps or ø7
M12 bolt
243
295
243
243
12.5
13
45
Plug-in
Mounting
Plug-in plate
Mounting plate StudStud can
can be be rotated
rotated 90 90°
terminal block
Plug-in terminal block
Breaker
Breaker
56
allowance
20
Connectionallowance
155
187
243
301
13
10
Connection
112
56
32
25
40
15
70 140
23
M8terminal
M8 terminal
blockblock
mounting screw
140 208
Ø10
278
126 mounting screw Ø13
f 13 for
M12 bolt
M12 bolt
3-pole
3-pole 4-pole
4-pole
Drilling plan
Drilling plan
[mm]
87
MCCB – Characteristics & Dimensions
NF800-UEW
[kA]
60947-2 400 V 200/200
(Icu/Ics) 380 V 200/200
230 V 200/200
200 V 200/200
DC 300 V —
Mounting screw: 3P: M6×35, M6×132 (2pcs each)
Standard attached parts 4P: M6×35 (3pcs), M6×132 (2pcs)
NF800-UEW (front connection) Insulation barrier: (3P: 2pcs, 4P: 3pcs)
Operating characteristics
10h
Operating characteristics
5h
NF800-UEW
2h
Current Rated
1h setting Ir current In
400, 450, 500, 800 A
30min
20min LTD operating time at 125 % (I6t ON) 600, 700, 800 A
14min 1000 s (TL = 150 s set) Adjustable
10min 670 s (TL = 100 s set)
6min 400 s (TL = 60 s set)
4min 80 s (TL = 12 s set)
長限時動作時間
LTD operating time TLL
7 2min
1min
12–60–80–100 s ±20 %
(at 200%)
(at 200 %)
Operating time
動 30s
20s
作
10s Pre-alarm pickup
MCCB – Characteristics & Dimensions
130
Rated ambient
100
External accessories
Accessories Type name Reference page Accessories Type name Reference page
Operating handle F F-8U 63 3P TCL-8UW3
Large TC-L
HL HL-4SW Terminal 4P TCL-8UW4
Handle lock device 64 67
HL-S HLS-8UW cover 3P BTC-8SW3
Rear BTC
3P MI-8SW3 4P BTC-8SW4
Mechanical interlock MI 68
4P MI-8SW4 Electrical operation device MDS (*1) 66
Notes *1 Specify the working voltage. Refer to the reference page for type name.
88
MCCB – Characteristics & Dimensions
Front connection
Insulation barrier
Insulating barrier (removable)
(removable)
Mounting holehole
Mounting
(Conductor 143
44(ON
44 (ONside)
position)
thickness
Conductor thickness
123,5(OFF
123.5 (OFFside)
position)
64
t = 12
t=12 max. max.)
8
110
87
Handle
Auxiliary handle
Ø14
(removable)
(removable)
Ø7
27.5
15 Terminal
Terminal dimension
dimension for for
directly connecting
directly connecting
322
112 conductor
275
102
conductor
Ø8.5
Ø7
N
12
8
Ø14
8
14 22
87
32
143 4-pole
4-pole
Trip 40
button
Trip button 51
70
194 3-pole
3-pole
15
22.5
M12 bolt 314 R6
M12 bolt
3-pole
3-pole 4-pole
4-pole
143
92
(Conductor
Conductor
Insulation barrier
Insulating barrier (removable) thickness
(removable) thickness 97
Mounting holehole
Mounting t=8 max.)
t = 8 max.
6.5
70
Handle
Auxiliary handle
Breaker
110
Ø14
Breaker (removable)
(removable) 51
f7
48 172
27.5
1.0mm
1.0mm clearance
clearance onon each side
each
15
of the
side handle frame
of the handle frame.
322
Front-panel cutout
290
275
Front-panel cutout
102
112
Ø7
N
16
Trip
48
Ø14
button
Trip button
7
70 70 6.5
M6screw
M6 screwor or
f 7 ø7 51 35
3-pole
3-pole 4-pole
4-pole 141
Neutral pole
Neutral pole
Drilling plan 70
Drilling plan f 14 for
Ø14
194
210 M12 bolt
M12 bolt 200
M6 tap
M6 or
tapø7 Groovefor for reducing
or f 7
Stud power supply side horizontal, Groove reducing
Connection Standard
vertical
direction of stud is horizontal
Breaker heat
heat byby overcurrent
overcurrent Connection
Connection
Connection on powerload
side,side
and is standard.
vertical on load side. Breaker
Mounting allowance
Mounting
Mounting allowance Otherwise,
plate allowance Please specify if other
specify the direction. Mounting plate
allowance Stud can
Stud can bebe 6-f 48
plate 25 plate 25 rotated
rotated 90°90°
5
24 24
10
8
10
4 × M6
4-M6 tap
tap or f7
or ø7
290
290
290
342
290
342
12.5
13
26
45
24 24
32 70 20
11 11 8 × M4
8-M4 screws
screw
8 15
70 Add
Addthese tapped
these holes in
tapped
10 10 10 70
70 8holes
positions
into8 standard boring.
positions
Ø13
f 13 for 140 M6 for for
M6 screw 140 Ø48 210 83 Ø13
f 13 for
to standard boring.
