SHIPLINK® - CABLE SOLUTIONS AND SERVICES FOR SAFETY AND EFFICIENCY IN SHIPS 3
4
SHIPLINK® - Cable solutions and services for safety and efficiency in ships
Introduction................................................................6
MPRX® & MPRX® FLEXISHIP® 0.6/1 (1.2) kV....................8
MPRXCX® & MPRXCX® FLEXISHIP® 0.6/1 (1.2) kV..........12
MPRXCX® FLEXISHIP® EMC - 0.6/1 (1.2) kV..................16
MX Wiring cables 0.6/1 (1.2) kV...............................18
Class 2 Class 5
Cross section DC Maximum Resistance at 20°C DC Maximum Resistance at 20°C
(mm) Number (Ohm/km) Max. diameter of (Ohm/km)
of wires wires in conductor
Bare copper Tinned copper Bare copper Tinned copper
1.5 7 12.1 12.2 0.26 13.3 13.7
2.5 7 7.41 7.56 0.26 7.98 8.21
4 7 4.61 4.70 0.31 4.95 5.09
6 7 3.08 3.11 0.31 3.30 3.39
10 7 1.83 1.84 0.41 1.91 1.95
16 7 1.15 1.16 0.41 1.21 1.24
25 7 or 19 0.727 0.734 0.41 0.780 0.795
35 7 or 19 0.524 0.529 0.41 0.554 0.565
50 19 or 37 0.387 0.391 0.41 0.386 0.393
70 19 or 37 - 52 0.268 0.270 0.51 0.272 0.277
95 19 or 37 - 61 0.193 0.195 0.51 0.206 0.210
120 37 or 61 0.153 0.154 0.51 0.161 0.164
150 37 or 61 0.124 0.126 0.51 0.129 0.132
185 37 or 61 0.0991 0.100 0.51 0.106 0.108
240 61 or 61 0.0754 0.0762 0.51 0.0801 0.0817
300 61 or 61 0.0601 0.0607 0.51 0.0641 0.0654
For different length, or other air ambient temperature, the electrical resistance can be calculated with the formula:
Rt = R20 x L / Kt
where
Rt (Ohm/km) Electrical resistance in DC at a temperature t in °C for a length L (km).
R20 (Ohm/km) Maximum electrical resistance value in DC given in the IEC 60228 at 20°C.
Kt Correction temperature factor given in the following table and depending on the room air ambient
temperature.
6
Correction factors according to IEC 60228 Armour
IEC 60228 standard provides electrical resistance of copper On board, mechanical risk on cables is quite usual in
conductors at an ambient temperature of 20°C. For other unprotected spaces, it is the reason why most of them are
temperatures, correction factors are applied as below: armoured. As cable weight is important, and is aimed to be
minimized, steel tapes or steel wires armour are not used,
preference is given to metal braid.
Temperature (°C) Kt
5 1.064 That is the best compromise between mechanical protection,
10 1.042 weight and installation facility.
Application
MPRX® 0.6/1 kV power and control cables are used for wiring fixed installations not subject to mechanical risk. The highly
flexible MPRX® FLEXISHIP® range is recommended for installations and connections in narrow spaces where an optimal bending
radius is required. The sectoral conductors of multicore cables provide further space and weight savings on the cable trays.
Designed with halogen-free fire retardant materials, they provides optimum safety for people and maximal asset protection
against all risks of fire.
3. Outer sheath
Marking
(Filler if necessary)
NEXANS MPRX® or MPRX® FLEXISHIP® 0.6/1 kV
Polyolefin SHF1
«n» x «s» mm2 90°C
Colour: black
IEC 60092-353 / IEC 60332-3-22
SHF2 on request
«WW/YY» * * + metric marking
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity Flexible -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2 Class 5
IEC 60684-2
8
MPRX® 0.6/1 (1.2) kV - Power
10
MPRX® 0.6/1 (1.2) kV - Control
Test Voltage
AC between cores................................................................................................ 3.5 kV AC
Minimum bending radius for fixed installations MPRX® FLEXISHIP®....... 4 x outer diameter
Application
MPRXCX® 0.6/1 kV armoured power and control cables are used for wiring fixed installations where enhanced mechanical
protection and electrical screening (EMC) is required. The highly flexible MPRXCX® FLEXISHIP® range is recommended for
installations and connections in narrow spaces where an optimal bending radius is required. The sectoral conductors of multicore
cables provide further space and weight savings on the cable trays. Designed with halogen-free fire retardant materials, they
provides optimum safety for people and maximal asset protection against all risks of fire.
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity Flexible -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2 Class 5
IEC 60684-2
12
MPRXCX® 0.6/1 (1.2) kV - Power
14
MPRXCX® 0.6/1 (1.2) kV - Control
Test Voltage
AC between cores................................................................................................ 3.5 kV AC
Minimum bending radius for fixed installations MPRXCX® FLEXISHIP®... 5 x outer diameter
Application
Motor supply cable for frequency converters controlled low voltage AC drives on ships, called VFD applications. MPRXCX® EMC
cables are designed with a special coverage, copper-polyester tape and braid, which provide a 100% EMC protection.
Insu-lation with low dielectric constant is used to reduce reflected wave voltage peak magnitude. Symmetrical insulated ground
wires, placed in corner, can reduce reflected wave and return common mode noisy currents back to the drive. Enhanced
insulation is implement for 0.6/1(1.2) kV cable to fulfill periodic peak voltage up to 2xU=2 kV due to harmonics. These cables
are used on board of ships in all locations for fixed installations.
