You are on page 1of 1

TDBFP A working & Remote= A TDBFP A Suction Flow= X

TDBFP B working & Remote= B TDBFP B Suction Flow= Y

MDBFP C on and Scoop Auto= C MDBFPC Suction Flow= Z

Desired suction Flow= (AX+BY+CZ)/ (A+B+C)= F

Bias for TDBFP A

PV
F SP

PID

BIAS BLOCK

-10 %
LSC
+10 % IF (A+B+C)<= 1, force to 0 at ramp rate,
HSC
force to man
RAMP RATE
1% G (Forced to Auto)

(A+B+C)>1

MDBFP C Standby selected T off= 10 sec AND T pulse G

MDBFP C ON 2 sec

BIAS for TDBFP B: Substitute X wth Y BIAS For MDBFP C: Substitute Y with Z