Guide
TH6220D
Programmable Thermostat
Product Application Table of contents
This thermostat provides electronic control of 24 VAC single-stage and multi-stage Installation Appendices
heating and cooling systems, or 750 mV heating systems. Pre-installation checklist ................2 Quick reference to controls..........15
Wallplate installation ......................3 Quick reference to display............15
System Types Power Options Wiring..............................................4 Battery replacement......................15
Wiring diagrams ..............................5 In case of difficulty ......................16
(up to 2 heat/2 cool) • Battery power only Power options ..............................10 Accessories/replacement parts ....17
• Gas, oil, or electric heat with air • Common wire only Thermostat mounting ..................10 Specifications ................................17
conditioning
• Common wire with battery backup Setup and testing
• Warm air, hot water, high-efficiency Installer setup................................11
furnaces, heat pumps, steam, gravity Installer system test ......................13
Changeover Options
• Heat only — two-wire systems, Explanation of features ................14
• Selectable manual or
power to open and close zone
auto-changeover modes
valves (Series 20), and normally-
open zone valves
System Settings
• Heat only with fan
• Heat, Off, Cool,Auto, Em Heat Installation tips
• Cool only
• 750 mV heating systems Install the thermostat about 5 feet (1.5m) above the floor in an area
Fan Settings with good air circulation at average temperature.
• Auto, On
• Check the ratings in this booklet to verify that this product is suitable for your
application (see page 17).
NO
• Always test for proper operation after installation (see page 13).
• Check the ratings in this booklet to verify that this product is suitable for your
application (see page 17).
NO
• Always test for proper operation after installation (see page 13).
Quick
4 Drill holes at marked positions as
FocusPRO™ TH6220D reference Operating manual shown below, then tap in supplied
programmable thermostat card wall anchors.
(wallplate attached to back)
Insert quick reference card 5 Place wallplate over anchors, insert
and tighten mounting screws.
2 3
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Quick
4 Drill holes at marked positions as
FocusPRO™ TH6220D reference Operating manual shown below, then tap in supplied
programmable thermostat card wall anchors.
(wallplate attached to back)
Insert quick reference card 5 Place wallplate over anchors, insert
and tighten mounting screws.
2 3
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Terminal Designations
Heat Pump Conventional Terminal Letters:
Conventional Y2 2nd stage compressor contactor
W2 2nd stage heat relay
G Fan relay Remove
NOTES W 1st stage heat relay jumper
C Common wire from secondary side of
R & Rc terminals cooling system transformer
In single-transformer system, leave metal Y 1st stage compressor contactor
jumper in place between R & Rc. Remove R Heating power. Connect to secondary
metal jumper if two-transformer system. side of heating system transformer.
Rc Cooling power. Connect to secondary
C terminal side of cooling system transformer.
The C (common wire) terminal is optional
when thermostat is powered by batteries. Heat Pump Terminal Letters:
L Heat pump reset. L terminal powered
W (O/B) terminal continuously when System is set to Em
If thermostat is configured for a heat pump Heat.
in the Installer Setup, configure changeover E Emergency heat relay
valve for cool (“O” factory setting) or heat Aux Auxiliary heat relay
(“B”). G Fan relay
O/B Changeover valve for heat pumps
L terminal (Output) C Common wire from secondary side of
Heat pump reset. L terminal powered contin- cooling system transformer.
uously when thermostat is set to Em Heat. Y Compressor contactor
Configure thermostat for 2 heat / 1 cool heat R Heating power. Connect to secondary
pump in the Installer Setup. side of heating system transformer.
Rc Cooling power. Connect to secondary
Wire specifications side of cooling system transformer.
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
4 5
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Terminal Designations
Heat Pump Conventional Terminal Letters:
Conventional Y2 2nd stage compressor contactor
W2 2nd stage heat relay
G Fan relay Remove
NOTES W 1st stage heat relay jumper
C Common wire from secondary side of
R & Rc terminals cooling system transformer
In single-transformer system, leave metal Y 1st stage compressor contactor
jumper in place between R & Rc. Remove R Heating power. Connect to secondary
metal jumper if two-transformer system. side of heating system transformer.
Rc Cooling power. Connect to secondary
C terminal side of cooling system transformer.
The C (common wire) terminal is optional
when thermostat is powered by batteries. Heat Pump Terminal Letters:
L Heat pump reset. L terminal powered
W (O/B) terminal continuously when System is set to Em
If thermostat is configured for a heat pump Heat.
in the Installer Setup, configure changeover E Emergency heat relay
valve for cool (“O” factory setting) or heat Aux Auxiliary heat relay
(“B”). G Fan relay
O/B Changeover valve for heat pumps
L terminal (Output) C Common wire from secondary side of
Heat pump reset. L terminal powered contin- cooling system transformer.
uously when thermostat is set to Em Heat. Y Compressor contactor
Configure thermostat for 2 heat / 1 cool heat R Heating power. Connect to secondary
pump in the Installer Setup. side of heating system transformer.
