2.3 Close the dilution air flow regulation valve (FV511050) and stop ADF511050 2.4 Check content CO in the gas circuit: 2.4.1 If CO is present in the gas circuit Do slowly ventilation avoiding to cool down temperature of the system with refractory thermal shock. Open N2 valves in to the boiler area and in to the gas manifold. Make ventilation approx. 5 -10 min. (during this period GCF should work at minimum speed ) and check the CO content in the gas circuit. If CO is present, continue ventilation. 2.4.2 If CO is absent Close N2 valves. Close the inlet damper (MOV521001.01; 02) of the GCF and stop GCF. Close the temporary stack valve (FV510099) (all gas circuit must be closed, N2 valves must be closed)