Data: 12/12/2016

Projeto: Instituto Moreira Salles

Projeto: Instituto Moreira Salles

1
Data: 12/12/2016 Projeto: Instituto Moreira Salles

Selected pressure maintenance products


Calculated pressure maintenance selection
Input data Calculated data
Description Value Description Value
Application type Cooling Expansion coefficient [e] 0,0210
Fluid type: Água/Propilenoglicol - 50% por pes Expansion volume [Ve] 0,078 m3
Water content [Vs] 3,7 m3 Water reserve [Vwr] 0,019 m3
Installed power [Qs] 0 ton (refrig.) Water reserve optimized [Vwropt] 0,027 m3
Static height [Hst] 5m Contracted volume [Vcontr] 0,042 m3
Safety valve response pressure [psvs] 20 m H2O Vapour over-pressure [pv] 0 m H2O
Maximum temperature [tsmax] 30 °C Minimum pressure [p0] 8,33 m H2O
Supply temperature -4,4 °C Minimum PSV [psvs] 20 m H2O
Return temperature -0,9 °C Initial pressure [pa] 11,6 m H2O
Minimum temperature [tsmin] -4,4 °C Initial pressure optimized [paopt] 12,2 m H2O
Fill temperature 15 °C Target pressure [pman] -
Pressurisation on pump suction Final pressure [pe] 14,9 m H2O
Pump head - Specific flowrate of equalization volume -
NPSH of the pump [pzmin] 0 m H2O [qN/Q]
Necessary flowrate of equalization volume -
Max width 0m [qN]
Pressure factor [PF] 3,82
Max height 0m Nominal volume [VN] 0,368 m3
Expansion pipe up to (10 m) [DNe] -
Expansion pipe up to (30 m) [DNe] -

Product
#1 #2 Produto Artigo N° Qtde §

Membrane vessel 11111-015400 1


MN-400
Connection = Rosca macho
Etileno Glicol Nom. volume = 0,4 m3
Max. pressure = 61,2 m H2O
Temp. range = -10/100 °C
Weight = 55 kg
Max. weight = 477 kg

2
Data: 12/12/2016 Projeto: Instituto Moreira Salles

3
Data: 12/12/2016 Projeto: Instituto Moreira Salles

Lista de Artigos
Artigo N° Descrição Qtde

11111-015400 MN-400; Standard; PN 6 1