Rc Cooling power. Connect to secondary
Wire specifications side of cooling system transformer.
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
4 5
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Power supply. Provide disconnect means and overload protection as required. Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only. Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection. Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only. In Installer Setup, set system type to Heat Only.
In Installer Setup, set system type to 1Heat/1Cool Heat Pump & changeover valve to 0 or B. In Installer Setup, set system type to 1Heat/1Cool Heat Pump & changeover valve to 0 or B.
In Installer Setup, set system type to 2Heat/1Cool Heat Pump. In Installer Setup, set system type to 2Heat/1Cool Heat Pump.
L terminal is powered continuously when thermostat is set to Em Heat. L terminal is powered continuously when thermostat is set to Em Heat.
Install field jumper between Aux and E if there is no emergency heat relay. Install field jumper between Aux and E if there is no emergency heat relay.
In Installer Setup, set system type to 2Heat/2Cool conventional. In Installer Setup, set system type to 2Heat/2Cool conventional.
Typical 1H/1C heat pump system Typical heat-only system Typical heat-only system with fan Heat-only system (Series 20)
6 7
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Power supply. Provide disconnect means and overload protection as required. Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only. Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection. Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only. In Installer Setup, set system type to Heat Only.
In Installer Setup, set system type to 1Heat/1Cool Heat Pump & changeover valve to 0 or B. In Installer Setup, set system type to 1Heat/1Cool Heat Pump & changeover valve to 0 or B.
In Installer Setup, set system type to 2Heat/1Cool Heat Pump. In Installer Setup, set system type to 2Heat/1Cool Heat Pump.
L terminal is powered continuously when thermostat is set to Em Heat. L terminal is powered continuously when thermostat is set to Em Heat.
Install field jumper between Aux and E if there is no emergency heat relay. Install field jumper between Aux and E if there is no emergency heat relay.
In Installer Setup, set system type to 2Heat/2Cool conventional. In Installer Setup, set system type to 2Heat/2Cool conventional.
Typical 1H/1C heat pump system Typical heat-only system Typical heat-only system with fan Heat-only system (Series 20)
6 7
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Power supply. Provide disconnect means and overload protection as required. Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only. Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection. Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only. In Installer Setup, set system type to Heat Only.
In Installer Setup, set system type to 1Heat/1Cool Heat Pump & changeover valve to 0 or B. In Installer Setup, set system type to 1Heat/1Cool Heat Pump & changeover valve to 0 or B.
In Installer Setup, set system type to 2Heat/1Cool Heat Pump. In Installer Setup, set system type to 2Heat/1Cool Heat Pump.
L terminal is powered continuously when thermostat is set to Em Heat. L terminal is powered continuously when thermostat is set to Em Heat.
Install field jumper between Aux and E if there is no emergency heat relay. Install field jumper between Aux and E if there is no emergency heat relay.
In Installer Setup, set system type to 2Heat/2Cool conventional. In Installer Setup, set system type to 2Heat/2Cool conventional.
Typical cool-only system Heat-only system (normally open zone valve) Typical 2H/2C system (1 transformer) Typical 2H/1C heat pump system
8 9
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Power supply. Provide disconnect means and overload protection as required. Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only. Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection. Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only. In Installer Setup, set system type to Heat Only.
In Installer Setup, set system type to 1Heat/1Cool Heat Pump & changeover valve to 0 or B. In Installer Setup, set system type to 1Heat/1Cool Heat Pump & changeover valve to 0 or B.
In Installer Setup, set system type to 2Heat/1Cool Heat Pump. In Installer Setup, set system type to 2Heat/1Cool Heat Pump.
L terminal is powered continuously when thermostat is set to Em Heat. L terminal is powered continuously when thermostat is set to Em Heat.
Install field jumper between Aux and E if there is no emergency heat relay. Install field jumper between Aux and E if there is no emergency heat relay.
In Installer Setup, set system type to 2Heat/2Cool conventional. In Installer Setup, set system type to 2Heat/2Cool conventional.