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity Flexible -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2 Class 5
IEC 60684-2
16
MPRXCX® FLEXISHIP® EMC 0.6/1 (1.2) kV Flexible class 5
Test Voltage
AC between cores................................................................................................... 5 kV AC
Application
MX 0.6/1 kV power wires are used for wiring switchboards, cabinets, control panels and various electrical enclosures. These
highly flexible wires are designed with finely stranded conductors for easy connection. The halogen-free fire retardant insulation
provides optimum safety for people and maximal asset protection against all risks of fire.
Design Standards
Max conductor temperature: 90°C • Construction & Design
IEC 60228
IEC 60092-350
IEC 60092-353
• Tests performances
1. Conductor
IEC 60332-3-22
Flexible bare copper
IEC 60332-1
class 5
IEC 60754-1/60754-2
2. Insulation IEC 60684-2
Halogen-free cross-linked IEC 61034
polyolefin type HF 90
• Materials
Colours: IEC 60092-360
black, green/yellow, red,
blue, white Marking
NEXANS MPRXCX® FLEXISHIP® EMC ”voltage”
«n» x «s» mm2 90°C
IEC 60092-353 / IEC 60332-3-22
«WW/YY» * * + metric marking
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity Flexible -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2 Class 5
IEC60684-2
18
MX® 0.6/1 (1.2) kV wiring cables
Test Voltage
AC in water........................................................................................................ 3,5 kV AC
Introduction..............................................................21
TCX® (C) 150/250 (300) V.......................................22
TCX® (I) 150/250 (300) V.........................................24
TX® (C) 150/250 (300) V..........................................26
TX® (I) 150/250 (300) V...........................................28
MPRX® 150/250 (300) V..........................................30
MPRXCX® 150/250 (300) V......................................32
20
INSTRUMENTATION & CONTROL CABLES
Introduction
Conductor Insulation
Tinned or bare copper, class 2 stranded conductors with 7 As for the power cables, Nexans‘s choice is for XLPE
wires are generally required for control and instrumentation compound according to IEC 60092-360 that offers the best
links. The most commun nominal cross-section areas are 0.75 compromise in terms of mechanical and electrical properties.
and 1 mm² for control, 0.75 and 1.5 mm² for instrumentation. XLPE compound has also a low permittivity value about 2.3.
Due to assembly length factor for large number of unit, electrical Cabling
resistance are not strictly in accordance with IEC 60228, For instrumentation range, in adjacent units, different cores
but electrical resistance values are complying with lay lengths are selected, in order to reduce inductive effects
IEC 60092-376 as indicated in the following table: and cross-talks. All units are assembled in concentric layers.
Instrumentation and control conductors in accordance with
Electrostatic Screen Individual (I) or/and Collective (C)
IEC 60092-376
Laminated aluminium bonded to polyester tape with a tinned
Class 2 drain wire is generally used as electrostatic screen with a
minimum overlap of 25% of the tape width. Copper braid
DC Maximum Resistance at 20°C
(Ohm/km) is also allowed to be used as screening as stated in IEC
Nominal
cross-section 60092-376.
Number
(mm) of wires
Bare copper Tinned copper Armour
As for power cables, armour is made of tinned or bare
0.50 7 40.4 41.6 copper braid.
0.75 7 26.0 26.3
For instrumentation TCX® (C) range, the armour is also used to
1.00 7 19.2 19.3 provide the function of a collective screen.
1.50 7 12.8 12.9
2.50 7 7.86 8.02 Sheath
SHF1 or SHF2 sheathing compounds are in accordance with
IEC 60092-360 standard.
Application
TCX® (C) 150/250V armoured twisted pair cables are used for telecommunication and instrumentation purposes. These cables
show a low transfer impedance in low frequency and an effective screening in high frequency, making them very suitable for
polluted electromagnetic surroundings. TCX® (C) cables are also selected where enhanced mechanical protection is required.
Designed with halogen-free fire retardant materials, they provide optimum safety for people and maximal asset protection against
all risks of fire.
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60684-2
22
TCX® (C)150/250 (300) V - Instrumentation
Test Voltage
Between cores of the same unit............................................................................... 1,5 kV AC
Application
TCX® (I) 150/250V armoured individually screened twisted pair cables are used for telecommunication and instrumentation
purposes. These cables provide strong protection against cross-talk in both low and high frequency runs, making them suitable
for highly polluted electromagnetic surroundings. TCX® (I) cables are also selected where enhanced mechanical protection is
required. Designed with halogen-free fire retardant materials, they provide optimum safety for people and maximal asset
protection against all risks of fire.
6. Outer sheath
Polyolefin SHF1
Colour: grey
SHF2 on request
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60684-2
24
TCX® (I)150/250 (300) V - Instrumentation
Outer diameter
Cables (mm²) Weight approx. (kg/km) El.no Nexans code no.
nom. (mm)
Test Voltage
Between cores of the same unit............................................................................... 1,5 kV AC
Minimum bending radius for fixed installations TCX® (I)................... 6 x outer diameter
Application
TX® (C) 150/250V overall screened twisted pair cables are used for telecommunication and instrumentation purposes. These
cables provide a medium protection against external electromagnetic disturbances. Designed with halogen-free fire retardant
materials, they provide optimum safety for people and maximal asset protection against all risks of fire.