210 110 mounting M12 bolt 140
M12 bolt breaker 210 M12 bolt
M12 bolt breaker
mounting
3-pole
3-pole 4-pole
4-pole 4-pole 4-pole
NF400-UEW
NF400-UEW
Drilling
Drillingplan
plan
[mm]
89
MCCB – Characteristics & Dimensions
NF1000-SEW, NF1250-SEW
[kA]
60947-2 400 V 85/43 85/43
(Icu/Ics) 380 V 85/43 85/43
230 V 125/63 125/63
200 V 125/63 125/63
DC 250 V — —
Standard attached parts Mounting screw: M8×40 (4pcs each)
NF1000-SEW (front connection) Insulation barrier: (3P: 2pcs, 4P: 3pcs)
Operating characteristics
10h 10h
Operating characteristics Operating characteristics
5h 5h
NF1000-SEW NF1250-SEW
2h 2h
Current Rated Current Rated
1h setting Ir current In 1h setting Ir current In
500, 600, 700, 1000 A 600, 700, 800, 1000, 1250 A
30min 30min
20min LTD operating time at 125 % (I6t ON) 800, 900, 1000 A 20min LTD operating time at 125 % (I6t ON) 1200, 1250 A
14min 1000 s (TL = 150 s set) Adjustable 14min 1000 s (TL = 150 s set) Adjustable
10min 670 s (TL = 100 s set) 10min 670 s (TL = 100 s set)
7
6min 400 s (TL = 60 s set) 6min 400 s (TL = 60 s set)
4min 80 s (TL = 12 s set) 4min 80 s (TL = 12 s set)
長限時動作時間
LTD operating time TLL 長限時動作時間
LTD operating time TLL
2min 12–60–80–100s ±20 % 2min 12–60–80–100s ±20 %
(at 200%)
(at 200 %) (at 200%)
(at 200 %)
1min 1min
Operating time
Operating time
動 30s 動 30s
MCCB – Characteristics & Dimensions
20s 20s
作 作
10s Pre-alarm pickup 10s Pre-alarm pickup
時 current Ip STD pickup current Is 時 current Ip STD pickup current Is
5s Ir x ( 0.70-0.75-0.80- In × (2–2.5–3–3.5–4 5s Ir x ( 0.70-0.75-0.80- In × (2–2.5–3–3.5–4
間 0.85-0.90-0.95-1.0) –5–6–7–8–10) ±15 % 間 0.85-0.90-0.95-1.0) –5–6–7–8–10) ±15 %
2s ±10 % 2s ±10 %
1s 1s
0.5s Pre-alarm operating STD operating time Ts 0.5s Pre-alarm operating STD operating time Ts
time Tp 0.3 ±0.06 s time Tp 0.3 ±0.06 s
TL TL
0.2s Tp = Tl ±20 % 0.2 ±0.04 s 0.2s Tp = Tl ±20 % 0.2 ±0.04 s
2 2
0.1s (at 200 %) 0.1 ±0.03 s 0.1s (at 200 %) 0.1 ±0.03 s
0.06 ±0.02 s 0.06 ±0.02 s
0.05s 0.05s
INST pick up current li i INST pick up current li i
0.02s Note x4 – x12 ±15 % 0.02s Note x4 – x12 ±15 %
(Magnification to reference current) Max. total interrupting time
最大全遮断時間 (Magnification to reference current) Max. total interrupting time
最大全遮断時間
0.01s 0.01s
60 70 100 125 200 300 400 500 600 1000 1500 2000 3000 4000 60 70 100 125 200 300 400 500 600 1000 1500 2000 3000 4000
Current setting (% of Ir) Current setting (% of Ir)
Instantaneous tripping current (% of In) Instantaneous tripping current (% of In)
direction
temperature
mounting mounting
110
100
External accessories
Accessories Type name Reference page Accessories Type name Reference page
Handle lock device HL HL (on request) 64 Terminal Large 3P TCL-10SW3
TC-L 67
3P MI-10SW3 cover 4P TCL-10SW4
Mechanical interlock MI 68
4P MI-10SW4 Electrical operation device MDS (*1) 66
Notes *1 Specify the working voltage. Refer to the reference page for type name.
90
MCCB – Characteristics & Dimensions
Front connection
(Conductor
thickness
Conductor thickness 15 40
Insulation
Insulatingbarrier
barrier (removable)
(removable)
t=8 t2pcs
= 8, max.
2 pcs)
BoltM12
Bolt 50
M12× 50
110
Mounting
Mounting Breaker
Breaker
hole
hole
Handle
Auxiliary handle
(removable)
(removable)
346
406
375
Ø9.5
13
15 32 8
Ø17.5
80
18.5
Neutral 70 M8
M8taps
tap or ø10
f 10 70
Neutral pole
pole 15 44
43 70 133.5
140 210 17 140
3-pole
3-pole 4-pole
4-pole
f 13 M12
Ø13bolt
for 210 280 190
M12 bolt 280 Drilling plan
Drilling plan
3-pole
3-pole 4-pole
4-pole
Rear connection
4-pole
4-pole
Mountingplate
Mounting hole Breaker
3-pole
3-pole Breaker
M8
M8screw for mounting
for breaker breaker
mounting Breaker
Breaker
35.5
Studcan
Stud canbe
berotated
rotated90°
90°
86
R11.5
109
269
97
Connection
18 Connection
7
273
39.5
allowance
allowance 81.5
Ø13
22 (Conductor
Conductor
thickness thickness
13
86
t = 6,2pcs
2 pcs)
45
t=6 max.
Plug-in
Mountingplate
Mounting holes
Plug-in
Plug-interminal
terminalblock
block Breaker
M10
M10 for breaker
terminal mounting
block mounting screw
Stud can
Stud canbe
berotated
rotated90°
90°
28.5
136
269
105
100.5
25.5
269
13
28.5
225
30
32 8
104
136
Connection
12
Connection
allowance
allowance Ø12
(Conductor Ø13
15
Conductor
thickness thickness 43
t = 6, 2pcs
t=6 2 pcs)
max.
Insulation
Insulating 70 140
barrier 140
68
barrier 204 274
Bolt M12 ×45
Bolt M12 45
208 134
3-pole
3-pole 4-pole
4-pole
Drilling plan
Drilling plan
[mm]
91
MCCB – Characteristics & Dimensions
NF1600-SEW
[kA]
60947-2 400 V 85/43
(Icu/Ics) 380 V 85/43
230 V 125/63
200 V 125/63
DC 250 V —
Standard attached parts Mounting screw: M8×40 (4pcs each)
(front connection) Insulation barrier: (3P: 2pcs, 4P: 3pcs)
NF1600-SEW
Operating characteristics
10h
Operating characteristics
5h
NF1600-SEW
2h
Current Rated
1h setting Ir current In
800, 1000, 1200, 1600 A
30min
20min LTD operating time at 125 % (I6t ON) 1400, 1500, 1600 A
14min 1000s (TL = 150 s set) Adjustable
10min 670s (TL = 100 s set)
7
6min 400s (TL = 60 s set)
4min 80s (TL = 12 s set)
長限時動作時間
LTD operating time TLL
2min 12–60–80–100s ±20 %
(at 200%)
(at 200 %)
1min
Operating time
動 30s
MCCB – Characteristics & Dimensions
20s
作
10s Pre-alarm pickup
時 current Ip STD pickup current Is
5s Ir x ( 0.70-0.75-0.80- In × (2–2.5–3–3.5–4
間 0.85-0.90-0.95-1.0) –5–6–7–8–10) ±15 %
2s ±10 %
1s
0.5s Pre-alarm operating STD operating time Ts
time Tp 0.3 ±0.06 s
TL
0.2s Tp = Tl ±20 % 0.2 ±0.04 s
2
0.1s (at 200 %) 0.1 ±0.03 s
0.06 ±0.02 s
0.05s
INST pick up current li i
0.02s Note x4 – x12 ±15 %
(Magnification to reference current) Max. total interrupting time
最大全遮断時間
0.01s
60 70 100 125 200 300 400 500 600 1000 1500 2000 3000 4000
Current setting (% of Ir)
Instantaneous tripping current (% of In)
direction
temperature
mounting mounting
110
100
External accessories
92
MCCB – Characteristics & Dimensions
Front connection
Conductor
Insulation barrier thickness
60 t = 6 × W75 2035 4-pole
(removable) 38 ø 11
3-pole
Bolt M10 × 65 Breaker
38 15
(185.5)
(185.5)
Handle Breaker
Moun- (removable)
ting hole
18.5
210 280
R11.5
97
406
346
375
Ø17.5
Ø9.5
Trip button N
80
115
130
M8 taps or
20 49.5 7070
ø10 hole 1.0 mm clearance on each side
203 101.5 133.5
263 304.5 Neutral 17 140 3-pole 4-pole of the handle frame
364.5 pole 190
Drilling plan Front-panel cutout
280
3-pole 4-pole
38
60
18
106106
318
Stud can be
212
Stud can be
rotated 90°
rotated 90°
Breaker Mounting angle
Mounting angle Mounting angle Conductor
Conductor thickness t = 6 ×75
t = 6 ×75
160 min.
