CCNI ANTOFAGASTA SAFETY MANUAL
PART I
FIRE FIGHTING SYSTEMS
Cargo ships of 2000 gross tonnage and upwards, if a fire in any one compartment could put
all the pumps out of action there shall be an alternative means consisting of a fixed independely driven
emergency pump which shall be capable of supplying two jets of water to the satisfaction
of Administration. The capacity of pump shall not be less than 40% of total capacity of the fire pumps
and in any case not less than 25 m³/h. No direct access shall be permotted between the machinery space
and the space containing the emergency fire pump and it's source of power.
Entrance to Emergency Fire Pump compartement is located between bays 03 and 05.
This is vertical, cenrtifugal,
selfpriming, electric motor
driven, with capacity
72m³/h at 0.9MPa.
This pump is supplied from
Emergency Switchboard.
2
CCNI ANTOFAGASTA SAFETY MANUAL
PART I
FIRE FIGHTING SYSTEMS
3
CCNI ANTOFAGASTA SAFETY MANUAL
PART I
FIRE FIGHTING SYSTEMS
● Spraying Pump
● Spraying Pump
4
CCNI ANTOFAGASTA SAFETY MANUAL
PART I
FIRE FIGHTING SYSTEMS
5
CCNI ANTOFAGASTA SAFETY MANUAL
PART I
FIRE FIGHTING SYSTEMS
NOTE : To have Emergency Fire pump ready to use discharge and succion valves shall be always open.
●Dismountable, flexible hoses with Storz 65-2½ " connectionsto connect pipeline to the nozzles in hatch cover
Pipeline flanges on cross deck Hose connecting fixed pipeline with Nozzle system
6
CCNI ANTOFAGASTA SAFETY MANUAL
PART I
FIRE FIGHTING SYSTEMS
7
CCNI ANTOFAGASTA SAFETY MANUAL
PART I
FIRE FIGHTING SYSTEMS
ISOLATING VALVE
Location of valve
on portside
FIRE MAIN
Fire hoses shall be non-perishable material approved by
the Administration and shall be sufficient in length to project a jet
water to any of the spaces in which they may be required to be
used.each hose shall be provided with a nozzle and the
necessary couplings.Hoses shall, together with any necessary
fittings and tools,be kept ready for use in conspicuous
positions near the water service hydrants or connections.
Hoses dia 50mm with Storz C-2" type connection.
Fire hose holder with nozzle and spaner View of typical fire hose box
in machinery space.Always located close . on deck
to the fire hydrant
8
CCNI ANTOFAGASTA SAFETY MANUAL
PART I
FIRE FIGHTING SYSTEMS
All nozzles shall be of an approved dual-purpose type ( spray / jet type) incorporating a shutoff.
Those for superstructure have 12mm diameter, remaining 16 mm.Connection Storz C-2" type.
When sailing in freezing area fire line shall be drained by opening drain valve
located at each side of the vessel. Fire line is drained to the cofferdam
and than by opening of remote valve to no6 hold bilge.This water
can be pumped out by bilge system.
9
CCNI ANTOFAGASTA SAFETY MANUAL
PART II
FIRE DETECTION SYSTEM
10
CCNI ANTOFAGASTA SAFETY MANUAL
PART II
FIRE DETECTION SYSTEM
Manual Push Buttons- located all around the vessel ( always at the entrance to accommodations)
Heat Detectors
Heat detectors shall be certified to operate before
temperature exceeds 78°C but not until the temperature
exceeds 54°C, when the temperature is raised to those limits
at the rate less tham 1°C per minute.
11
CCNI ANTOFAGASTA SAFETY MANUAL
PART II
FIRE DETECTION SYSTEM
Alarm Signals
to the ship's whistle.
12
CCNI ANTOFAGASTA SAFETY MANUAL
PART II
ALARM SIGNALS
2 sec
1 2 3 4 5 6 7 LONG
2 sec
1 2 3 4 5 6 7 LONG
2. CO2 Alarm
Continuous high tone of dual tone sirens
3.Fire Alarm
High tone of dualtone sirens
1s
1s
4.Machinery Alarm
Second tone of dualtone sirens
2 sec
5.Telephone call
Second tone of dualtone sirens
2 sec
6. Telegraph sign
Second tone of dualtone sirens
2 sec
2 sec
2 sec
1 2 3 4 5 6 7 LONG
1s
1s
4
CCNI ANTOFAGASTA SAFETY MANUAL
PART III
EMERGENCY GENERATOR
The doors to Emergency Diesel Generator are located on 1st deck portside
Hydraulic starter
Emergency power source shall be capable of being readily
started in its cold condition down to a temperature of 0°C
by hand ( manual).Starting means shall be such as to
enable the diesel driven power source to be started at least
six times within a period of 30 min, and at least twice within
first 10 min.
