You are on page 1of 6

2019 6th International Advanced Research Workshop on Transformers (ARWtr) – Cordoba - Spain, (6)7-9 October 2019

On-Site Dry-type Power Transformer Condition


Assessment based on Partial Discharge Activity
C. Engelen and V. Lozano, OMICRON electronics

 Abstract -- As part of the energy transition and the transformers a DGA is not applicable. Therefore, partial
associated development of renewable energies, the number of discharge diagnosis by means of a single-phase induced
installed dry-type transformers is increasing on the medium- voltage test is discussed below. In contrast to a three-phase
voltage power grid. Therefore, the paper at hand focuses on on-
excitation in the factory, the transformer under test is
site condition assessment of dry-type power transformers which
are often installed in wind turbine nacelles, industrial sites as energized with a single-phase source. Thus, the power intake
well as in marine and civil applications. The assessment of the is reduced, and a more compact and lightweight source can
insulation condition is based on an induced voltage test in be used on-site. This way, measurements in confined spaces
combination with a partial discharge measurement. In contrast can be conducted rendering a bulky trailer mounted source
to laboratory tests under controlled conditions, an increased unnecessary. A portable test system of 30 kg [2] is used to
level of interference from rotating machinery, power electronics
energize transformers with power ratings up to 4 – 5 MVA.
and other consumers is to be expected on site. The approach of
energizing transformers of power ratings up to 15 - 20 MVA For power ratings up 15 – 20 MVA to two additional
with a portable, scalable single-phase voltage source is amplifiers can be installed. Combining this approach with a
presented. Due to the single-phase injection the power intake is PD measurement offers the possibility to analyse the
reduced, and an individual evaluation of each coil becomes insulation system of each coil individually, resulting in a
possible. Practical examples show how partial discharge signals powerful tool for reliable on-site insulation diagnostics of
can be separated from these interferences using a synchronous medium-voltage transformers.
multi-frequency PD measurement.

Index Terms-- Condition Assessment, Dry-type transformer, II. TRANSFORMER DIAGNOSIS


Partial Discharge, 3CFRD, Electrical Insulation, Medium The main difference between oil-filled and dry-type
Voltage, Insulation testing transformers is the fluid insulation system. Instead of mineral
oil which acts both as insulating and cooling medium, in
most cases the windings of dry-type transformers are casted
I. INTRODUCTION in epoxy resin. Thus, the coils are natural air cooled.

T HE use of dry-type transformers has proved to be


successful in a range of applications. Such equipment is
often used in medium-voltage power grids in industrial
Switching on fans allows the dry-type transformer to operate
in a short-time overload condition. Besides, the mechanical
structure has to meet high requirements to withstand short-
plants and in the marine and civil sectors, such as in subway circuit currents [3].
networks. Deciding factors for the use of dry-type Like for oil-filled transformers a variety of tests are in
transformers include low-maintenance operation and reduced place to check these characteristics after the assembly in the
fire risk. The latter can be of particular significance for factory. Common electrical measurements such as no-load
installation in building complexes and tunnels. Furthermore, loss, winding resistance and short-circuit impedance
measurements are performed. Besides, applied and induced
the absence of mineral oil as an insulating medium eliminates
voltage withstand tests are carried out to verify the dielectric
the need for oil sumps. This makes dry-type transformers
strength of the insulation system. Finally, after pre-stressing
particularly advantageous for use in wind turbines, as they
the insulation during the aforementioned tests, a partial
are often installed in areas with high groundwater protection discharge measurement is performed to detect localized
requirements or at sea. insulation defects [4].
In the context of wind turbines, the transformers, which
are connected directly to the turbine generator, can be III. PARTIAL DISCHARGE MEASUREMENT
considered as generator step-up units (GSU). Diagnostic
Partial discharge impulses are localized dielectric
measurements and the condition assessments of these units
breakdowns that only partially bridges the insulation system
are of corresponding significance. In the following, the
[5]. Due to the local energy transport the solid insulation
applicability of partial discharge (PD) measurements for the system of a dry-type transformer can degenerate over time.
condition assessment of dry-type transformers with power Thus, affecting the dielectric strength and, in the worst case,
ratings up to 15 – 20 MVA is discussed and illustrated with causing an outage of the unit due to an insulation failure. PD
case studies. Typical voltage ratings are up to 30 kV on the measurements are a powerful tool to detect insulation defects
HV side and up to 690 V on the LV side. For oil-filled and irregularities. Compared to integral insulation
transformers, a dissolved gas analysis (DGA) provides initial diagnostics such as a dissipation factor measurement, local
indications about potential internal faults, such as partial imperfections can be identified. Therefore, this measurement
discharges or local overheating [1]. For dry-type is part of the factory acceptance routine testing procedure for
every new dry-type transformer [4]. In addition, on-site
C. Engelen is with OMICRON electronics Germany, 91054 Erlangen measurements of the transformer can be realized. For this
Germany, (e-mail: christoph.engelen@omicronenergy.com). purpose, both offline and online partial discharge diagnostics
V. Lozano is with OMICRON Technologies España, 28109 Madrid
Spain (e-mail: victor.lozano@omicronenergy.com).