Typical cool-only system Heat-only system (normally open zone valve) Typical 2H/2C system (1 transformer) Typical 2H/1C heat pump system
8 9
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
To begin, press and hold the and FAN Press or to change settings
buttons until the display changes Press NEXT to advance to next function
Press DONE to exit and save settings
Battery Power
The thermostat can be powered by Setup Function Settings & Options
batteries alone or, if used with AC
power, can provide backup power. 1 System type 0 Gas, oil or electric heat with air conditioning
1 1 heat/1 cool heat pump
During power interruptions the 2 Heat only (2-wire systems/power to open & close zone valves/
batteries will save time/day settings normally open zone valves)
3 Heat only with fan
and power the display. 4 Cool only
5 2 heat/1 cool heat pump
After installation, batteries can be 6 2 heat/2 cool conventional
changed without removing the ther- 7 2 heat/1 cool conventional
Install batteries in back of thermostat 8 1 heat/2 cool conventional
(optional if AC powered). mostat from the wall (see page 15).
2 Changeover valve 0 Changeover valve (O/B terminal energized in cooling)
(O/B terminal) 1 Changeover valve (O/B terminal energized in heating)
3 Fan control 0 Gas or oil furnace — equipment controls fan in heating
To Mount Thermostat (heating) 1 Electric furnace — thermostat controls fan in heating
5 Heat cycle rate 5 For gas or oil furnaces of less than 90% efficiency
Align the 4 tabs on the wallplate with (CPH: cycles/hour) 1 For steam or gravity systems
corresponding slots on the back of the 3 For hot water systems & furnaces of over 90% efficiency
9 For electric furnaces
thermostat, then push gently until the [Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
thermostat snaps in place.
6 Second stage heat 5 For gas or oil furnaces of less than 90% efficiency
cycle rate/ 1 For steam or gravity systems
Auxiliary heat 3 For hot water systems & furnaces of over 90% efficiency
(CPH) 9 For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
10 11
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
To begin, press and hold the and FAN Press or to change settings
buttons until the display changes Press NEXT to advance to next function
Press DONE to exit and save settings
Battery Power
The thermostat can be powered by Setup Function Settings & Options
batteries alone or, if used with AC
power, can provide backup power. 1 System type 0 Gas, oil or electric heat with air conditioning
1 1 heat/1 cool heat pump
During power interruptions the 2 Heat only (2-wire systems/power to open & close zone valves/
batteries will save time/day settings normally open zone valves)
3 Heat only with fan
and power the display. 4 Cool only
5 2 heat/1 cool heat pump
After installation, batteries can be 6 2 heat/2 cool conventional
changed without removing the ther- 7 2 heat/1 cool conventional
Install batteries in back of thermostat 8 1 heat/2 cool conventional
(optional if AC powered). mostat from the wall (see page 15).
2 Changeover valve 0 Changeover valve (O/B terminal energized in cooling)
(O/B terminal) 1 Changeover valve (O/B terminal energized in heating)
3 Fan control 0 Gas or oil furnace — equipment controls fan in heating
To Mount Thermostat (heating) 1 Electric furnace — thermostat controls fan in heating
5 Heat cycle rate 5 For gas or oil furnaces of less than 90% efficiency
Align the 4 tabs on the wallplate with (CPH: cycles/hour) 1 For steam or gravity systems
corresponding slots on the back of the 3 For hot water systems & furnaces of over 90% efficiency
9 For electric furnaces
thermostat, then push gently until the [Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
thermostat snaps in place.
6 Second stage heat 5 For gas or oil furnaces of less than 90% efficiency
cycle rate/ 1 For steam or gravity systems
Auxiliary heat 3 For hot water systems & furnaces of over 90% efficiency
(CPH) 9 For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
10 11
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
1 0 10 0
Done Next
Done Next
To begin, press and hold the and FAN Press or to change settings
buttons until the display changes Press NEXT to advance to next function To begin, press and hold the and Press to turn on system
Press DONE to exit and save settings
buttons until the display changes Press to turn off system
Press to advance to next test
NEXT
27 Heat temperature 90 Highest heating temperature setting CAUTION: EQUIPMENT DAMAGE HAZARD
range stops 40-89 Heating temperature range (increments of 1°F, or 0.5°C)
Compressor protection (minimum off time) is bypassed during testing. To prevent
28 Cool temperature 50 Lowest cooling temperature setting equipment damage, avoid cycling the compressor quickly.
range stops 51-99 Cooling temperature range (increments of 1°F, or 0.5°C)
12 13
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
1 0 10 0
Done Next
Done Next
To begin, press and hold the and FAN Press or to change settings
buttons until the display changes Press NEXT to advance to next function To begin, press and hold the and Press to turn on system
Press DONE to exit and save settings
buttons until the display changes Press to turn off system
Press to advance to next test
NEXT
27 Heat temperature 90 Highest heating temperature setting CAUTION: EQUIPMENT DAMAGE HAZARD
range stops 40-89 Heating temperature range (increments of 1°F, or 0.5°C)