Any service fuel tank shall contain sufficient fuel to enable
run power source at least 18 hours.
No direct access shall be permitted between the machinery
space and the space containing emergency source of power.
14
CCNI ANTOFAGASTA SAFETY MANUAL
PART III
EMERGENCY GENERATOR
INLET AIR
OUTLET AIR
15
CCNI ANTOFAGASTA SAFETY MANUAL
PART III
EMERGENCY GENERATOR
16
CCNI ANTOFAGASTA SAFETY MANUAL
PART III
EMERGENCY GENERATOR
2 START BY BATTERIES
2 AUTO
1 MAN.
- TURN SWITCH # E 201 S6 ON ESB TO
MANUAL CONTROL
3 AFTER STOPPING
- WHEN TWO GREEN DIODES (POS 1) STOP BLINKING CHANGE SWITCHES BACK TO AUTO
- PREPARE FOR NEXT START BY RAISING PRESSURE UP TO 276 - 340 BAR (4000-5000 lbf/in 2)
NOTE :
DURING FUNCTIONAL TEST USE "HANDRAULIC" STARTER EVERY SECOND TIME
4
CCNI ANTOFAGASTA SAFETY MANUAL
PART IV
FIRE FIGHTING SYSTEMS
EXTINGUISHERS ON BOARD
18
CCNI ANTOFAGASTA SAFETY MANUAL
PART IV
FIRE FIGHTING SYSTEMS
PURIFIER ROOM
ATTENTION:
Due to hot oil in process there is
general danger of fire in purifier
rooms,mainly case when bursting
a hot fuel oil pipe or upon any
other leakages of hot oil.
19
CCNI ANTOFAGASTA SAFETY MANUAL
PART IV
FIRE FIGHTING SYSTEMS
Small fire can be extinguished by fire blanket which is also located inside the purifier room.
20
CCNI ANTOFAGASTA SAFETY MANUAL
PART V
GALLEY FIRE PROTECTION
GALLEY
Galley is one of the most frequent scene of fire.This is reason that need special precautions
1.Galley suction filter has to be cleaned in short intervals.When filter screens are removed, check
for oil residues in suction trunk.
2.Never leave empty pot on hot plates.
3.Never put water into heated oil in pan.
For fighting small fire in galley powder extinguisher or fire blanket can be used.
In case of fire in suction trunk close dumper located in galley follow instructions for local CO2
system which is next to galley doors.When CO2 bottle is opened fire dumper shall be
closed automatically.If is still opened close it
manually. To close dumper
1.Open doors in galley ceiling.
2.Unsecure handle.
3.Put handle on valve and close it.
valve handle
21
CCNI ANTOFAGASTA SAFETY MANUAL
PART VI
MAIN ENGINE
MAIN ENGINE
Mist detector
22
CCNI ANTOFAGASTA SAFETY MANUAL
PART VI
MAIN ENGINE
MACHINERY ALARM
CO2 ALARM
ENGINE TELEGRAPH
23
CCNI ANTOFAGASTSA Manual
PART VII
SMOKE DETECTING
In case of fire
Press ACCEPT - button to silence sounder
Read display to locate sourece of fire
ATTENTION
The ball valves of Smoke Detection System must be closed before pressure test
and cleaning with compressed air !
24
CCNI ANTOFAGASTSA Manual
PART VII
SMOKE DETECTING
25
CCNI ANTOFAGASTA SAFETY MANUAL
PART VIII
CO 2 FIRE EXTINGUISHING SYSTEM
▲CO2 is not poisonous gas but already at 5% concentration it may cause death by ASPHYXIA.
Before entering CO2 compartment be sure that ventilation is running. It shall start automatically when
doors were opened.
Sensor which is
Switching ON ventilation
when the doors are open
For Engine room and Emergency Generator total flooding, quick release system is provided.
Remote cylinder valves and distribution valves opening for particular spaces is arranged from release cabinets
26
CCNI ANTOFAGASTA SAFETY MANUAL
PART VIII
CO 2 FIRE EXTINGUISHING SYSTEM
For Engine Room - additional emergency cabinet is fitted in CO2 Cylinder compartment. Manual releasing of CO2
for each space is also possible.