978-84-09-11168-8 /19 © 2019 Red iNtransf 93


2019 6th International Advanced Research Workshop on Transformers (ARWtr) – Cordoba - Spain, (6)7-9 October 2019

are suitable. In the following, the main characteristics of the reduced compared to a three-phase excitation. Fig. 3 depicts
FAT and the on-site, offline PD diagnostics are discussed. the power intake in “kVA” at nominal voltage of three
distribution transformers with power ratings between
A. Factory Acceptance Test
800 kVA and 1600 kVA. It can be seen that in case of a
After finalizing all voltage withstand tests during the single-phase excitation the power intake is reduced by
factory acceptance test (FAT), the partial discharge approx. 50 %.
measurement is carried out on each individual unit. For a
three-phase transformer a three-phase voltage source is
connected to the low-voltage winding to energize the device
under test. On the high-voltage winding a coupling capacitor
and a measurement impedance (“coupling device”, “CD”)
are connected to each phase terminal. A PD measurement
system is then installed which is switched between the phases
during the test cycle to record the PD activity. Alternatively,
a three-channel PD measurement system can be used to
simultaneously analyse all three phases. Using the latter
approach, identifying possible cross-talk between the phases
and separating multiple PD sources can be realized. A
schematic overview of the common measurement setup is
given in Fig. 1.
Fig. 3. Comparison of power intake between a three-phase (blue) and a
single-phase (green) excitation.

Furthermore, the inductive and capacitive components of


the transformer under test form a resonant test circuit. By
tuning the frequency of the test voltage to the resonant point
Fig. 1. FAT measurement setup for induced voltage test according to [4]. a maximum impedance of the test setup can be achieved. The
change of impedance and phase angle in dependence of the
A pre-defined test cycle is then carried out. First, a pre- frequency is shown exemplary in Fig. 4. The frequency is
stress voltage of 1.8-times the rated line-to-line voltage (Ur) changed between 50 Hz and 400 Hz. In this case a suitable
is applied for 30 seconds. During this interval, possibly operation point is found at approx. 120 Hz. While the
active partial discharges are not considered for the impedance is at its maximum the phase angle approaches 0°
transformer assessment. Afterwards, the test voltage is which means that only the active power intake of the
reduced to 1.3-times the rated line-to-line voltage and held transformer has to be covered by the test system. Thus, the
constant for 180 seconds. In this second part of the test cycle excitation current and therefore the power intake is further
no partial discharges above 10 pC are allowed for the reduced allowing the operator to energize transformers with
transformer to pass the test. power ratings of up to 4 – 5 MVA.

Fig. 2. FAT test cycle for PD measurement according [4].


Fig. 4. Frequency dependency of the impedance of the device under test.