Compressor protection (minimum off time) is bypassed during testing. To prevent
28 Cool temperature 50 Lowest cooling temperature setting equipment damage, avoid cycling the compressor quickly.
range stops 51-99 Cooling temperature range (increments of 1°F, or 0.5°C)
12 13
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Adaptive Intelligent Recovery™ (Setup Function 13) Quick reference to display screen
Current inside temperature Low battery warning Current time/day
Adaptive Intelligent Recovery eliminates guesswork when setting your schedule. It
allows the thermostat to “learn” how long your furnace and air conditioner take to
reach the temperature you want. In Recovery Temperature setting
Inside Replace Battery Heat
Adaptive Intelligent Setting
Just set your program schedule to the time you want the house to reach your
desired temperature.The thermostat then turns on the heating or cooling at just the
right time to reach your scheduled temperature at your scheduled time.
For example: Set the Wake time to 6 am, and the temperature to 70°.The heat will
Recovery
6:30
Wed
AM
75
Auxiliary
Heat On
° Auxiliary heat
(Only for heat pumps
with auxiliary heat)
75 °
6:30 AM
75
Cool On
° compressor in your air conditioning or heat
pump system.
Damage can occur if the compressor is re-
started too soon after shutdown.This feature
settings (functions change depending on the task)
Battery replacement
Press and pull to remove
Auto/On
Insert fresh AA
Fan System
Set Clock/Day/ Auto Cool forces the compressor to wait for a few alkaline batteries,
Schedule then reinstall
minutes before restarting. battery holder
During the wait time, the message Cool On
Message flashes until safe or Heat On (heat pumps only) will flash on
restart time has elapsed
the display.When the safe wait time has
elapsed, the message stops flashing and the
compressor turns on.
14 15
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Adaptive Intelligent Recovery™ (Setup Function 13) Quick reference to display screen
Current inside temperature Low battery warning Current time/day
Adaptive Intelligent Recovery eliminates guesswork when setting your schedule. It
allows the thermostat to “learn” how long your furnace and air conditioner take to
reach the temperature you want. In Recovery Temperature setting
Inside Replace Battery Heat
Adaptive Intelligent Setting
Just set your program schedule to the time you want the house to reach your
desired temperature.The thermostat then turns on the heating or cooling at just the
right time to reach your scheduled temperature at your scheduled time.
For example: Set the Wake time to 6 am, and the temperature to 70°.The heat will
Recovery
6:30
Wed
AM
75
Auxiliary
Heat On
° Auxiliary heat
(Only for heat pumps
with auxiliary heat)
75 °
6:30 AM
75
Cool On
° compressor in your air conditioning or heat
pump system.
Damage can occur if the compressor is re-
started too soon after shutdown.This feature
settings (functions change depending on the task)
Battery replacement
Press and pull to remove
Auto/On
Insert fresh AA
Fan System
Set Clock/Day/ Auto Cool forces the compressor to wait for a few alkaline batteries,
Schedule then reinstall
minutes before restarting. battery holder
During the wait time, the message Cool On
Message flashes until safe or Heat On (heat pumps only) will flash on
restart time has elapsed
the display.When the safe wait time has
elapsed, the message stops flashing and the
compressor turns on.
14 15
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Check temperature range stop settings (Function 27 & 28 on page 12). “Heat On” is • Change the System Setting to Heat, and set the temperature level above
not displayed the current room temperature.
Heating system • Check for 24 Vac at the equipment on the secondary side of the trans-
does not respond former between power and common. If voltage is not present, check the “Cool On” is not • Change the System Setting to Cool, and set the temperature level below
(“Heat On” heating equipment to find the cause of the problem. displayed the current room temperature.
appears on • Check for 24 Vac between the heat terminal (W) and the transformer “Cool On” or • Compressor protection timeout is engaged. Wait 5 minutes for the
screen) common. If 24 Vac is present, the thermostat is functional. Check the “Heat On” system to restart safely, without damage to the compressor.
heating equipment to find the cause of the problem. is flashing
• Check for loose or broken wires between the thermostat and the heating
equipment.
Accessories & replacement parts
Cooling system • Check for 24 Vac at the equipment on the secondary side of the trans- Please contact your distributor to order replacement parts.
does not respond former between power and common. If voltage is not present, check the
(“Cool On” cooling equipment to find the cause of the problem Battery holder ......................................................Part Number 50007072-001
appears on Cover plate assembly ........................................Part Number 50002883-001
• Check for 24 Vac between the cooling terminal (Y) and the transformer (Use to cover marks left by old thermostats.)
screen) common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
• Check for loose or broken wires between the thermostat and the cooling Specifications
equipment.