20
20
269
109
109
100 max.
273
273
15
81.5
18
38
54
15
140
38
ø10 hole
38 Ø11 70 Ø11 3-pole 4-pole
125 15 140125
Bolt M10 × 50 210 Bolt M10 × 50
3-pole 140 200 4-pole Drilling plan
20
109
269
109
506
534
273
81.5
273
38
54 18
60
36
38 15
38 70 70
15 Ø11
20 20 70 292 398
5
[mm]
93
MS-N – Overview
Mounting pitch
zz Safety and speedy terminal functions
zz Thermo plastic improves the barrier strength
Rated voltage zz Coil boasts lower coil consumption
terminals
zz Improvement of Electromagnet
DIN rail zz (DC electromagnet with AC operation)
mounting catch
zz Less noise nor surge from coil
zz Conform to IEC947-4-1, EN-Standards
Release button zz Mounting of the contactors is described on
Model name page 113.
Contact spring
Stationary contact
94
MS-N – Overview
DC interface unit
Surge absorber
S-NmmCX
Side clip-on
Side clip-on 54
Side clip-on
auxiliary contact
54
Front clip-on
MS-N – Overview
Pneumatic time
Auxiliary contact Auxiliary contact delay module
Auxiliary contact for (4 pole) (2 pole) (Factory install)
low level signal
Terminal cover
TH-NmmmCX
Mounting adapter
for OLR
UN-HZ12CX
Trip indicator
Reset release
for OLR
Terminal cover
95
MS-N – Overview
8
Thermal Overload Relays
MS-N – Overview
Contactor Relays
AC-operated type SR-N4CX 4A SR-N4CX 3A1B SR-N4CX 2A2B
Auxiliary contacts 4 NO 3 NO, 1 NC 2 NO, 2 NC
96
MS-N – Overview
S-N50CX S-N65CX S-N80 S-N95 S-N125 S-N150 S-N180 S-N220 S-N300 S-N400 S-N600 S-N800
SD-N50 SD-N65 SD-N80 SD-N95 SD-N125 SD-N150 — SD-N220 SD-N300 SD-N400 SD-N600 SD-N800
22 30 45 55 60 75 90 132 160 220 330 440
80 100 135 150 150 200 260 260 350 450 800 1000
2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC
JEM 1038
NK 98T405
AC3 1 1-0
V~ kW
220 19
440 37
550 45
IEC
60947-4-1
S-N80 DIN VDE
BS EN AC-3
V~ kW
240 22
440 45
500 45
690 45
MITSUBISHI ELECTRIC
BH762Y900H03
MITSUBISHI ELECTRIC
S-N50CX S-N65CX S-N80 S-N95 S-N125 S-N150 S-N180 S-N220 S-N300 S-N400 S-N600 S-N800
SD-N50 SD-N65 SD-N80 SD-N95 SD-N125 SD-N150 — SD-N220 SD-N400 SD-N400 SD-N600 SD-N800
AC operated: BH569N350
BH559N350 BH579N355 BH589N355 BH589N355 — —
DC operated: BH569N352
8
MS-N – Overview
TH-N60KPCX TH-N60TAKP TH-N120KP TH-N120TAKP TH-N220RHKP TH-N400RHKP TH-N600KP
12 – 65 A 54 – 105 A 34 – 100 A 85 – 150 A 65 – 250 A 85 – 400 A 200 – 800 A
97
MS-N – Contactors, Relays
S-N10CX S-N10CX S-N11CX S-N11CX S-N12CX S-N18CX S-N20CX S-N21CX S-N25CX S-N35CX
Specifications
ACmmmV1A ACmmmV1B ACmmmV1A ACmmmV1B ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV
Rated data
Rated continuous current Ith A 20 20 20 20 20 25 32 32 50 60
220–240 V kW (A) 2.5 (11) 2.5 (11) 3.5 (13) 3.5 (13) 3.5 (13) 4.5 (18) 5.5 (22) 5.5 (22) 7.5 (30) 11 (40)
Rated motor capacity 380–440 V kW (A) 4 (9) 4 (9) 5.5 (12) 5.5 (12) 5.5 (12) 7.5 (16) 11 (22) 11 (22) 15 (30) 18.5 (40)
3-phase
Category AC-3 500 kW (A) 4 (7) 4 (7) 5.5 (9) 5.5 (9) 5.5 (9) 7.5 (13) 11 (17) 11 (17) 15 (24) 18.5 (32)
690 V kW (A) 4 (5) 4 (5) 5.5 (7) 5.5 (7) 5.5 (7) 7.5 (9) 7.5 (9) 7.5 (9) 11 (12) 15 (17)
220–240 V kW (A) 7.5 (20) 7.5 (20) 7.5 (20) 7.5 (20) 7.5 (20) 9.5 (25) 12 (32) 12 (32) 18 (50) 20 (60)
Rated capacity for 380–440 V kW (A) 7 (11) 7 (11) 8.5 (13) 8.5 (13) 8.5 (13) 13 (20) 20 (32) 20 (32) 30 (50) 35 (60)
resistive loads 3ph,
Category AC-1 500 V–550 V kW (A) 7 (8) 7 (8) 9.5 (11) 9.5 (11) 9.5 (11) 13 (16) 25 (32) 25 (32) 40 (50) 50 (60)
690 V kW (A) 7 (6) 7 (6) 8 (8) 8 (8) 8 (8) 11 (10) 30 (32) 30 (32) 50 (50) 60 (60)
220–240 V kW 0.75 0.75 1.1 1.1 1.1 1.5 2.2 2.2 3 3.7
Rated capacity for jogging of AC 380–440 V kW 1.1 1.1 1.5 1.5 1.5 2.2 3.7 3.7 5.5 5.5
motors 3-ph, Cat. AC-4 (electrical
life is approx. 200,000 oper.) 500–550 V kW 1.1 1.1 1.5 1.5 1.5 2.2 3.7 3.7 5.5 5.5
690 V kW 1.1 1.1 1.5 1.5 1.5 2.2 3.7 3.7 5.5 5.5
Max. current for AC-4 duty at 440 V A 6 6 9 9 9 9 13 13 17 24
Rated curr. for DC non-ind. loads, 48 V A 10 10 12 12 12 12 20 20 25 35
Category DC-1, 100 oper./hour 110 V A 8 8 12 12 12 12 20 20 25 35
max. 500,000 oper. 220 V A 8 8 12 12 12 12 20 20 22 30
Rated curr. for DC motors 48 V A 6 6 10 10 10 10 20 20 25 30
Category DC-2 & DC-4, 100 oper./ 110 V A 4 4 8 8 8 8 15 15 20 20
hour, max.500,000 oper. 220 V A 2 2 4 4 4 4 8 8 10 10
220–240 V kvar 2.2 2.2 3 3 3 4 5.5 5.5 8.5 12
Rated capacity for 3-ph,
capacitors, 15 oper./hour 380–440 V kvar 3.3 3.3 4 4 4 6 10 10 14 20
max. 100,000 oper. a 550 V kvar 4 4 5 5 5 6 10 10 14 20
(ambient temp.: 40 °C)
690 V kvar 3.3 3.3 4.5 4.5 4.5 5.5 10 10 14 20
Current; 3-ph, Making A 110/110 110/110 130/120 130/120 130/120 180/180 220/220 220/220 300/300 400/400
cos φ = 0.35, 240/440 V Breaking A 100/72 100/72 120/100 120/100 120/100 180/130 220/220 220/220 300/240 400/320
Rated insulation voltage V 690 690 690 690 690 690 690 690 690 690
Electrical data
Inrush VA 60 60 60 60 60 60 90 90 110 110
Coil consumption Sealed VA 10 10 10 10 10 10 15 15 13 13
(at rated coil voltage)
Watts W 3.5 3.5 3.5 3.5 3.5 3.5 5.3 5.3 5.3 5.3