Opening of release cabinet door activates the CO2 alarm in extinguished space, while opening of distribution valve
stops fans and working equipment.
System is provided with time delay unit which shall be set minimum to 30 second delay.
3.Close all quick valves at fuel/oil tanks in engine room using releasing devices.
4.Working arrangements ( ME, Fuel pumps,ER fans etc,) are stopped automatically
after starting up the installation.
6.Close all doors. Louvers and vent heads to ER spaces apart from one exhaust louver.
( remote device is located on the wall of funnel, 1st deck Fr15PS)
7.Open cylinder valves on control cylinders and pull both the valves handles down.
The pressure from the control cylinder will open the main ER valve and
open ( after the preset time about 1 minute , requested minimum is 30 sec)
the CO2 valves on group cylinders for ER extinguishing.
Total designated is 149 cylinders
8.After directing CO2 to the Engine Room close lover described in pos 6.
1st deck Fr15 PS.
27
CCNI ANTOFAGASTA SAFETY MANUAL
PART VIII
CO 2 FIRE EXTINGUISHING SYSTEM
1.Cut off fuel supply to Emergency Generator set by remote closing fuel closing valve.
see PART III of manual.
1.Wait 2 hours after fire extinguishing, then appoint people equipped with fireman outfits and powder extinguishers
to check compartment. Check for flames and risk of explosion
2.Open ventilation .In Engine room start exhaust fans If it is impossible start portable fan with hoses.
3.Wait 2 hours and then send again two people for checking if an atmosphere is safe.
28
CCNI ANTOFAGASTA SAFETY MANUAL
PART VIII
CO 2 FIRE EXTINGUISHING SYSTEM
Compartment Co2
HOLD capacity amount Quantity released cylinders in pieces
m³ kilograms Total for empty hold Initially for full hold After lapse of one hour
1 7184 3848.5 86 56 ONE BY ONE
2 12254 6564.6 147 92
3 14229 7622.6 172 102 UP TO THE
4 14422 7726 174 103
5 13861 7425.5 167 99 DEDICATED
6 6071 3252.3 73 44 NUMBER
29
CCNI ANTOFAGASTA SAFETY MANUAL
PART VIII
CO 2 FIRE EXTINGUISHING SYSTEM
8.If in case of fully loaded hold, the fire has not been extinguished
after about 1 hour, then open same manhole slightly
and release the remaining cylinders up to the dedicated
number for empty hold and close manhole again.
1.Do not open the hold or ventilate it before calling at the nearest port.
2.After calling nearest port, extinguished hold to be checked by two people equipped with fireman's outfits in presence
of harbor fire brigade.
Check if there are not sources of open flames.
4. After two hours of fans operation send again two people for checking if the atmosphere is safe.
IN CASE VESSEL IN PORT AND FIRE IS STILL NOT EXTINGUISHED CO2 CAN BE SUPPLIED FROM SHORE
BY USING SHORE CONNECTION.
30
CCNI ANTOFAGASTA SAFETY MANUAL
PART VIII
CO 2 FIRE EXTINGUISHING SYSTEM
CO2 Shore connection on main deck Stdbside Valve connecting CO2 shore connection
and main CO2 manifold.
31
CCNI ANTOFAGASTA SAFETY MANUAL
PART IX
LIFESAVING APPLIANCES
Every SART shall be powered by batteries able to keep device in standby mode 96 hours
and at least 8 hours continuous work.When receiving signal from any X-band radar , audible
beeper shall be activated.
On board one SART is stowed on bridge- port side, other one inside the freefall life boat.
Normal switch position shall be put to automatic. How to switch to manual mode see
instruction on EPIRB's body.
32
CCNI ANTOFAGASTA SAFETY MANUAL
PART IX
LIFESAVING APPLIANCES
Testing of EPIRB :
●press test button and observe red led lamp. It shall
flash regularly .If not repeat test.
In case of second unsuccessful test result contact service.
Not less than 12 rocket parachute flares shall be carried and stowed on or near
the navigational bridge.
Additional 4 pieces shall be carried inside lifeboat.
You can find such rockets inside life raft as well.
Operation:
Remove red cap at the bottom
put your finger in the ring
hold the rocket over your head and pull the ring
The rocket will ignite instantaneously.
2.Hand flares stowed inside libfeboat 3.Smoke signal bouy stowed inside lifeboat.