B. On-site Testing In the following the setup for a single-phase excitation is


The on-site partial discharge measurement can be a discussed on the example of a YNd11 transformer, Fig. 5.
powerful tool to investigate possible insulation defects of a The complete test cycle consists of three consecutive
dry-type transformer. In contrast to a factory acceptance test, measurements. This means each phase of the transformer is
certain limitations are in place when testing on-site. Often the separately energized to facilitate the evaluation of each
device under test is installed in a confined space which single coil. As a first step phase “A” on the HV side shall be
requires a portable test system. In addition, the available measured. Therefore, the voltage source is connected to the
testing power is limited to a conventional power supply of a corresponding terminals on the low-voltage side. In addition,
wall socket. To account for both limitations a different a coupling capacitor and a partial discharge system are
approach compared to the FAT is chosen. Instead of using a installed at the HV terminal of phase “A”.
three-phase voltage source a single-phase test system is used One major difference between a three-phase and a single-
to excite the transformer. This way the apparent power phase excitation is the voltage distribution across the
needed to energize the transformer can be significantly transformer windings. Energizing only one coil will induce a

978-84-09-11168-8 /19 © 2019 Red iNtransf 94


2019 6th International Advanced Research Workshop on Transformers (ARWtr) – Cordoba - Spain, (6)7-9 October 2019

voltage across the remaining two windings of the transformer


due to the magnetic coupling. However, the magnetic flux
distribution in the core limbs depends on the transformer
design and the voltage frequency [3]. Thus, some uncertainty
is introduced regarding the electrical stress of the de-
energized windings. By applying a short-circuit to the unused
terminals of the star-winding an equal magnetic flux
distribution is achieved in those two core limbs. This way the
electrical stress on all three coils is clearly defined. Fig. 5
depicts that only phase “A” is stressed with the full test
voltage Up while on the other two phases only a voltage of Fig. 6. Schematic 3CFRD star-diagram.
0.5 * Up is induced [6]. Consequently, each of the three In the following the application of the 3CFRD method to
phases can be energized and checked for partial discharge an actual on-site measurement is shown. Fig. 7 depicts the
activity. The clearly defined voltage distribution can be star-diagram with two distinct clusters. The centre
utilized to cross-check the PD results and draw conclusions frequencies are set to 160 kHz, 1 MHz and 2 MHz with a
regarding the origin and the inception voltage of the PD bandwidth of 160 kHz. Different filter settings have to be
source. tested on-site to obtain an optimal separation. Like the PRPD
diagrams, the amount of impulses in a cluster is represented
by the colour coding. To make full use of the 3CFRD
method, the cluster representation is used to separate noise
and possibly individual PD sources. By selecting an area in
the star diagram, as marked in red in Fig. 7, a back
transformation to the PRPD is performed. This way each
cluster can be selected and evaluated individually.

Fig. 5. Setup for on-site single-phase induced voltage test.

IV. ELECTROMAGNETIC INTERFERENCES


In contrast to a factory acceptance test during which the
partial discharge measurement is carried out in a shielded
room, on-site PD measurements can be heavily affected by
electromagnetic interferences (“noise”). In most cases the
root cause of the interferences, such as power electronics,
cannot be removed or switched off during the measurement.
If there are no means to eliminate the noise, a common way
to cope with these external signals, is tuning the
measurement frequency in way that the influence is
minimized. Recommendations regarding appropriate
frequency ranges can be found in [5]. However, a suitable
frequency range always depends on the individual frequency
characteristics of the setup and the device under test. Fig. 7. Star-diagram with noise (middle) and a PD source (marked red).
Therefore, care should be taken to avoid selecting a
frequency range in which the signal-to-noise ratio of the For the example at hand the corresponding unfiltered
partial discharge impulses is minimized. PRPD is depicted in Fig. 8-a). A clear PD activity can be
In the following, the three-centre frequency relation observed which is to some extent overlapped with a high
diagram method (3CFRD) is introduced as a measure to noise floor. When activating the 3CFRD functionality all
separate external noise and PD signals. The following measured impulses are automatically used to create the
technique of three band-pass filters is used to simultaneously aforementioned star-diagram. It is worth mentioning that
record each impulse entering the measurement system. only those impulses are depicted which are picked up at all
Depending on the frequency spectrum of the impulse each three centre frequencies. After selecting the corresponding
filter response will result in a different charge value. The cluster in the 3CFRD star-diagram, a back transformation to
charge values are plotted as vectors in a star-diagram in the PRPD is performed. Since now only those impulses are
which each axis is associated with one band-pass filter, Fig. shown which belong to the partial discharge source of
6. The length of each vector corresponds to the magnitude of
interest, a much clearer pattern is obtained, Fig. 8-b). In this
the charge. By geometrically adding all three vectors a single case a symmetric pattern in both halfwaves of the voltage
point in the diagram is obtained. Each impulse with a similar signal is observed. Consequently, each cluster in the star-
frequency spectrum will add another point in the same area diagram can be selected and analysed. Eventually, an
of the diagram. Thus, each PD source, including external individual evaluation of each PD source without any negative
noise, will generate an individual cluster in the star-diagram influences such as a high noise floor or external disturbances
[7]. is made possible.