Category AC-1 oper./h 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800
Switching frequency Cat. AC2; AC-3 oper./h 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800 1,800
Category AC-4 oper./h 600 600 600 600 600 600 600 600 600 600
Operating time Closing ms 15 15 15 15 15 15 15 15 15 15
Main terminal (contactor) mm 2 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5 1–6 1–6 1–6 2–16 2–16
Main terminal (overload relay) mm2 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5 1–6 1–6 1–6 2–16 2–16
Control terminal mm2 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5
Busbar width mm — — — — — — — — — —
Standard auxiliary NO 1 — 1 — 1b — 1 2 2 2
contacts NC — 1 — 1 1b — 1 2 2 2
Weight kg 0.3 0.3 0.3 0.3 0.32 0.33 0.4 0.4 0.52 0.52
Dimensions (WxHxD) mm 43x78x78 43x78x78 43x78x78 43x78x78 53x78x78 43x79x81 63x81x81 63x81x81 75x89x91 75x89x91
AC 24 V 52566 52571 52576 52581 52586 57390 52591 52596 59365 59370
AC 48 V 52567 52572 52577 52582 52587 57391 52592 52597 59366 59371
AC 100 V — — — — — — — — — —
Order information c AC 120 V Art. no. 52568 52573 52578 52583 52588 57392 52593 52598 59367 59372
AC 200 V — — — — — — — — — —
AC 230 V 52569 52574 52579 52584 52589 57393 52594 52599 59368 59373
AC 400 V 52570 52575 52580 52585 52590 57394 52595 52600 59369 59374
a Peak value of inrush current <2000 % of the effective value for rated current of capacitors. Selection is invalid for the circuit of parallel capacitors which are controlled individually.
b Special with 2 NO and without NC; on request.
c Voltage range please see page 80.
d 660 A at ambient temperature 40–55 °C.
98
MS-N – Contactors, Relays
S-N50CX S-N65CX S-N80 S-N95 S-N125 S-N150 S-N180 S-N220 S-N300 S-N400 S-N600 S-N800
ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV ACmmmV
Rated data
80 100 135 150 150 200 260 260 350 450 800 d 1000 e
15 (55) 18.5 (65) 22 (85) 30 (105) 37 (125) 45 (150) 55 (180) 75 (250) 90 (300) 125 (400) 190 (630) 220 (800)
22 (50) 30 (65) 45 (85) 55 (105) 60 (120) 75 (150) 90 (180) 132 (250) 160 (300) 220 (400) 330 (630) 440 (800)
25 (38) 37 (60) 45 (75) 55 (85) 60 (90) 90 (140) 110 (180) 132 (200) 160 (250) 225 (350) 330 (500) 500 (720)
22 (26) 30 (38) 45 (52) 55 (65) 60 (70) 90 (100) 110 (120) 132 (150) 200 (220) 250 (300) 330 (420) 500 (630)
30 (80) 35 (100) 50 (135) 55 (150) 55 (150) 75 (200) 95 (260) 95 (260) 130 (350) 170 (450) 250 (660) 300 (800)
50 (80) 65 (100) 85 (135) 90 (150) 90 (150) 130 (200) 170 (260) 170 (260) 230 (350) 290 (450) 430 (660) 530 (800)
65 (80) 85 (100) 110 (135) 120 (150) 120 (150) 170 (200) 220 (260) 220 (260) 300 (350) 380 (450) 570 (660) 700 (800)
80 (80) 100 (100) 135 (135) 150 (150) 150 (150) 200 (200) 260 (260) 260 (260) 350 (350) 450 (450) 660 (660) 900 (800)
5.5 7.5 7.5 11 15 18.5 22 22 37 45 65 75
7.5 11 15 18.5 22 30 37 45 60 75 110 130
7.5 11 15 18.5 22 37 45 55 60 90 130 130
7.5 11 15 18.5 22 30 50 55 75 90 130 150
32 47 62 75 90 110 150 180 220 300 400 630
50 65 80 93 120 150 180 220 300 400 630 800
50 65 80 93 100 150 180 220 300 400 630 800
40 50 60 70 80 150 180 220 300 300 630 800
35 40 60 90 90 130 180 220 280 280 630 630
30 35 50 80 80 120 150 150 200 200 630 630
12 15 20 50 50 80 100 100 150 150 630 630
20 20 35 35 38 50 60 60 95 115 190 190
40 40 60 60 65 80 120 120 150 200 350 350
30 35 48 60 65 80 150 150 200 250 350 350
30 40 50 60 65 80 150 150 200 200 400 400
550/460 650/620 850/850 1050/1050 1250/1250 1500/1500 1800/1800 2500/2500 3000/3000 4000/4000 6500/6500 8000/8000
550/460 650/620 800/750 930/930 1000/1000 1200/1200 1450/1450 2000/2000 2400/2400 3200/3200 5040/5040 6400/6400
690 690 690 690 690 690 1000 1000 1000 1000 1000 1000
Electrical data
132 132 225 225 320 320 480 480 480 480 800 800
17 17 22 22 26 26 44 44 54 54 100 100
2.8 2.8 3.3 3.3 3.5 3.5 5 5 7.3 7.3 15 15
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
600 600 600 300 300 300 300 300 300 300 300 300
25 25 27 27 25 27 30 30 35 35 65 65
53
Mechanical data
53 75 75 85 85 100 100 120 120 75 75
9
1 1 1 1 1 1 1 1 1 0.5 0.5 0.5
5 5 5 5 5 5 5 5 5 5 5 5
99
MS-N – Contactors, Relays
9 Mechanical data
Electrical life (Category AC-3) Oper. 1 1 1 1 1 1 1
Mechanical life (million) 10 10 10 10 10 5 5
Main terminal (contactor) mm 2 1–2.5 1–2.5 1–2.5 1–6 2–16 2–25 2–25
MS-N – Contactors, Relays
Main terminal (overload relay) mm2 1–2.5 1–2.5 1–2.5 1–6 2–16 2–25 2–25
Control terminal mm2 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5 1–2.5
Busbar width mm — — — — — — —
Standard auxiliary NO 1 — 1b 2 2 2 2
contacts NC — 1 1b 2 2 2 2
Weight kg 0.62 0.62 0.64 0.72 0.85 2.1 2.1
Dimensions (WxHxD) mm 43x78x110 43x78x110 53x78x110 63x81x113 75x89x123 88x110x133 88x110x133
Order information f Art. no. 52601 52602 52603 52604 58533 113675 113678
a Peak value of inrush current <2000 % of the effective value for rated current of capacitors. Selection is invalidfor the circuit of parallel capacitors which are controlled individually.