33
CCNI ANTOFAGASTA SAFETY MANUAL
PART IX
LIFESAVING APPLIANCES
Every vessel over 200m shall carry on board more than 14 life buoys , at least half of these rings shall be
equipped with lights.
3.Life buoys equipped with lifeline 4.Life bouy equipped with light and smoke signal MOB
34
CCNI ANTOFAGASTA SAFETY MANUAL
PART IX
LIFESAVING APPLIANCES
35
CCNI ANTOFAGASTA SAFETY MANUAL
PART X
FREEFALL LIFEBOAT
FREEFALL LIFEBOAT
- Ensure that the batteries are in serviceable condition and correctly connected
-Check that oil levels in engine and gear box are correct
-Coolant level in header tank.
-Battery main switch is ON.
The charge control and oil pressure lights will be ON and the buzzer will sound.
Ignition position
36
CCNI ANTOFAGASTA SAFETY MANUAL
PART X
FREEFALL LIFEBOAT
● Depend on temperature, turn the starter switch to preheat position for 10-20 seconds
then turn the switch furter to position 2 to energize starter. Release immidiately when engine started.
If engine fail to start repeat sarting procedure after 15 seconds.
In very cold weather ( below -10C) it could be necessary to increasing preheating time to 30 sec.
and run the a starter for about 1 minute.
Starter positions
"0" Stop
Ignition
37
CCNI ANTOFAGASTA SAFETY MANUAL
PART X
FREEFALL LIFEBOAT
3.By operating release lever ( 3 - 4 strokes) the hydraulic pluger opens the stop pawn
until release hook is opened.The boat will slide down the lauching way
1.Remove glass.
2.Check if bypass valve is opened.
3. Take out handle for emergency release and screw -in release bolt by turning it clockwise until stop.
Stop pawn opens and the boat slides down the launching way.
38
CCNI ANTOFAGASTA SAFETY MANUAL
PART X
FREEFALL LIFEBOAT
● Connect recovery slings ( stored in deck store aft). Using davit heave up and put to the position
on slip way
39
CCNI ANTOFAGASTA SAFETY MANUAL
PART X
FREEFALL LIFEBOAT
40
CCNI ANTOFAGASTA SAFETY MANUAL
PART X
FREEFALL LIFEBOAT
41
FREEFALL RELEASE GEAR OPERATION
Operation for launching:
1. Before opening door remove safety bolt (13) from release gear, put
it into support at door and secure it
2. Take out securing pin
3. Close bypass valve
4. By operating release lever the hydraulic plunger opens the stop
pawl until the release hook is open. The boat now slides down the
launching way.
Operation for re-insetting the boat:
1. By opening bypass valve the return spring of the hydraulic plunger
returns the stop pawl in closed position while release hook is still
open. Put in securing pin.
2. Return boat with the recovery arrangement on to the launching way
One person will put the long link into lashing position while another
person will pull up the release hook to closed position. By doing
this the stop pawl opens and closes again automatically by the
return spring. (Remember that vypass valve must be open!)
Important: Check, if release hook rests abt. 15mm onto stop pawl.
(see marking)
3. When leaving the boat, put securing bolt (13) into release gear and
secure it.
If securing bolt doesn`t fit in hole, stop pawl is NOT in end position-
BOAT CAN BE LOST, IF SECURING PROCEDURE WILL BE IGNORED
IMPORTANT: Hydraulic oil level must be in within markings
NOTE: Side lashing fittings to be in open position during reinsetting:
afterwards to be closed
CAUTION: Release gear bypass valve has to be constantly OPEN
otherwise DANGER of unintended lauching.
CCNI ANTOFAGASTA SAFETY MANUAL
PART XI
RESCUE BOAT
Rescue boat equipment is stored inside the Rescue Boat locker on port side
1.Attach the fuel connector to the engine 2. Feed fuel to the carburetor
connector. Arrow mark on the primer valve by turn to right,pump until it is firm
should be facing the engine. .,and turn back the valve
Loosen the air vent screw on the tank
3. Place the control lever in the neutral position 4.Pull the starter handle slowly until you feel resistance.
and turn the throttle grip until the mark on the Then pull it quickly to run motor
grip faces the triangular mark on the steering
handle.Pull out the choke knob all the way.
( no choke operation is necessary when engine
is warm )
Be sure to connect the emergency stop hook to your waistor clothing. The engine will shut down it the hook's
line becomes disconnected from the engine.
