Project:-2 X 48MW Dikchu HEP

Client:-HIPL

Design Calculation for 75 MVA G.S.U Transformer

A. Deluge valve calculation for Generator Transformer


The Calculation for water requirement of Generator Transformer is carried out based on
Clause No.3.2 of TAC Publication of "Rules for water spray system"-System Design of
Transformer Protection
Design Standard:-TAC Rules for Watre Spray System
Sizes
1.Transformer Body
L= 9m
W= 6.5 m ( size of transformer has been taken from alstom d
H= 5.1 m
Surface area of the body 2{(LxW)+(WxH)+(HxL)}
Area 275.1

1.Radiator Body
L= 5m
W= 8m ( size of transformer has been taken from alstom d
H= 5m
Surface area of the body 2{(LxW)+(WxH)+(HxL)}
Area 210

HV Cable Box
L= 2.7 m
W= 2m ( size of transformer has been taken from alstom d
H= 1.5 m
Surface area of the body 2{(LxW)+(WxH)+(HxL)}
Area 24.9

LV Cable Box
L= 3.1 m
W= 0.5 m ( size of transformer has been taken from alstom d
H= 0.5 m
Surface area of the body 2{(LxW)+(WxH)+(HxL)}
Area 6.7

3. Conservator Tank
D= 1.5 m
L= 5.3 m
Surface area of Conservator Tank
= 2(πxD2/4)+(πxDxL)
28.5099533313
Surface area of the body
= 2{(LxW)+(WxH)+(HxL)}
= 275.1 Sq.m
Surface area of the radiator
= 2{(LxW)+(WxH)+(HxL)}xNo.of radiator
210 Sq.m

Surface area of Conservator Tank


= 2(πxD2/4)+(πxDxL)
= 28.4972917353 Sq.m
Surface area of the radiator
= 2{(LxW)+(WxH)+(HxL)}xNo.of radiator
#VALUE! Sq.m

Total Surface Area for the Transformer


= 513.60 Sq.m
Misc. area to be protected 10% considered = 51.36 Sq.m
Total surface area to be protected= 564.96 Sq.m

Total surface area to be protected= 564.96


Total water required @ 10.2 LPM/M2 = 5762.56 LPM
Flow Requriement for one Transformer 345.75 m3/hr

Deluge Valve proposed is 150mm dia having flow rate of 50 to 225 m3/hr (833.33 to 3750
LPM)
B.Sizing of Gravity Tank:
Requirement I :

As per Clause No. 7.4.1.4.6 of TAC Fire Protection manual -"Where transformer are protected
by high velocity water spray system tapped from hydrant system,water requirement of the
spray system worked out as above shall then be loaded by 1750 LPM (105 Cum/Hr) for
supplementry hose stream protection.If the total water requirement for spray protection and
hose stream protection worked out as above exceeds the requirements of the hydrant service
as per Table 2, the pumping capacity shall be equivalent to the former."
The total water requirement shall be as per TAC clause
Water requirement of the spray system (Larget deluge valve) : 345.75 m3/hr
As per TAC Supplementry hose stream protection : 105 m3/hr
Total water requirement for the fire fighting system : 450.75 m3/hr

As per TAC the capacity of static storage /Gravity tank for light hazard occupancies shall not
be less than the aggregate pumping capacity.
Size of Gravity Tank : 450.75 m3
As per NFPA 851 Cl.6.2.2 for 2 hours 901.507393592
Assuming 10m x
10m and depth
Dead Volume 20 m3 200mm
Total volume 921.507393592 m3
As per NFPA 851
Time for filling OHT 8 hr clause no. 6.2.3.4

Capacity of pump 115.188424199 m3/hr

Selected pump capacity 60 m3/hr

Requirement II :
As Per Clause No.3.2.2 of TAC Manual (Rules for water spray system) the effective exclusive
capacity of the reservoir / tank shall not be less than 40 minutes run for aggregate pumping
capacity for the spray system.
Min water required for the for spray system for 40 min : = 230.5025 m3
As per TAC Supplementry hose stream protection : = 70 m3
Total water requirement = 300.5025 m3
As per TAC the capacity of static storage /Gravity tank for light hazard occupancies shall not
be less than the aggregate pumping capacity.
Size of Gravity Tank : 300.502464531 m3

Size of Gravity tank taken 224

OHT filling line


Pump Capacity 60 m3/hr
Maximum velocity in pipe (V) 2.5 m/s
Pipe size 92.1317731924 mm
Selected pipe size 100 NB

Deluge valve for CAT


Sl.No. Description Unit Value
A Overhead tank (OHT) filling line
1 Pump Capacity (Q) m^3/hr. 55

2 Maximum velocity in pipe (V) m/sec. 2.5


3 Calculated pipe size diameter (d) mm 88.22

4 Selected pipe size NB 100


B Fire Fighting water header from OHT to power house

1 Discharge through pipe (Q) m^3/hr. 194.82

2 Maximum velocity in pipe (V) m/sec. 2.5


3 Calculated pipe size diameter (d) mm 166

4 Selected pipe size NB 200

Deluge Valve Calculation for Cable Spreading Area


SI.NO Description Unit Value

1 Width of the Cable Tray


m 3
2 Length of the cable Tray m 181
3 Exposed Area of Cable Trays m^2 543
Total Exposed Area of Cable Tray
considering 10% margin in Cable m^3 553
4 spreading Area

5 Water Requried for Cable Trays LPM 6746.6

6 Water Requriement for cable Trays m^3/hr 404.796


7 Selected Deluge Valve 239.3277
Selected Deluge Valve NB 250
Remark

As calculated above in
clause no. 8.3

d = Sqrt
(4*Q/V/3600/3.141)

power house

As calculated above in sl.


no. A-3 of clause no. 8.2

d = Sqrt
(4*Q/V/3600/3.141)

e Spreading Area
Renmark

As per the Proposed cable


Tray Layout

12.2 LPM per square meter


of Exposed area of Cable
Tray as per Tac

d = Sqrt (4*Q/V/3600/3.141)
Sl.No. Description Unit Value Remark
1 Width of the cable tray m As per proposed
1.5 cable tray layout
2 Length of the 1.5 m wide m
cable trays 20
3 Exposed area of Cable trays m
30
4 Width of the cable tray m As per proposed
cable tray layout
0.75
5 Length of the 0.75 m wide m
cable trays
25
6 Exposed area of Cable trays m
18.75
7 Total exposed area of Cable m^2 48.75
tray in cable spreading area

8 Total exposed area of Cable m^2 53.63


tray considering 10% margin
in cable spreading area

9 Water requirement for cable LPM 654.23 12.2 LPM per


trays square meter of
exposed area of
cable tray as per
TAC

10 Water requirement for cable m^3/hr. 39.25


trays
11 Selected Deluge Valve NB 80 As per clause no.
4.4.8.2 Of spray
system of TAC
manual