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60684-2
26
TX® (C) 150/250 (300) V - Instrumentation
Outer diameter
Cables (mm²) Weight approx. (kg/km) El.no Nexans code no.
nom. (mm)
Test Voltage
AC between cores of the same unit............................................................................... 1.5 kV
Application
TX® (I) 150/250V overall and individually screened twisted pair cables are used for telecommunication and instrumentation pur-
poses. These cables show strong protection against cross-talk and result into a good compromise between TX® (C) and TCX® (C)
cables against external electromagnetic disturbances. Designed with halogen-free fire retardant materials, they provide optimum
safety for people and maximal asset protection against all risks of fire.
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60684-2
28
TX® (I)150/250 (300) V - Instrumentation cable standard class 2
Outer diameter
Cables (mm²) Weight approx. (kg/km) El.no Nexans code no.
nom. (mm)
Test Voltage
AC between cores of the same unit............................................................................... 1.5 kV
Application
MPRX® type is used on board of ships for fixed installations not subject to mechanical risk complying with IEC 60092-352.
MPRX® type withstands IEC 60332-3-22 fire test on bunched cables and performs to the SOLAS requirements. All materials used
to produce this cable are halogen-free. This design ensures that non corrosive and low toxic gases are emitted in case of fire.
Therefore, this cable type is especially designed for installations on passenger ships, as on other commercial vessels.
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60684-2
30
MPRX® 150/250 (300) V - Control
Test Voltage
AC between cores..................................................................................................... 1.5 kV
Application
MPRXCX® type is used on board of ships for fixed installations complying with IEC 60092-352. The good screening qualities of
the braid also reduce radio interference and electrical influences to electronic installations. MPRXCX® type withstands
IEC 60332-3-22 fire test on bunched cables and performs to the SOLAS requirements.
All materials used to produce this cable are halogen-free. The design ensures that non corrosive and low toxic gases are emitted
in case of fire. Therefore, this cable type is especially designed for installations on passenger ships, on Mega Yachts as on other
commercial vessels.
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
32
MPRXCX® 150/250 (300) V - Control
Test Voltage
AC between cores..................................................................................................... 1.5 kV
Introduction..............................................................35
LANmark Maritime Cables..........................................38
LAN SF/UTP Category 6............................................40
LAN S/FTP Category 7..............................................42
COAX FLAMEX - RG/KX serie 50 Ω / 75 Ω.................44
34
COMMUNICATION CABLES
Introduction
Communication cables include Coaxial, Fieldbus, LAN copper pairs and optical fibers cables.
Can Bus cable comes in a single or double pair; while An optical fiber is made up of three main parts: the core, the
Profibus cable is a single pair and both can be supplied with cladding and the coating.
SHF1 or SHF2 outer sheath depending on specification.
In the center, the “core” is made of doped silica and is
Adapted from the industrial plant environment, these high surrounded by the “cladding”, made of natural silica.
performance cables are fully sea resistant and can operate
The light signal propagates along the core and the signal is
safely in temperatures from -20°C to +70°C.
reflected on the surface between the core and the cladding.
Coating
Cladding
Core
62.5 µm 50 µm 9 µm
62.5/125 50/125 9/125
36
Technical fibers properties
Fiber types
... E9/125 ... G50/125 ... G62.5/125
Geometrical characteristics
Core diameter 9.0 ± 0,5 µm 50 ± 3 µm 62.5 ± 3 µm
Cladding diameter 125 ± 2 µm
Coating diameter 245 ± 10 µm
Numeral aperture 0.200 ± 0.015 0.275 ± 0.015
Optical characteristics
Attenuation:
850 nm ≤ 2.8 dB/km ≤ 3.4 dB/km
1300 nm ≤ 1.0 dB/km ≤ 1.1 dB/km
1550 nm ≤ 0.6 dB/km
Brandwidth at:
850 nm - ≥ 600MHz ≥ 200MHz
1300 nm - ≥ 1200MHz ≥ 600MHz
Dispersion at:
1310 nm < 3.5 ps/nm
1550 nm < 18 ps/nm
Index of reflaction (IOR) at:
850 nm 1.482 1.496
1300 nm 1.477 1.491
1310 nm 1.4677
1550 mm 1.4682
38
LANmark Maritime Connector
LANmark-7A GG45M is a standardised High Speed ‘2 in 1’ Snap-In Connector which contains
a full Cat 6A (RJ45) Interface as well as a full Cat 7A Interface, using additional contacts for the
1000 MHz transmission. LANmark-7A offers uniquely backwards compatible services realised
through an incorporated switch, which activates a maximum of 8 out of 12 contacts. For <500
MHz transmission performance, the upper 8 RJ45 contacts are used, for 1000 MHz the 8 contacts
in the extreme corners are used. When combined with a LANmark Cat 6 or Cat 7 Patch cord the
LANmark-7 GG45M exceeds the requirements of the Cat 6/Class E standard as well as
Cat 7 / Class F (ISO/IEC/11801:2002) with considerable headroom.
Application
Nexans SF/UTP Category 6 cables are the mid-range 250 MHz offered from Nexans. Manufactured in accordance with ISO
IEC 61156-5 requirements, the SF/UTP cable is the best choice to support all Class E applications like Ethernet, Fast Ethernet,
Gigabit Ethernet... The Cat. 6 SF/UTP cables are suitable for basic voice and data installations up to 250 MHz.
Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 +80 °C High protection
IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60684-2
40
LOCAL AREA NETWORK (LAN) - SF/UTP Category 6
Dimensional data
Electrical Characteristics
• Mutual capacitance.............................................................. 56 nF/km
• Characteristic Impedance....................................................... 100 Ohm
• Maximum conductor electrical resistance in DC at 20°C...........80 Ohm/km
Transmission Characteristics
• Skew..............................................................................45 ns/100m
• Velocity of propagation..................................................................67%
• Coupling attenuation at 30 MHz.................................................. 75 dB
• Propagation delay (Max at 100 MHz)............................537.6 ns/100m
Application
Nexans S/FTP Category 7 cables are the high-end 600 MHz offered from Nexans. Manufactured in accordance with
ISO IEC 61156-5 requirements, this cable is the best choice to support all Class F applications like Ethernet, Fast Ethernet, Giga-
bit Ethernet... The Cat. 7 S/FTP cables are suitable for voice, data, CATV and sharing application installations up to 600 MHz.
5. Outer Sheath
Polyolefin SHF1
Colour: orange
Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 +80 °C High protection
IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60684-2
42
LOCAL AREA NETWORK (LAN) - SF/FTP Category 7
Dimensional data
Electrical Characteristics
• Mutual capacitance.............................................................. 45 nF/km
• Characteristic Impedance....................................................... 100 Ohm
• Maximum conductor electrical resistance in DC at 20°C...........75 Ohm/km
Transmission Characteristics
• Velocity of propagation..................................................................80%
• Propagation delay (Max at 100 MHz)............................537.6 ns/100m
Application
High Frequency Data transmission (communication equipment, radar, instrumentation equipment and video signal transmission.
COAX FLAMEX® cables show a high level of protection against electromagnetic interferences.
4. Screen
Single or double braid
Bare, tinned or silvered
copper
5. Outer Sheath
Polyolefin SHF1
Colour: black
SHF2 on request
Flame retardant Halogen-free Low smoke No toxicity Low corrosivity -30 +80 °C
IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60684-2
44
COAX 50 Ω - MIL C17
Conductor Dielectric
Braid Wire Outer Diameter Weight Nexans
Cable type Diam Diam El.no
Stranding Diameter (mm) (kg/km) code no.
(mm) (mm)
RG 58 CU 19 x 0.18 TC 0.90 3.0 TC 4.95 ± 0.15 40 TBD 10039962
RG 174 AU 7 x 0.16 BCw 0.48 1.55 TC 2.80 ± 0.15 10 TBD 10039961
RG 213 U 7 x 0.75 BC 2.25 7.30 BC 10.3 ± 0.20 157 TBD 10039963
RG 214 U 7 x 0.75 SC 2.25 7.30 2 x SC 10.8 ± 0.20 195 TBD 10039964
RG 178 U 7 x 0.10 SPCCS 0.30 0.90 SC 1.80 ± 0.10 7 TBD
RG 223 U 1 x 0.90 SC 0.90 3.02 2 x SC 5.38 ± 0.15 55 TBD
Conductor Dielectric
Braid Wire Outer Diameter Weight Nexans
Cable type Diam Diam El.no
Stranding Diameter (mm) (kg/km) code no.
(mm) (mm)
RG 6 1 x 1.0 BC 1.0 4.5 TC 7.1 ± 0.20 80 TBD TBD
RG 59 1 x 0.57 BCw 0.57 3.75 BC 6.15 ± 0.15 53 TBD 10039965
RG 11 1 x 1.6 BC 1.6 7.2 TC 10.3 ± 0.20 135 TBD TBD
Electrical Characteristics
KX 3B RG 174 AU
KX 4 RG 213 U
50 Ω KX 13 RG 214 U
KX 15 RG 58 CU
KX 21 RG 178 BU
KX 6A RG 59 BU
75 Ω
KX 8 RG 11AU
Introduction..................................................................................47
MPRX® 331 & MPRX® 331 FLEXISHIP® 0.6/1 (1.2) kV .......................48
MPRXCX® 331 FLEXISHIP® & MPRXCX® 331 0.6/1 (1.2) kV................51
TCX® (C) 331 150/250 (300) V....................................................54
TCX® (I) 331 150/250 (300) V......................................................56
TX® (C) 331 150/250 (300) V.......................................................58
TX® (I) 331 150/250 (300) V........................................................60
46
FIRE RESISTANT CABLES
Introduction
+
Fire resistant test according to
IEC 60331-2
+
Fire resistant test according to
IEC 60331-21
+
Fire resistant test according to IEC 60331-1
Application
MPRX® 331 0.6/1 kV fire resistant power and control cables maintain circuit integrity in case of fire by meeting performances re-
quirements from the IEC 60331 series for 90 minutes. They are used for detection and warning systems not subject to mechanical
risk. The highly flexible MPRX® 331 FLEXISHIP® range is recommended for installations and connections in narrow spaces where
an optimal bending radius is required. The sectoral conductors of multicore cables provide further space and weight savings on
the cable trays. Designed with halogen-free fire retardant materials, they provides optimum safety for people and maximal asset
protection against all risks of fire.