b Special with 2 NO and without NC; on request
c 660 A at ambient temperature 40–55 °C.
d 800 A ambient temperature 40–55 °C.
e Conductor size in parentheses indicate compression terminal style not for bare clamping.
f Other coil voltages on request (please see page 102).
100
MS-N – Contactors, Relays
101
MS-N – Contactors, Relays
Coil ratings
9 AC 48 V
AC 100 V
48–50
100
48–50
100–110
V DC 24 V
DC 48 V
24
48
V
102
MS-N – Contactors, Relays
Electrical life AC
AC220–240
220–240VV
The electrical life of the main contacts of 5
a contactor is determined mainly by the
circuit-opening duty it will perform.
3
The relationship between electrical life
and rated current of Mitsubishi Electric 2
contactors under normal and jogging
1.5
duties of squirrel-cage motors is shown in
the figures. 1
operations)
ofoperations)
In the case of a mixture of normal and
jogging duties, the expected contactor 0.7
life can be determined as follows: 0.5
α S-N18
N = Nr/1 + 100 (Nr/Ni – 1) 0.3
(millionof
(millions
0.07
0.05
S-N220
0.03
S-N25 S-N125
S-N180
0.02 S-N10 S-N20,21
S-N65 S-N95 S-N300
S-N400 S-N800
S-N11,12 S-N35
0.01 S-N50 S-N80 S-N150 S-N600
2 3 5 7 10 15 20 30 50 70 100 150 200 300 500 800
Rated operating
Rated current
current (A) (A)
on-load factor 7 %,
600 operations/hour
(AC-4)-S-N10 to S-N300
300 operations/hour
(AC-4)-S-N400 to S-N600
150 operations/hour
(AC-4)-S-N800
N N
N
N
N
N N N N
N N N
103
MS-N – Contactors, Relays
Display
External trip mechanism
TH-N12KPCX, TH-N18KPCX TH-N12KPCX, TH-N18KPCX
When the green of the display lever can be seen, the device has been reset. When reset When tripped
Display
lever
MS-N – Contactors, Relays
When the display When the display window Can be tripped manually by
window is green the is white the device has been pushing in with a screwdriver
device has been reset. tripped. and turning the display lever.
When When
reset tripped
82 82
Reset Reset
RC.A. 65 H A RC.A. 65 H A
View View
Switchover Switchover from from
plate plate right right
Switching from manual to automatic: Break the stopper off and then, slide the switchover plate to the right Switching from manual to automatic: Flip the stopper on the end of the reset bar down and then, after
(to position “A”) to immobilize the reset bar. pushing it all the way in, rotate it counterclockwise 90° (to position “A”).
Switching from automatic to manual: Slide the switchover plate to the left (to position “H”). Switching from automatic to manual: Rotate the reset bar 90° clockwise (to position “H”) and the reset bar
will pop out
104
MS-N – Contactors, Relays
Specifications
TH- TH- TH- TH- TH- TH- TH- TH- TH- TH- TH-
Specifications N12KPCX N18KPCX N20KPCX N20TAKPCX N60KPCX N60TAKP N120KP N120TAKP N220RHKP N400RHKP N600KP
kkk A kkk A kkk A a kkk A kkk A kkk A kkk A kkk A kkk A kkk A kkk A b
Rated data
Max. setting current A 13 18 22 40 65 105 100 150 220 400 800
Range of setting current A 0.1–13 1–18 0.2–22 18–40 12–65 54–105 34–100 85–150 65–250 85–400 200–800
Rated insulation voltage V 690 690 690 690 690 690 690 690 1000 1000 690
Auxiliary contacts For all types: 1 NO + 1 NC
Min. W 0.8 0.9 0.8 1.4 1.7 2.4 2.5 3.2 2.5 2.5 2.5
Max. heater dissipation persetting
current path Max. W 1.8 2.2 2.2 3.5 4.9 5.2 7.1 8.6 6.0 6.0 6.0
setting
Rated operating current of auxiliary contacts
120 V A 2 2 2 2 2 2 2 2 2 2 2
NO
contact 240 V A 1 1 1 1 1 1 1 1 1 1 1
Category 500 V A 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
AC-15 120 V A 2 2 3 3 3 3 3 3 3 3 3
NC
contact 240 V A 1 1 2 2 2 2 2 2 2 2 2
500 V A 0.5 0.5 1 1 1 1 1 1 1 1 1
48 V A 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
Category DC-13 110 V A 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
220 V A 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Sizes
Main terminal Line side mm — — M4 M4 M6 M6 M8 M8 — — M4
screw size Load size mm M3.5 M4 M4 M5 M6 M6 M8 M8 M10 M12 M4
Line side mm² 2.5 c — 6 — 25 — 38 60 — — 6
Max. Main
Load side mm² 2.5 6 6 16 25 38 38 60 70 240 6
conductor
size Line side mm — — — — 15 — 20 20 — — —
Busbar
Load side mm — — — — 15 20 20 20 25 30 —
Auxiliary contacts mm² 2.5 2.5 4 4 4 4 4 4 4 4 4
Bimetal heating Direct Direct Direct Direct Direct Direct Direct Direct Via CTs Via CTs Via CTs b
Weight kg 0.11 0.14 0.14 0.2 0.26 0.32 0.48 0.75 2.5 2.7 0.14
89x73.5x83.5 103x67x105 112x87x105 x180x114
144
Dimensions (WxHxD) d mm 46x55x76.5 54x59x80 63x51x79 74x72x83.5 92x57x87 144x160x194 63x42x83.5
Order information Art. no. See page 106 for order information
a Specifications for the TH-N20HZKPCX (for stand-alone) are the same as for the TH-N20KPCX.
b Used with current transformer (to be supplied by the customer), for further information, see table on bottom of the page.