978-84-09-11168-8 /19 © 2019 Red iNtransf 95


2019 6th International Advanced Research Workshop on Transformers (ARWtr) – Cordoba - Spain, (6)7-9 October 2019

evaluation reveals typical signs of internal discharges in a


solid insulation system [8]-[10]. The inception voltage is
determined to be 26 kV while the extinction voltage is
around 20 kV.

Fig. 10. PRPD obtained during single-phase excitation on phase U.

Close to the voltage minimum a single PD cluster is


visible. Typically, impulses only recorded around 270° of the
voltage phase are related to discharges in air, also called
“Corona” [9]. Since these discharges occur in air and not in
the solid insulation system, they are regarded as external
noise and are not considered during the evaluation. To
Fig. 8. a) Original PRPD showing all picked up impulses, b) filtered PRPD separate the PD signals from all external influences, the
showing only impulses of the PD source.
3CFRD method is applied. As discussed previously, a
simultaneous measurement using three band-pass filters is
V. CASE STUDIES performed to build the corresponding star-diagram, Fig. 11.
A. 27.5 kV / 10.5 kV / 1.6 MVA Transformer The centre frequencies are set to 160 kHz, 2 MHz and 4
During a routine measurement of a 27.5 kV / 10.5 kV / MHz with a bandwidth of 160 kHz. Several clusters are
1.6 MVA / YNy0 transformer a PD measurement is formed, each of which representing an independent PD
requested. A single-phase induced voltage test with source. Marked in red are the two clusters identified as the
combined partial discharge measurement is carried out. Corona discharges and the internal PD source.
Therefore, a variable voltage source [2] is connected to the
low-voltage side of the transformer. As a PD measurement
system, a MPD600 [11] from OMICRON is installed on the
HV side. Fig. 9 depicts the schematic of the measurement
setup. Due to the short-circuit on the low voltage terminals a
defined voltage distribution across the core limbs is
achieved. Thus, only the phase under test is stressed with the
full test voltage. Consequently, each phase is tested one after
the other.

Fig. 11. 3CFRD star-diagram obtained during the PD measurement.


Marked in red are the clusters for internal PD and Corona discharges.

After selecting the areas of interest, a back transformation


Fig. 9. Measurement setup for the excitation of a YNy0 transformer. is performed to show the PRPD patterns of the marked
clusters. The lowest cluster in Fig. 11 is identified as the
The test cycle of the FAT, as shown in Fig. 2, remains internal PD source. Typical signs such as the symmetrical
unchanged in terms of testing time. However, a reduced pre- pattern distribution for the positive and the negative
stress voltage of 1.2 x Un (33 kV) and a test voltage of halfwave, as well as the occurrence in the 1st and 3rd quadrant
1.0 x Un (27.5 kV) are agreed upon with the operator. of the sine wave can be observed. In addition, the “bended”
The voltage amplitude is reduced to avoid excessive structures, following the slope of the sine wave can be seen
electrical stress on the insulation system. On the other hand, as another indicator for a gaseous void inside an insulating
the test time of 3 minutes is kept to account for a possible material [8] – [10], Fig. 12.
delayed inception of the PD activity. The test frequency was Due to the low inception voltage and the classification as
set to 68 Hz which was found to be a resonant point. It is internal PD, the criticality of the insulation defect was rated
observed that on phase U considerable discharges are as high.
recorded up to 800 pC, Fig. 10. Besides, the pattern

978-84-09-11168-8 /19 © 2019 Red iNtransf 96


2019 6th International Advanced Research Workshop on Transformers (ARWtr) – Cordoba - Spain, (6)7-9 October 2019

adequate signal-to-noise ratio. This way a measurement


range with a noise floor of 5 – 10 pC is achieved.