Fire resistant Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60331-21 IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60331-1 or 2 IEC 60684-2
48
MPRX® 331 - 0.6/1 (1.2) kV - Power
Test Voltage
AC between cores................................................................................................ 3.5 kV AC
50
MPRXCX ® 331/MPRXCX ® 331 FLEXISHIP ®
0.6/1 (1.2) kV Power & control
Application
MPRXCX® 331 0.6/1 kV armoured fire resistant power and control cables maintain circuit integrity in case of fire by meeting
performances requirements from the IEC 60331 series for 90 minutes. They are used for detection and warning systems where
enhanced mechanical protection and electrical screening (EMC) is required. The highly flexible MPRXCX® 331 FLEXISHIP® range
is recommended for installations and connections in narrow spaces where an optimal bending radius is required. The sectoral
conductors of multicore cables provide further space and weight savings on the cable trays. Designed with halogen-free fire retar-
dant materials, they provides optimum safety for people and maximal asset protection against all risks of fire.
Fire resistant Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60331-21 IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60331-1 or 2 IEC 60684-2
52
MPRXCX® 331 FLEXISHIP® 0.6/1 (1.2) kV - Power
Test Voltage
AC between cores................................................................................................ 3.5 kV AC
Application
TCX® (C) 331 150/250V fire resistant armoured twisted pair cables maintain circuit integrity in case of fire by meeting perfor-
mances requirements from the IEC 60331 series for 90 minutes. These telecommunication and instrumentation cables show a
low transfer impedance in low frequency and an effective screening in high frequency, making them very suitable for polluted
electromagnetic surroundings. TCX® (C) 331 cables are used for detection and warning systems where enhanced mechanical
protection is required. Designed with halogen-free fire retardant materials, they provide optimum safety for people and maximal
asset protection against all risks of fire.
5. Outer sheath
Polyolefin SHF1
Colour: orange
SHF2 on request
Fire resistant Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60331-21 IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60331-1 or 2 IEC 60684-2
54
TCX® (C) 331 150/250 (300) V - Instrumentation
Test Voltage
AC between cores of the same unit.......................................................................... 1.5 kV AC
Application
TCX® (I) 331 150/250V fire resistant armoured individually screened twisted pair cables maintain circuit integrity in case of fire
by meeting performances requirements from the IEC 60331 series for 90 minutes. These telecommunication and instrumentation
cables provide strong protection against cross-talk in both low and high frequency runs, making them suitable for highly polluted
electromagnetic surroundings.
TCX® (I) 331 cables are used for detection and warning systems where enhanced mechanical protection is required. Designed with
halogen-free fire retardant materials, they provide optimum safety for people and maximal asset protection against all risks of fire.
6. Outer sheath
Polyolefin SHF1
Colour: orange
SHF2 on request
Fire resistant Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60331-21 IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60331-1 or 2 IEC 60684-2
56
TCX® (I) 331 150/250 (300) V - Instrumentation standard class 2
Test Voltage
AC between cores of the same unit.......................................................................... 1.5 kV AC
Application
TX® (C) 331 150/250V fire resistant overall screened twisted pair cables maintain circuit integrity in case of fire by meeting
performances requirements from the IEC 60331 series for 90 minutes. These telecommunication and instrumentation cables
provide a medium protection against external electromagnetic disturbances. Designed with halogen-free fire retardant materials,
they provide optimum safety for people and maximal asset protection against all risks of fire.
Fire resistant Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60331-21 IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60331-1 or 2 IEC 60684-2
58
TX® (C) 331 150/250 (300) V - Instrumentation
Test Voltage
AC between cores of the same unit.......................................................................... 1.5 kV AC
Application
TX® (I) 331 150/250V fire resistant overall and individually screened twisted pair cables maintain circuit integrity in case of fire
by meeting performances requirements from the IEC 60331 series for 90 minutes. These telecommunication and instrumentation
cables show strong protection against cross-talk and result into a good compromise between TX® (C) 331 and TCX® (C) 331
cables against external electromagnetic disturbances. Designed with halogen-free fire retardant materials, they provide optimum
safety for people and maximal asset protection against all risks of fire.
Fire resistant Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity -30 + 80 °C
IEC 60331-21 IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2
IEC 60331-1 or 2 IEC 60684-2
60
TX® (I) 331 150/250 (300) V - Instrumentation
Test Voltage
AC between cores of the same unit.......................................................................... 1.5 kV AC
Introduction............................................................... 63
MPRXCX® FLEXISHIP® & MEPRXCX® FLEXISHIP® .............. 65
6/10 (12) kV – 8.7/15 (17.5) kV – 12/20 (24) kV
MPRXCX® FLEXISHIP® EMC 1.8/3 (3.6) kV.................... 68
MPRXCX® FLEXISHIP® 1.8/3 (3.6) kV............................ 70
62
MEDIUM VOLTAGE CABLES
Introduction
Nexans produces medium voltage cables for power backbone and propulsion in 1.8/3 kV, 6/10 kV, 8.7/15 kV and up to
12/20 kV. These cables are designed for fixed applications on board of commercial, offshore or navy vessels.
In order to provide easier installation conditions (enhanced flexibility and easy pulling) and shorter bending radius the
products MPRXCX® and MEPRXCX® FLEXISHIP® are designed with class 5 conductors.
In particular Nexans Variable frequency Driver cables (VFD) are designed to improve EMC protection compared to
regular screened types and the operating performance of VFD systems used for thrusters, movable propulsion systems, lifts
or drives.