9
c When used with UN-HZ12CX.
d Dimensions on request
Specifications
Heater designation A 250 330 500 660
Setting range A 200 – 300 260 – 400 400 – 600 520 – 800
Current transformer ratio 400 / 5A 500 / 5A 750 / 5A 1,000 / 5A
Current transformer capacity at least 15 VA at least 15 VA at least 15 VA at least 15 VA
Recommended MITSUBISHI Cable CW-15L 400/5A 15 VA CW-15L 500/5A 15 VA CW-15L 750/5A 15 VA —
current transformer model number Bus bar CW-15LM 400/5A 15 VA CW-15LM 500/5A 15 VA CW-15LM 750/5A 15 VA CW-40LM 1000/5A 40 VA
105
MS-N – Contactors, Relays
TH-
Heater TH- TH- TH- TH- TH- TH- TH- TH- TH- TH- TH-
N20HZK-
Range (A) desig- N12KPCX N18KPCX N20KPCX N20TAKPCX N60KPCX N60TAKP N120KP N120TAKP N220RHKP N400RHKP N600KP
PCX
nation kkk A kkk A kkk A kkk A kkk A kkk A kkk A kkk A kkk A kkk A kkk A h
kkk A l
0.10–0.16 0.12A 52637
0.14–0.22 0.17A 52638
0.20–0.32 0.24A 52639 52656 63996
0.28–0.42 0.35A 52640 52657 63997
0.40–0.60 0.5A 52644 52658 63998
0.55–0.85 0.7A 52645 52659 63999
0.70–1.10 0.9A 52646 52660 64000
1.00–1.60 1.3A 52647 57378 52661 64002
1.40–2.00 1.7A 52648 57379 52662 64003
1.70–2.50 2.1A 52649 57380 52663 64004
2.00–3.00 2.5A 52650 57381 52664 64006
2.80–4.40 3.6A 52651 57382 52665 64007
4.00–6.00 5A 52652 57383 52666 64008
5.20–8.00 6.6A 52653 57384 52667 64009
7.00–11.0 9A 52654 57386 52668 64010
9.00–13.0 11A 52655 a 57388 52669 64011
12.0–18.0 15A 57389 52671 64012 113709
16.0–22.0 19A 52672 b 64015
18.0–26.0 22A 59393 113710
24.0–34.0 29A 59394 113711
30.0–40.0 35A 59395 c 113712
34.0–50.0 42A 113713 124425
43.0–65.0 54A 113714 124426
54.0–80.0 67A 113715 124427
65.0–100 82A 113716 d 124428 124432
85.0–105 95A 113717 d
85.0–125 105A 124430 124433 124438
100–150 125A 124431 e 124434 124439
120–180 150A 124435 124440
140–220 180A 124436 f 124441
170–250 210A 124437 f
9 200–300
260–400
250A
330A
124442
124443 g
on request
on request
400–600 500A on request
520–800 660A on request i
MS-N – Contactors, Relays
Contactors modified with thermal overload relays correspond to motor starter combination j (see also the overview on pages 96 and 97)
S-N10CX, S-N18CX S-N20CX, — S-N25CX, S-N50CX, S-N80, S-N125, S-N125, S-N180, S-N300, S-N600,
S-N11CX, S-N21CX, S-N35CX, S-N65CX, S-N95, S-N150, S-N150, S-N220, S-N400, S-N800,
S-N12CX, SD-N21CX SD-N35CX S-N80, SD-N80, SD-N125, SD-N125, SD-N220 SD-N300, SD-N600,
SD-N11CX, – – S-N95, SD-N95 SD-N150 SD-N150 SD-N400 SD-N800
SD-N12CX with with SD-N50,
Contactors UN-TH20 n UN-TH25CX SD-N65,
– SD-N80,
with SD-N95
connecting parts k
S-N25CX,
S-N35CX,
SD-N35CX
–
with
UN-TH25CX
Stand-alone type m U — — x — U u u u u u u
With connecting part UN-HZ12CX — — — — — — — — — — —
a Except for all S-N10. k For further information, see accessories on page 120.
b For all -N20 and all -N21 only. l Stand-alone
c For all -N35 only. Stand-alone with finger protection
m U
d For all -N95 only. u Stand-alone without finger protection
e For all -N150 only. x Stand-alone only
f For all -N220 only. – Stand-alone not possible
g For all -N400 only. n With finger protection
h TH-N600KP must be used with the current transformers
(to be supplied by the customer), see page 105.
i For all -N800 only.
j For the standard operation it is important to use the thermal overload relay
with one of the mentioned contactors and if necessary with a connecting part.
106
MS-N – Contactors, Relays
Max. fuse rating (AC 660 V) IEC 269-1 (A) Standard wire Motor capacity (three phase 50/60 Hz, based on four poles) (kW)
Heater
Range (A) size, (mm2)
designation aM gG gM AC 220–240 V AC 380 V AC 400–440 V AC 500 V
recommended
0.10–0.16 0.12 A 0.5 0.5 — 2
0.14–0.22 0.17 A 0.5 1 — 2
0.20–0.32 0.24 A 1 2 — 2 0.03 0.06 0.06 0.09
0.28–0.42 0.35 A 1 2 — 2 0.05 0.09 0.09 0.12
0.40–0.60 0.5 A 1 2 — 2 0.06 0.12 0.12 0.18
0.55–0.85 0.7 A 2 4 — 2 0.09 0.18 0.18 0.25
0.70–1.10 0.9 A 2 4 — 2 0.12 0.25 0.25 0.37
1.00–1.60 1.3 A 2 4 — 2 0.18 0.37 0.37; 0.55 0.55
1.40–2.00 1.7 A 4 6 — 2 0.25 0.55 0.75 0.75
1.70–2.50 2.1 A 4 6 — 2 0.37 0.75 — 1.1
2.00–3.00 2.5 A 6 10 — 2 0.55 1.1 1.1 1.5
2.80–4.40 3.6 A 6 10 — 2 0.75 1.5 1.5 2.2
4.00–6.00 5A 8 16 — 2 1.1 2.2 2.2 3
5.20–8.00 6.6 A 12 20 — 2 1.5 3 3; 3.7 3.7
7.00–11.0 9A 12 20 — 2 2.2 3.7; 4 3; 3.7 5.5
9.00–13.0 11 A 16 25 32M35 2 3 5.5 5.5 7.5
12.0–18.0 15 A 20 32 32M50 3.5 3.7 7.5 7.5; 9 9
16.0–22.0 19 A 25 40 32M63 3.5 5.5 11 11 11
18.0–26.0 22 A 40 63 32M63 5.5 5.5 11 11 15
24.0–34.0 29 A 50 80 63M80 8 7.5 15 15 18.5
30.0–40.0 35 A 63 80 63M80 8 9 18.5 18.5 22
34.0–50.0 42 A 63 100 100M100 14 11 22 22 30
43.0–65.0 54 A 80 125 100M125 22 15 30 30 37
54.0–80.0 67 A 100 160 100M160 22 18.5 37 37 45
65.0–100 82 A 125 200 100M200 38 22 45 45 55
85.0–105 95 A — 200 100M200 38 30 55 55 —
85.0–125 105 A — 250 200M250 50 30 55 55 75