Fig. 12. PRPD of the isolated internal PD. Fig. 14. Frequency spectrum of noise and calibrator impulse, filter
frequencies marked in red.
B. 19 kV / 3 kV / 9.5 MVA Transformer
While there are no signs of PD activity on phase A, phase
The second case study deals with the on-site testing of a
B clearly shows the inception of partial discharges at 15 kV.
19 kV / 9.5 MVA / Dyn11 dry-type transformer. The unit is
After visual inspection of the coil it was is found that the top
installed in a cavern power plant and part of the excitation
part of the winding body is polluted with dirt. Since a
system of a 400 MVA asynchronous generator. As one sister
comprehensive cleaning of the winding surface is not
transformer showed PD activity the operator decided to
feasible, it is decided to change the setup of the
check all remaining units for partial discharges. Since the
measurement. While the excitation of the transformer
transformers are all installed in the cavern, it became
remains unchanged, one side of the tested HV winding is
necessary to perform the requested measurements with a
connected directly to ground. First the coupling capacitor
portable test system. The single-phase excitation of the
stays connected to the terminal on top of the winding where
transformer is realized by using two synchronized test
the pollution is the heaviest, Fig. 15-a). Afterwards, the
systems [2] to provide the needed power. In addition, a 0.4
connection of the coupling capacitor and the ground
kV / 3 kV transformer stepped up the output voltage U of the
connection are exchanged. This way the main insulation of
test system to the LV rating of the transformer under test.
the winding is electrically stressed in the same way while
The complete connection diagram can be seen in Fig. 13. As
there is no electrical stress on the terminal next to the
a PD measurement system, a MPD600 [11] from OMICRON
polluted winding surface, Fig. 15-b).
is installed on the HV.

Fig. 13. Single-phase measurement setup including step-up transformer.

The test cycle is again derived from the one proposed by


the FAT. In this case a pre-stress voltage of 1.3 x Un (25 kV)
and a test voltage of 1.0 x Un (19 kV) are agreed upon.
Due to excessive electromagnetic interferences, typical
filter frequencies for the PD measurement are not applicable. Fig. 15. Polluted side on a) high-voltage and b) on ground.
Therefore, it is decided to select a narrow-band filter with a
bandwidth of 9 kHz. On the one hand a narrow-band filter is Using the first setup, again the partial discharge activity is
very selective and can thus be used to select a frequency observed. In this case discharge levels of up to 80 pC are
range with minimum interferences. On the other hand, if the recorded, Fig. 16-a). In contrast to this, the PD measurement
frequency spectrum of a PD impulse shows a local minimum using the second setup does not show any PD activity above
at the selected frequency range, the signal-to-noise ratio can the recorded noise floor of 3 pC, Fig. 16-b). The evaluation
be worse compared to a wideband-filter. This possible of the 3CFRD star-diagram is used to make sure that no
disadvantage is countered by using the above described additional PD sources are hidden in the noise floor. In this
3CFRD method. Three narrow-band filters with different case the 3CFRD method can be used as inverse filter. The
centre frequencies are selected to minimize the risk of noise cluster is selected and all impulses except for the noise
measuring at a local minimum of the frequency spectrum. In are shown. This way it is made sure that no overlapping of
this case the centre frequencies are set to PD signals and noise floor is taking place. Since the
375 kHz / 756 kHz / 3900 kHz. In addition, the frequency electrical stress on the main insulation is the same for both
spectrum of the ambient electromagnetic noise and the setups, it is concluded that the origin of the partial discharges
spectrum of the calibrator impulse have been recorded. Fig. are surface discharges along the polluted surface of the
14 shows that the signal strength of the calibrator impulse is winding body. In addition, the comparison of the results with
well above the noise level up to a measurement frequency of well-known patterns from literature indicate surface
approximately 10 MHz. The red bars indicate the positions discharges [8]-[10].
of the three narrow-band filters. All three of them show an

978-84-09-11168-8 /19 © 2019 Red iNtransf 97


2019 6th International Advanced Research Workshop on Transformers (ARWtr) – Cordoba - Spain, (6)7-9 October 2019

The PD activity of phase V is rated with a low criticality


since cleaning the winding surface should eliminate the
source of the discharges. On the other hand, the discharges
observed on phase W are rated as critical as they are
occurring inside the main insulation even below nominal
voltage.