IEC 60228 specifies different maximum electrical resistance 35 0.41 0.554 0.565
values for each nominal cross section area, both in class 2 or 50 0.41 0.386 0.393
class 5 conductors, and in bare or tinned copper. 70 0.51 0.272 0.277
95 0.51 0.206 0.210
In the table below, these values in Ohm/km are given for DC
measurement (direct current) at the normative temperature of 120 0.51 0.161 0.164
For different length, or other air ambient temperature, the electrical resistance can be calculated with the formula:
64
MPRXCX ® FLEXISHIP ® 6/10 (12) kV
MEPRXCX ® FLEXISHIP ® 8.7/15 (17.5) kV 12/20 (24) kV
Application
MPRXCX® FLEXISHIP® 6/10 kV and MEPRXCX® FLEXISHIP® 8.7/15 kV and 12/20 kV armoured power cables are used for
critical medium voltage systems where enhanced mechanical protection and electrical screening (EMC) is required. These products
are recommended for installations and connections in environments where an optimal bending radius is required. Designed with
halogen-free fire retardant materials, they provides optimum safety for people and maximal asset protection against all risks of fire.
MPRXCX® FLEXISHIP® 6/10 kV and MEPRXCX® FLEXISHIP® 8.7/15 kV and 12/20 kV are compatible with Nexans’ medium
voltage accessories to connect generators, switchgears and transformers.
4. Screen • Materials
Extruded semi-conductor IEC 60092-360
Concentric layer of copper wires
5. Inner covering
Halogen-free polyolefin
Marking
6. Armouring
NEXANS MPRXCX® or MEPRXCX® FLEXISHIP® «voltage»
Bare copper braid
«n» x «s» mm2 90°C
7. Outer sheath IEC 60092-354 / IEC 60332-3-22
Polyolefin SHF1 «WW/YY» + metric marking
Colour: red
SHF2 on request
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity Flexible -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2 Class 5
IEC 60684-2
66
MEPRXCX® FLEXISHIP® 12/20 (24) kV
Application
Motor supply cable for frequency converters controlled low voltage AC drives on ships, called VFD applications. MPRXCX®
FLEXISHIP® EMC cables are designed with a special coverage, copper-polyester tape and braid, which provide a 100% EMC
protection. Insulation with low dielectric constant is used to reduce reflected wave voltage peak magnitude.
Symmetrical insulated ground wires, placed in corner, can reduce reflected wave and return common mode noisy currents back to
the drive. Enhanced insulation is implement for 1.8/3 (3.6) kV cable to fulfill periodic peak voltage up to 3 kV due to harmonics.
These cables are used on board of ships in all locations for fixed installations.
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity Flexible -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2 Class 5
IEC 60684-2
68
MPRXCX® FLEXISHIP® EMC - 1.8/3 (3.6) kV flexible class 5
Test voltage
AC between cores..................................................................................................... 6.5 kV
Application
MPRXCX® FLEXISHIP® 1.8/3 kV armoured power cables are used for equipment in medium voltage areas where enhanced
mechanical protection and electrical screening (EMC) is required. These products are recommended for installations and
connections in narrow spaces where an optimal bending radius is required. Designed with halogen-free fire retardant materials,
they provides optimum safety for people and maximal asset protection against all risks of fire.
Fire retardant Flame retardant Halogen-free Low smoke No toxicity No corrosivity Flexible -30 + 80 °C
IEC 60332-3-22 IEC 60332--1 IEC 60754-1 IEC 61034 IEC 60754-2 Class 5
IEC 60684-2
70
MPRXCX® FLEXISHIP® 1.8/3 (3.6) kV
Test voltage
AC between cores..................................................................................................... 6.5 kV
Part 6 Accessories
Application Design
A kit of 3 terminations for use indoors in controlled environ-
mental conditions and subject to light condensation.
To connect MPRXCX® FLEXISHIP® and MEPRXCX® FLEXISHIP®
1. Cable lug
to equipments (transformers, switchgear, motors, etc).
(not included in the
standard kit)
3. Silicone tube
Termination Voltage UM Strike distance L Diameter over core insulation (mm) Conductor sizes (mm²)
type (kV) (mm) Min. Max. Min. Max.
ITK 224 24 260 14 33 25 240
ITK 324 24 300 30 50 300 800
For use with copper For use with copper For use with Alupe or For use with If the cable lug borrel Can be supplied with
wire screened cables. tape screened cables. C 33-226 cables. three-core cables: diameter (A) is less all common types of
No earthing device Also order a Kit MT. Please contact our see T-ITK. than 20 mm: order cable lugs.
is necessary. representative. a rubber adapting
sleeve.
74
Kit contents
The complete ITK termination kit comprises the following 3 x ITK 224 3 x ITK 324
components: termination kit termination kit
3 x Factory pre-assembled
silicone tubes comprising
stress relief and sealing
The kit also comprises water sealing mastic
mastic.
and installation instructions.
Ordering instructions
Select the part number corresponding All commercialised European standard
to both the system voltage and the cable lugs can be used. Cable lugs should
cable insulation diameter in mm. be within the dimensions specified (not
applicable for ITK 312 and ITK 324).
Application
These separable tee shape connectors (bolted type) are designed to connect MPRXCX® FLEXISHIP® and MEPRXCX® FLEXISHIP®
cables to equipments (transformers, switchgear, motors, etc.).
Technical characteristics
• A thick conductive EPDM sheath provides a total safe to touch screen.
• Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Design
1. Conductive EPDM insert The screen break design
enables cable outer sheath
2. Conductive EPDM jacket testing without removing or
dismantling the connector.