100–150 125 A — 250 200M250 60 37 75 75 90
120–180 150 A — 315 200M315 45 90 90 110
140–220 180 A — 400 — 55 110 110 132
170–250 210 A — 500 — 75 132 132 —
200–300 250 A — 630 — 75 132; 160 132; 160 160
260–400
400–600
330 A
500 A
—
—
630
800
—
—
90; 110
132; 160
200
220; 250; 300
200
220; 250; 300
220; 250
400 9
520–800 660 A — 1000 — 200; 220 400 400 500
107
MS-N – Contactors, Relays
TH-N12KP
TH-N18KP
(h) (h)
2 2
1
Ambient 1 Ambient
Temperature: 20 °C Temperature: 20 °C
(s) (s)
1000 1000
800 800
600 600
400 400
200 200
Operating Time
Operating Time
100 100
Operating Time
Operating Time
80 80
60 60
40 40
30 30
20 20
10 10
8 8
6 6
4 4
2 2
Single phasing Single phasing
1 (TH-N12KP, 1
0.8 0.8 (TH-N18KP,
0.6 Mean value) 0.6 Mean value)
0.4 0.4
0.2 0.2
0.8 1 1.5 2 3 4 5 6 8 10 15 0.8 1 1.5 2 3 4 5 6 8 10 15
Multiples ofsetting
Multiple of setting current
current Multiples ofsetting
Multiple of setting current
current
9 TH-N20KP, TH-N20HZKP
TH-N20TAKP
MS-N – Contactors, Relays
(h) (h)
2 2
1 Ambient 1 Ambient
Temperature: 20 °C Temperature: 20 °C
(s) (s)
1000 1000
800 800
600 600
400 400
200 200
Operating Time
Operating Time
Operating Time
Operating Time
100 100
80 80
60 60
40 40
30 30
20 20
10 10
8 8
6 6
4 4
2 2
Single phasing Single phasing
1 1
0.8 (TH-N20..., 0.8 (TH-N20TAKP,
0.6 Mean value) 0.6 Mean value)
0.4 0.4
0.2 0.2
0.8 1 1.5 2 3 4 5 6 8 10 15 0.8 1 1.5 2 3 4 5 6 8 10 15
Multiples ofsetting
Multiple of setting current
current Multiples ofsetting
Multiple of setting current
current
108
MS-N – Contactors, Relays
TH-N60KP, TH-N60TAKP
TH-N120KP, TH-N120TAKP
(h) (h)
2 2
1 Ambient 1 Ambient
Temperature: 20 °C Temperature: 20 °C
(s) (s)
1000 1000
800 800
600 600
400 400
200 200
Operating Time
Operating Time
100 100
Operating Time
Operating Time
80 80
60 60
40 40
30 30
20 20
10 10
8 8
6 6
4 4
2 2
Single phasing Single phasing
1 (TH-N60(TA)KP, 1 (TH-N120(TA)KP,
0.8 0.8
0.6 Mean value) 0.6 Mean value)
0.4 0.4
0.2 0.2
0.8 1 1.5 2 3 4 5 6 8 10 15 0.8 1 1.5 2 3 4 5 6 8 10 15
Multiples
Multiple of setting
of setting current
current Multiples
Multiple of setting
of setting current
current
TH-N220RHKP, TH-N400RHKP
TH-N600KP
9
2 2
1
1 Ambient Ambient
Temperature: 20 °C Temperature: 20 °C
(s) (s)
1000 1000
800 800
600 600
400 400
200 200
Operating Time
Operating Time
Operating Time
Operating Time
100 100
80 80
60 60
40 40
30 30
20 20
10 10
8 8
6 6
4 4
2 2
Single phasing
(TH-N60(TA)KP, Single phasing
1 1
0.8 Mean value) 0.8 (TH-N120(TA)KP,
0.6 0.6 Mean value)
0.4 0.4
0.2 0.2
0.8 1 1.5 2 3 4 5 6 8 10 15 0.8 1 1.5 2 3 4 5 6 8 10 15
Multiple of
Multiples of setting
settingcurrent
current Multiple of
Multiples ofsetting
settingcurrent
current
109
MS-N – Optional Parts
Benefits:
zz High reliability: By adopting bifurcated mov- zz Various accessories common with the series
ing contacts and by improving the shape of S-N contactors (front and side clip-on type
the contacts, contact performance has been additional auxiliary contact blocks, surge
made more reliable than ever. absorbers)
zz Different types as: zz Finger protected types are available (DIN
Standard, big capacity or overlap contact 57106/VDE 0106 Part 100) (Suffix “CX”)
zz Various contact arrangement
zz Long life
zz Mountable on 35 mm DIN rails
zz Dust-proof construction
zz Easily visible coil ratings
zz Easy wiring (self-rising terminal screws)
Our standard contactor relay version is with With side clip-on or front clip-on a number of Type of auxiliary contact Symbol Code
4 auxiliary contacts. max. 8 auxiliary contacts is possible. Normally open NO = A
Normally closed NC = B
54
10 54
MS-N – Optional Parts
Side clip-on
Auxiliary contact for auxiliary contact
Low level signal
SR-N4
Auxiliary contact
Auxiliary contact (2 pole)
Auxiliary contact for (4 pole)
Low level signal
Terminal cover
110
MS-N – Optional Parts
Specifications
111
MS-N – Optional Parts
Environmental conditions
Coil ratings
In case of special order:
The following tables show the devices which are additionally available.
Please contact Mitsubishi Electric for further information.
10
MS-N – Optional Parts
112
MS-N – Optional Parts
Mounting
Top
Bottom
Frame size A B C D
B S-N10CX 5 5 10 15
D
A S-N11CX, S-N12CX 5 5 10 15
S-N18CX 5 5 10 15
C S-N20CX, S-N21CX 5 5 10 15
S-N25CX, S-N35CX 5 5 10 15
S-N50CX, S-N65CX 5 10 10 25
S-N80, S-N95 10 10 16 25
S-N125 10 12 16 25
S-N150
S-N180, S-N220
10
10
12
12
16
16
30
50 10
S-N300, S-N400 10 12 16 90
S-N600, S-N800 10 15 20 90
113
MS-N – Optional Parts
Application
All contactors can be extended by additional When ordering please check that the auxiliary
contacts which are available as a compact contact fits for your magnetic contactor.
module.
The auxiliary contacts are simple and safe to
extend by means of front or side clips.