VI. CONCLUSION
The article at hand focuses on the insulation assessment of
dry-type medium voltage transformers. A comparison is
drawn between the three-phase induced voltage test of the
factory acceptance test and a single-phase approach for on-
site testing purposes. Due to expected interferences, the
3CFRD-method is introduced. This synchronous multi-
frequency measurement allows the operator to separate
electromagnetic noise from PD signals. Besides, individual
PD sources can be distinguished and analysed independently.
Two case studies are presented which show that a single-
phase induced voltage test on three-phase transformers can
be utilized to identify insulation defects. Due to a defined
voltage distribution, each coil can be examined individually.
Finally, all obtained information during the PD measurement
Fig. 16. PRPD for polluted side on a) high voltage and b) on ground.
such as the type of the PD source and the inception voltage
are factored in the evaluation of the criticality of the defect.
Finally, phase C is energized and checked for any PD
activity. Again, partial discharges occur below nominal
voltage, at 14 kV, in both haft-waves of the test voltage. VII. REFERENCES
Discharge levels of up to 800 pC are recorded. The pattern [1] Mineral oil-filled electrical equipment in service - Guidance on the
interpretation of dissolved and free gases analysis, IEC 60599,
evaluation shows comparable results compared to phase V, Sept. 2015.
Fig. 17-a). However, the symmetrical patterns in both half- [2] CPC100 – Technical Data Sheet, OMICRON electronics, 2016.
waves show a tendency to follow the shape of the voltage [3] Martin J. Heathcote, "J&P Transformer Book", 13th edition, Elsevier
sine-wave. Typically, those characteristics point towards Ltd., 2007.
[4] Power transformers – Part 11: Dry-type transformers, IEC 60076-
internal discharges in the solid insulation system [8]-[10]. 11:2004, Jun. 2005.
Again, the same approach as discussed above is applied, Fig. [5] High-voltage test techniques – Partial discharge measurements,
15. In contrast to the previous phase, changing the IEC 60270, Ed. 3.1, Nov. 2015.
connection setup does not have any influence on the partial [6] A. Carlsson, F. Wegschneider, G. Schemel, J. Fuhr, "Testing of power
discharge activity, Fig. 17-b). As the voltage stress across the transformers and shunt reactors", ABB, 2nd ed., Chapter 8.5.4,
May 2010.
turn-to-turn insulation of the winding remains unchanged this [7] M. Krüger, A. Kraetge, K. Rethmeier, “Improved Partial Discharge
emphasizes the assumption that PD impulses are caused by Measurements by Real-time Impulse Waveform Analysis”, CIGRÉ
gaseous voids inside the main insulation. Workshop on Power Transformers, Iguacú, Apr. 2010.
[8] Partial Discharges in Transformers – Working Group D1.29,
CIGRÉ, Brochure 676, Feb. 2017.
[9] Recognition of Discharges – Working Group 21.03, CIGRÉ, 1969
[10] J. Fuhr, "Procedure for Identification and Localization of Dangerous
PD Sources in Power Transformers", IEEE Transactions on
Dielectrics and Electrical Insulation, Vol. 12, No. 5, Oct. 2005.
[11] MPD 600 – Technical Data Sheet, OMICRON electronics, 2015.

VIII. BIOGRAPHIES

Christoph Engelen was born in Aachen, Germany, in 1989. He received


his B.Sc. and M.Sc. in electrical engineering from RWTH Aachen,
Germany in 2011 and 2013, respectively. In 2014 he joined OMICRON
electronics as application engineer in the field of power transformer and
rotating machine diagnostics. Since 2017 he focuses as product manager on
medium voltage transformer diagnostics.

Victor Lozano was born in Madrid, Spain, in 1976. He received his high
technical degree in electronic product development in 1999. He was
working for 15 years in Unitronic electric as technician in the calibration
laboratory and specialized in Power transformers and rotating machines
testing. In 2014 he joined OMICRON Technologies España as Sales &
Application Engineer. He is concerned with sales, technical support and
training regarding substation assets and rotating machines diagnostics.

Fig. 17. PRPD for top of the winding on a) high voltage and b) on ground.

978-84-09-11168-8 /19 © 2019 Red iNtransf 98

You might also like