3. Insulating EPDM layer
moulded between the insert and
the jacket
4. Type C interface
5. Conductor contact
7. Cable reducer
9. Clamping screw
76
Kit contents
The complete (K) 480 TB/G tee conector kit The kit also comprises silicone grease, field control
comprises the following components: mastic, installation rod, gloves, wipers, roll adhesive
tape, installation instructions and crimp chart.
Conductor
contact = 3 x (K)(M)(P)480 TB/G-W-X
TMBC-X connector kit
120 120(K)M-11-2
120.300-12-5
150 150(K)M-11-2
185 185(K)M-11-2
240 240(K)M-11-2
300 300(K)M-11-2
For use with For use in potentially For use with For applications This product can also This product can also
copper tape explosive atmospheres other cable types. outdoors and in be installed using a be installed using
screened cables. (for 12 kV max). Please contact our humid climate. stud, nut & washer. a 411 CA. Please
Order: Kit MT. Add -/ATEX to part representative. Order: +MWS. Please contact our contact our
number. representative. representative.
78
ELECTRICAL PARAMETERS FOR POWER CABLES
For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several
parameters as:
• permissible current carrying capacities
• voltage drop
• short circuit values.
These values are applicable for DC and AC with a nominal • mutual heating effect due to cables grouping
frequency of 50 Hz or 60Hz. For higher frequency, current • short time duty
ratings shall be calculated with appropriate method. • solar radiation
First, these values depend on the temperature class of the This catalogue gives only an extract of IEC 60092-352
cable, and mainly on the maximum service temperature standard that selected 2 methods for the determination of
suitable for the insulation compound. Nowadays, in current carrying capacities for continuous service. These
shipbuilding industry, 90°C rated cables are mostly installed methods are derived from experimental data and from
on board. IEC 60287 (Electric cables - Calculation of current rating).
A and B are coefficients, m and n are exponents according to cable type and method of installation.
This method allows for greater choice of use in different installation configurations (see IEC 60092-352 and/or IEC 60364-5-52).
A is a coefficients depending on the conductor temperature class, e.g. A=17 for MPRX and
MPRXCX cables.
The following table gives current carrying capacities in continous service 90°C rated cables for an ambient air temperature of
45°C.
Ambient temperature 35°C 40°C 45°C 50°C 55°C 60°C 65°C 70°C 75°C 80°C
Kt 1.10 1.05 1.00 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Current ratings are recommended as being applicable to both unarmoured and armoured cables laid in free air as a group of
4 bunched together. These ratings may be considered applicable, without correction factors for a group of maximum 6 cables
bunched together on cable trays, operating simultaneously at their full rated capacity, without free air circulation around them.
When, it is to be expected that air temperature around cables could be higher than 45°C (due to heat transfer or in compart-
ments where heat is produced) the current rating given in the table shall be reduced.
80
Correction factor for U.V. solar radiation
Nexans recommends shielding cables from direct solar exposition. For cables with black or grey sheath, in case of solar radiation,
a correction factors must be applied to the current carrying capacities given in the table:
• 0.8 for black colour of outer sheath
• 0.9 for light colour of outer sheath (e.g. light grey)
Cables with other colors are not intended for direct UV.
Voltage drop
Current carrying in an electrical link induces a voltage drop. This value is the difference between the measured voltages at both
ends of the link. In general, accpeted values (in percentage) are 3% for lighting and 5% for motors or other uses.
For a quick calculation, the following table gives the voltage drop for most of low voltage cables with XLPE (90°C temperature
class) and for various values of cos ϕ. Values are for a tri-phased system (3 or 4 conductor cable, or 3 single core cables).
These temperatures are depending on the insulation compound, e.g. for XLPE, initial temperature is 90°C (maximum operating
conductor temperature) and final max temperature is 250°C.
Short circuit current ratings are also depending on the duration of the short circuit before the setting off the electrical protection
(circuit breaker or fuse).
The following table gives values for cables insulated with XLPE, HEPR and HF90 compounds as MPRX®, MPRXCX®, MPRX® 331
and MPRXCX® 331.
82
Short circuit current ratings (A)
Cross sectional area (mm²) Time durtion (s)
0.1s 0.2s 0.5s 1s
1.0 453 320 202 143
1.5 680 480 304 215
2.5 1 133 800 506 358
4 1 810 1 280 810 572
6 2 720 1 920 1 210 860
10 4 520 3 200 2 020 1 430
16 7 250 5 100 3 240 2 290
25 11 300 7 950 5 050 3 570
35 15 800 11 200 7 070 5 000
50 22 600 16 000 10 100 7 150
70 31 600 22 300 14 100 10 000
95 43 300 30 600 19 300 13 700
120 54 100 38 200 24 200 17 100
150 67 700 47 800 30 200 21 400
185 83 500 59 000 37 300 26 400
240 108 000 76 700 48 500 34 300
300 135 000 96 000 60 600 42 900
For other short circuit, the maximum short circuit rating is calculated with the formula:
I sc = A/√t where
I sc is the short circuit rating during ”t” second.
t is the short circuit duration.
A is the short circuit rating for 1 second.
All these values are given in the following table for Nexans TX® and TCX® range with bare copper conductor.
Capacitance at 1 kHz
Individual screen (nF/km) 82 92
Capacitance at 1 kHz 2p 62 69
Collective screen (nF/km) 4p 52 56
7 p to 24 p 51 to 48 p 54 to 52 p
Permissible current carrying capacities is given for an ambient temperature of 45°C and for a maximum conductor temperature
of 90°C.
