You are on page 1of 2

TDBFP A working & Remote= A TDBFP A Suction Flow= X, Quality of flow= Q1

TDBFP B working & Remote= B TDBFP B Suction Flow= Y Quality of flow= Q2

MDBFP C on and Scoop Auto= C MDBFPC Suction Flow= Z Quality of flow= Q3

0 for bad quality

Desired suction Flow= (AXQ1+BYQ2+CZQ3)/ (AQ1+BQ2+CQ3)= F,

Bias for TDBFP A

PV
F SP

PID

BIAS BLOCK

-10 %
LSC
+10 % K (force to 0 at ramp rate, force to man)
HSC
1% G (Forced to Auto)
RAMP RATE

(A+B+C)<= 1

A
AND
Q1

B OR K
AND
Q2

C
AND
Q3
(A+B+C)>1

MDBFP C Standby selected T off= 10 sec AND T pulse G

MDBFP C ON 2 sec

BIAS for TDBFP B: Substitute X wth Y BIAS For MDBFP C: Substitute Y with Z