This document provides ampacity tables for single conductor or triplexed cables in conduit. The tables list the ampacity ratings in amps for various conductor sizes of copper and aluminum cables at different voltage levels and temperatures, either non-shielded or shielded, for cables installed individually or in groups in conduit in air. Ratings are provided for ambient air temperatures of 40°C.
This document provides ampacity tables for single conductor or triplexed cables in conduit. The tables list the ampacity ratings in amps for various conductor sizes of copper and aluminum cables at different voltage levels and temperatures, either non-shielded or shielded, for cables installed individually or in groups in conduit in air. Ratings are provided for ambient air temperatures of 40°C.
This document provides ampacity tables for single conductor or triplexed cables in conduit. The tables list the ampacity ratings in amps for various conductor sizes of copper and aluminum cables at different voltage levels and temperatures, either non-shielded or shielded, for cables installed individually or in groups in conduit in air. Ratings are provided for ambient air temperatures of 40°C.
cables in conduit — in air Closed shield operation. Shields bonded and grounded at multiple points. Any load factor from 30 to 100%. One triplexed cable or three single conductor cables in conduit.
The load ratings are for a single, loaded
cable in still air. In a group of loaded cables in close proximity in air, exposed or enclosed, follow the correction method shown on the ampacity correction factors page.