84
An other important parameter for these instrumentation cables could be the screen efficiency and the transfer impedance value
designated by Zt.
Nexans has studied screening efficiency for TX® and TCS® range. Curves (transfer impedance related to frequency) have been
established for various 7 pairs.
FF (kHz)
(kHz)
In order to reduce pulling and installation time, Nexans has When several cables are pulled together, talcum is recom-
designed a cable range which offers: mended to limit friction and abrasion between cables and to
• time saving on connexions by easy sheath and insulation ease the pulling process with better cables sliding.
stripping
Where cables have to be pulled perpendicularly to other
• reduced weight, diameter and volume cables already installed, it is advised to protect them to avoid
• e
asier drawing due to low friction coefficient of polyolefin abrasion damage.
outer sheath compound.
Cables have to be pulled with a slow and regular speed
Nexans decides to distinguish main cable circuits by different about 20 m/minute, and with a minimum outer temperature
outer sheath colours: of -15°C. It is always necessary, to store cables in warmed
• red for medium voltage cables from 1.8/3 kV up to premises at an ambient temperature of +10°C for 12 hours.
12/20 kV A longer period might be necessary for large drums.
If the cable link is pre-cut before pulling, the cable has to be To limit the stress (elongation/compression) on insulation and
correctly coiled to avoid any over twist. sheath materials when cable are bent, rules about minimum
internal bending radius (MBR) have to be respected:
Pre-cut cable ends, in waiting position before final installation
• in fixed installations
and connexion must be protected.
• during pulling and installation
All cable runs must be smooth and clean or covered with a
complementary protection to prevent any outer sheath Values for these MBR stated in IEC 60092-352 and
damage. IEC 61892-4 are given in the following table.
86
Numbers of conductors per phase Number of single core cables Recommended cable positionning
2 6 L1 L2 L3 L3 L2 L1 or L1 L2 L3 or L3 L2 L1
3 9 L1 L2 L3 or L2 L3 L1 or L3 L1 L2
L1 L2 L3 L3 L2 L1 or L3 L2 L1 L1 L2 L3
4 12 or L3 L1 L2 L3 or L2 L3 L1 L2
or L1 L2 L3 L1
All these bending radius values must be multiplied by 2, during pulling and installation of the cables.
Nexans recommends to protect cables which are sensitive to UV by UV-proof hoods installed over those. When cables are installed
in luminaries or lighting, specific protection of insulation and cables must be applied as required in IEC 60598.
Nexans provides a wide family of cables for ships and offshore platform focusing on innovation for improved fire
performance. Some developments ensure fire performance characteristics for the Nexans shipboard cables range as
flame and fire retardancy, smoke and fumes emission, fire resistance integrity and cable recycling after life time.
Nexans shipboard cables are fully withstanding the requirements of the following IEC standards:
The test is passed if the cable has self extinguished and the
burnt portion of the cable has not reached the top of the
sample
Flame Retardant
IEC 60332-1
88
FIRE RETARDANCY: IEC 60332-3
Test on bunced wires or cables
Cables, when installed, vertically or horizontally laid,
bunched on cable trays, in conduit or pipes, are potential
vectors for fire propagation.
25 (D) 0.5 20
• F or data cables,
Part 23 - procedure and requirement.
90
MEASUREMENT OF COMBUSTIION GASES: SMOKE DENSITY:
IEC 60754 PART 1 & 2 IEC 61034 (27 m3 chamber)
Part 1: this test permits the determination of the amount of In case of fire smoke emissions considerably reduce the
halogen gas emitted during the combustion of the different visibility on board.
polymeric compounds (insulation, filler, sheaths) taken from a
cable. Passenger evacuation has to be held in a very short time.
Therefore materials used in ships should not spread a lot of
Part 2: this test determinates the degree of acidity of gases by opaque smoke.
measuring pH and conductivity.
Nexans shipboard cables are designed to withstand the
requirements of IEC 61034 based on the 27 m3 test
developed by the London Transport Executive Research
Laboratory.
+
Measurements test equipment of combustion
gases according to the IEC 60754-1/60754-2
TYPE APPROVALS:
Nexans shipboard cables are approved by certification
bodies in accordance with their rules and regulations for
classification of ships:
92
SYMBOLS
Temperature
Admissible ambient temperature for continuous duty operation..................................................................
Weather
Resistance to severe weather conditions...............................................................................................
Fire Performances
Fire performance according to:
• «Flame retardant».......................................................................................................................
IEC 60332-1
• «Fire retardant»..........................................................................................................................
IEC 60332-3-22 (for category A)
Halogen-free ..............................................................................................................
Smoke-Corrosivity-Toxicity
Smoke density, gases corrosivity and toxicity............................................................
Flexibility
Class 5 conductors..........................................................................................................................
LIFTING
When lifting with sling ropes, these must hang in parallel to
avoid pressure to the flanges. Always use yoke.
94
DRUM HANDLING GUIDE
Unreeling, temperature and end seal
UNWINDING/UNREELING
The cable drum must be placed on a suitable cable jack or a stand etc. When
unwinding/unreeling the cable it is important to maintain a steady speed, and
without a sudden start and stop. It is important never to pull the cable over the flan-
ge. The cable must be unreeled in the opposite direction of the indicated arrow
on the flenge. Use of swivel when unreeling cables is discouraged.