As per design As per Architect Capacity in Total Capaity in SL No Location Exhaust cutout area Area in Sqm No of Fans Louvered area inputs - Louvered Remarks CFM CFM required area available 1.5 Sq.m. cut out reduced B1E-1 6.96 1.0 60,000 60,000 7.4 7.5 which architect Provided 1 earlier Louvered area founds to be in B1E-2 2 6.96 1.0 60,000 60,000 7.4 7.5 order
1.0 60,000 60,000 4.0 Sq.m. cut out reduced
B1E-3 11.30 28.5 26.0 which architect provided 3 earlier 4 Basement-1 2.0 85,000 170,000 5 1.0 60,000 60,000 4.0 Sq.m. cut out reduced B1E-4 11.30 28.5 26.0 which architect provided 2.0 85,000 170,000 earlier 6 7 3.0 65,000 195,000 Louvered area founds to be in B1E-5 33.10 45.2 45.6 8 2.0 85,000 170,000 order
B2E-1 11.30 18.0 17.9 2 1.0 85,000 85,000 order 3 2.0 60,000 120,000 Louvered area founds to be in B2E-2 18.70 25.4 26.0 4 1.0 85,000 85,000 order 5 2.0 60,000 120,000 3.0 Sq.m. cut out reduced B2E-3 11.00 21.1 21.0 which architect provided 6 1.0 50,000 50,000 earlier B2E-4 4.13 2.0 65,000 130,000 16.1 Louvered area founds to be in 7 Basement-2 16 order As per discussion we have B2E-5 13.40 - - - - - requested slab cutout at 8 lowerbasement only B2E-6 9.80 2.0 80,000 160,000 19.8 Louvered area founds to be in 9 20.5 order 60,000 60,000 Louvered area founds to be in 10 B2E-7 12.80 1 17.3 17.5 order 11 1 80,000 80,000 Project :Mantri Arena Mall Basement Fresh air Louvered area requirements As per design As per Architect Capacity in Total Capaity in SL No Location Fresh Air cutout area Area in Sqm No of Fans Louvered area inputs - Louvered Remarks CFM CFM required area available Louvered area founds to be in B1F-1 5.70 1.0 35,000 35,000 4.3 4.15 1 order Louvered area founds to be in B1F-2 45,000 16.7 16.75 2 20.40 3.0 135,000 order Basement-1 Louvered area founds to be in B1F-3 23.40 4.0 43,000 172,000 21.3 21.4 order 3 Louvered area founds to be in 4 B1F-4 22.80 3.0 67,000 201,000 24.9 25.0 order
Louvered area founds to be in
B2F-1 10.90 2.0 50,000 100,000 12.4 12.3 1 order Louvered area founds to be in B2F-2 21.20 62,000 186,000 23.0 23.0 2 3.0 order Basement-2 Louvered area founds to be in B2F-3 9.30 70,000 70,000 8.7 8.8 3 1.0 order Shaft required up to B2F-4 5.30 1.0 85,000 85,000 10.5 11.5 4 basement-2 ceiling