UN-AX4
10 SD-N65CX
SR-N4CX
SD-N65CX
SR-N4CX
SD-N65CX
SR-N4CX
SD-N65CX
SR-N4CX
SD-N65CX
SR-N4CX
SD-N65CX
SR-N4CX
SD-N65CX
SR-N4CX
SRD-N4CX SRD-N4CX SRD-N4CX SRD-N4CX SRD-N4CX SRD-N4CX SRD-N4CX
MS-N – Optional Parts
Order information Art. no. 52625 52626 52627 52628 52629 52630 52631 52632
a Contact reliability may be decreased if it is operated more than 1 million operations.
b Front clip-on and side clip-on should not be mounted both.
c Maximum 1 piece of auxiliary contact block can be mounted on a Contactor/Relay.
d Maximum 2 pieces of auxiliary contact blocks can be mounted on a Contactor/Relay.
114
MS-N – Optional Parts
Mechanical interlocks
Application
Two contactors are safely and simply secured
against one another through mechanical
interlocking.
10
The mechanical interlocks are simple and safe to
115
MS-N – Optional Parts
DC interface modules
Application
Despite the low current requirements of our In accordance to the used contactor it can be
contactors and contactor relays, a number of mounted directly on the contactor or on a
PLC types with transistor outlets only allow separate location.
direct control via the DC interface module.
Order information Art. no. 52635 52636 On request On request On request On request
Specifications UN-TR4ANCX
Category
AC-15 AC 440 V A 1
Rated oper. AC 110 V A 6
current AC 230 V A 4
Category
AC-12 AC 440 V A 1.5
Rated DC 24 V A 1
operating DC 48 V A 0.5
120 current
Category DC 110 V A 0.3
DC-13 DC 220 V A 0.15
Rated DC 24 V A 2
90
operating DC 48 V A 1
Time delay (sec.)
current
Time delay (s)
116
MS-N – Optional Parts
Surge absorbers
Application
Surge absorbers serve the purpose of avoiding Contactors and relays with built-in surge
currency surges when coils are switched off. absorbers, varistor-type are available on your
They can be mounted safely and easily behind request.
the terminal strips. For S-N50 up to S-N800 the surge absorber are
implemented as standard (refer to page 94).
Order information Art. no. 127116 113704 113705 113706 113707 113708
a 2 pcs. are required for one contactor .
Order information Art. no. 127117 125994 125995 125996 125997 125998
b This part is only for the load side (1 piece). For the line side one UN-CZmm0 is required.
117
MS-N – Optional Parts
Replacement coils
Application
If, for technical or logistic reasons, a coil needs Changing procedure is done for
to be replaced, then this can be done fast and zz S-N10 to S-N95, SD-N11 to SD-N95, SR-N4
safely, as it involves very simple operations. and SRD-N4 by loosening a number of screws
When ordering please check for the right volt- zz S-N125 to S-N800, SD-N125 to SD-N800 by
age classification. replacing the coil cartridge.
AC-operated coils
10
MS-N – Optional Parts
DC-operated coils
118
MS-N – Optional Parts
Application
If used correctly, the contact kit does not need The kits consist of 3 moving contacts and
replacing during the lifetime stated in the 6 stationary contacts.
documentation. However, should this still be
required, then it can be done fast and without
any problems, as it involves no more than a few
simple operations.
BH- BH- BH- BH- BH- BH- BH- BH- BH- BH- BH-
Specifications 719N300 729N300 739N300 749N300 749N301 749N303 759N300 759N302 759N301 759N303 769N300
S-N10CX S-N18CX S-N20CX S-N25CX S-N35CX SD-N35CX S-N50CX SD-N50 S-N65CX SD-N65 S-N80
S-N11CX S-N21CX
Contactors S-N12CX SD-N21CX
SD-N11CX
SD-N12CX
Weight kg 0.03 0.05 0.05 0.07 0.07 0.07 0.11 0.11 0.11 0.11 0.1
Order information Art. no. 56754 59390 56755 59391 59392 62053 125971 125973 125975 125976 125977
BH- BH- BH- BH- BH- BH- BH- BH- BH- BH- BH-
Specifications 769N301 769N303 779N300 779N301 789N300 799N300 799N301 609N300 609N301 619N300 619N301
S-N95 SD-N95 S-N125 SD-N125 S-N150 S-N180 S-N220 S-N300 S-N400 S-N600 S-N800
Contactors SD-N150 SD-N220 SD-N300 SD-N400 SD-N600 SD-N800
Weight kg 0.1 0.1 0.1 0.1 0.2 0.4 0.4 0.8 0.8 2.5 2.5
Order information Art. no. 125979 125980 125981 125982 125983 125984 125985 125986 125987 125988 125989
Application
If used correctly, the bifurcated moving contact Nevertheless, auxiliary contacts can be replaced
warrants a maximum of contact safety and the safely and without any problems.
longest possible lifetime.
10
Order information Art. no. On request On request On request On request On request On request On request 113702 113703
119
MS-N – Optional Parts
Application
For connection between the contactor and the
thermal overload relay.
Connecting bars and mounting plate are
included in the OLR of TH-N220RHKP and
TH-N400RHKP for S-N180, S-N220, SD-N220,
S-N300, SD-N300, S-N400, SD-N400.
S-N20CX
UN-TH21CX
screws and cover
included S-N20CX
TH-N20KPCX
TH-N20KPCX
UN-TH21CX
screws and cover
included
10 Order information Art. no. 141108 63695 126000 126001 126002 126003 126004
MS-N – Optional Parts
Application
For the stand-alone application the thermal
overload relay TH-N12KPCX must be use with
the separate mounting adapter UN-HZ12CX.
Specifications UN-HZ12CX
Thermal overload relays TH-N12KPCX
120
MS-N – Optional Parts
Trip indicator
Application
An LED lights up to help you find and identify a
thermal overload relay that has been actuated.
The trip indicater consist of a cable (length
approx. 100 mm) and an indication module
which can be mounted separate from the
conductor.
Order information Art. no. On request On request On request On request On request On request On request On request On request
Reset release
Application
The reset release allows you to reset the actu- It has to be mounted directly on the thermal
ated thermal overload relay safely and without overload relay.
any problems while the cabinet door or drawout
is shut.
10
Order information Art. no. 52675 52676 52677 52678 52679 52680
Order information Art. no. 52681 52682 On request On request On request On request
121
Index
122
Automation solutions
A world of
automation solutions
Robots
Motion control and servos
Laser machines
CNC
controllers
HMI and GOTs
EDM machines
Micro PLCs
Modular PLCs
Mitsubishi Electric offers a wide range of automation equipment from PLCs and HMIs to CNC and EDM machines
15
Global partner. Local friend.
Mitsubishi Electric Europe B.V. / FA - European Business Group / Gothaer Straße 8 / D-40880 Ratingen / Germany /
Version check