44
CCNI ANTOFAGASTA SAFETY MANUAL
PART XI
RESCUE BOAT
45
CCNI ANTOFAGASTA SAFETY MANUAL
PART XI
RESCUE BOAT
Refilling valve
46
CCNI ANTOFAGASTA SAFETY MANUAL
PART XI
RESCUE BOAT
To heave up a boat
need to use electrical
winch operated by push
button or to use
handle for manual
operation.
47
CCNI ANTOFAGASTA SAFETY MANUAL
PART XI
RESCUE BOAT
48
CCNI ANTOFAGASTA SAFETY MANUAL
PART XII
LIFERAFTS
LIFERAFTS ON BOARD
● 30 Person davit launched life raft starboard side ●30 Person life raft on port side
49
CCNI ANTOFAGASTA SAFETY MANUAL
PART XII
LIFERAFTS
DAVIT OPERATION
Swinging direction
control valve
Refilling valve
Manual handle
for heaving loaden
hook
50
CCNI ANTOFAGASTA SAFETY MANUAL
PART XII
LIFERAFTS
51
CCNI ANTOFAGASTA SAFETY MANUAL
PART XII
LIFERAFTS
52
CCNI ANTOFAGASTA SAFETY MANUAL
PART XII
LIFERAFTS
53
CCNI ANTOFAGASTA SAFETY MANUAL
PART XIII
ESCAPING DEVICE SABRE
54
CCNI ANTOFAGASTA SAFETY MANUAL
PART XIII
ESCAPING DEVICE SABRE
55
CCNI ANTOFAGASTA SAFETY MANUAL
PART XIV
BREATHING APPARATUS
56
CCNI ANTOFAGASTA SAFETY MANUAL
PART XIV
BREATHING APPARATUS
57
CCNI ANTOFAGASTA SAFETY MANUAL
PART XIV
BREATHING APPARATUS
1. On the bridge
2.Fire fighting store - poop deck All equipped with 6 ltrs comperssed to 300
Bar air bottles.
Full charged bottle contains 1800ltrs of air.
58
CCNI ANTOFAGASTA SAFETY MANUAL
PART XIV
BREATHING APPARATUS
59
CCNI ANTOFAGASTA SAFETY MANUAL
PART XV
ESCAPING DEVICE SABRE
BLACK-OUT INSTRUCTION
( AFTER ELECTRIC POWER RESTORED)
60
CCNI ANTOFAGASTA SAFETY MANUAL
PART XVI
GMDSS
61
CCNI ANTOFAGASTA SAFETY MANUAL
PART XVI
GMDSS
62
CCNI ANTOFAGASTA SAFETY MANUAL
PART XVII MARPOL
ANNEX V
M/V CCNI ANTOFAGASTA
NOTE: IF YOU ARE IN DOUBT - PLEASE CONTACT NAVIGATION BRIDGE FOR GUIDANCE
KUNG IKAW AY NASA ALINLANGAN; TUMAWANG LANG SA "PUENTE"
PARA SA IYONG PATNUBAY
SPECIAL AREAS: MEDITERRANEAN ,BLACK SEA, BALTIC SEA, NORTH SEA INCL.
SKAW AND BRITISH CHANNEL,RED SEA, GULF AREAS, ANTARCTIC AREA
63
CCNI ANTOFAGASTA SAFETY MANUAL
PART XVII MARPOL
ANNEX V
AND THE WIDER CARIBBEAN AREA.
64
CCNI ANTOFAGASTA SAFETY MANUAL
PART XVIII
SYMBOLS USED ON FIRE PLANS AND PICTOGRAMS
65
CCNI ANTOFAGASTA SAFETY MANUAL
PART XVIII
SYMBOLS USED ON FIRE PLANS AND PICTOGRAMS
66
CCNI ANTOFAGASTA SAFETY MANUAL
PART XVIII
SYMBOLS USED ON FIRE PLANS AND PICTOGRAMS
67
CCNI ANTOFAGASTA SAFETY MANUAL
PART XVIII
SYMBOLS USED ON FIRE PLANS AND PICTOGRAMS
68
CCNI ANTOFAGASTA SAFETY MANUAL
PART XIX
SAFETY NET MOB
69
CCNI ANTOFAGASTA SAFETY MANUAL
PART XIX
SAFETY NET MOB
70
INSTRUCTIONS TO OPERATE EMERGENCY FIRE PUMP