Temperature Ranges Electrical Ratings
Fan does not • Check Installer Setup, Function 3 (Fan Control), to make sure the fan • Heat: 40° to 90°F (4.5° to 32°C)
turn on in a call control is properly set to match the type of system (see page 11). • Cool: 50° to 99°F (10° to 37°C) Terminal Voltage (50/60Hz) Running Current
for heat W (O/B) Heating 20-30 Vac 0.02-1.0 A
Operating Ambient Temperature
• 32° to 120°F (0° to 48.9°C) (Powerpile) 750 mV DC 100 mA DC
Heat pump • Check Installer Setup, Function 2 (Changeover Valve), to make sure it is
issues cool air properly configured for your system (see page 11). Shipping Temperature W2 (Aux) Heating 20-30 Vac 0.02-0.5 A
in heat mode, • -20° to 120°F (-28.9° to 48.9°C) Y Cooling 20-30 Vac 0.02-1.0 A
or warm air in
cool mode Operating Relative Humidity Y2 Cooling 20-30 Vac 0.02-1.0 A
• 5% to 90% (non-condensing) G Fan 20-30 Vac 0.02-0.5 A
Heat/cool both • Check Installer Setup, Function 1 (System Type), to make sure it is set to
Physical Dimensions E Emergency heat 20-30 Vac 0.02-1.0 A
on at same time, match the installed heating/cooling equipment (see page 11).
• 3-9/16” H x 5-13/16” W x 1-1/2” D
or heat does L Heat pump reset 20-30 Vac 0.02-0.5 A
• Check to make sure heating and cooling wires are not shorted together. • 91 mm H x 147 mm W x 38 mm D
not turn off
16 17
Installation Guide FocusPRO™ TH6220D Programmable Thermostat
Check temperature range stop settings (Function 27 & 28 on page 12). “Heat On” is • Change the System Setting to Heat, and set the temperature level above
not displayed the current room temperature.
Heating system • Check for 24 Vac at the equipment on the secondary side of the trans-
does not respond former between power and common. If voltage is not present, check the “Cool On” is not • Change the System Setting to Cool, and set the temperature level below
(“Heat On” heating equipment to find the cause of the problem. displayed the current room temperature.
appears on • Check for 24 Vac between the heat terminal (W) and the transformer “Cool On” or • Compressor protection timeout is engaged. Wait 5 minutes for the
screen) common. If 24 Vac is present, the thermostat is functional. Check the “Heat On” system to restart safely, without damage to the compressor.
heating equipment to find the cause of the problem. is flashing
• Check for loose or broken wires between the thermostat and the heating
equipment.
Accessories & replacement parts
Cooling system • Check for 24 Vac at the equipment on the secondary side of the trans- Please contact your distributor to order replacement parts.
does not respond former between power and common. If voltage is not present, check the
(“Cool On” cooling equipment to find the cause of the problem Battery holder ......................................................Part Number 50007072-001
appears on Cover plate assembly ........................................Part Number 50002883-001
• Check for 24 Vac between the cooling terminal (Y) and the transformer (Use to cover marks left by old thermostats.)
screen) common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
• Check for loose or broken wires between the thermostat and the cooling Specifications
equipment.
Temperature Ranges Electrical Ratings
Fan does not • Check Installer Setup, Function 3 (Fan Control), to make sure the fan • Heat: 40° to 90°F (4.5° to 32°C)
turn on in a call control is properly set to match the type of system (see page 11). • Cool: 50° to 99°F (10° to 37°C) Terminal Voltage (50/60Hz) Running Current
for heat W (O/B) Heating 20-30 Vac 0.02-1.0 A
Operating Ambient Temperature
• 32° to 120°F (0° to 48.9°C) (Powerpile) 750 mV DC 100 mA DC
Heat pump • Check Installer Setup, Function 2 (Changeover Valve), to make sure it is
issues cool air properly configured for your system (see page 11). Shipping Temperature W2 (Aux) Heating 20-30 Vac 0.02-0.5 A
in heat mode, • -20° to 120°F (-28.9° to 48.9°C) Y Cooling 20-30 Vac 0.02-1.0 A
or warm air in
cool mode Operating Relative Humidity Y2 Cooling 20-30 Vac 0.02-1.0 A
• 5% to 90% (non-condensing) G Fan 20-30 Vac 0.02-0.5 A
Heat/cool both • Check Installer Setup, Function 1 (System Type), to make sure it is set to
Physical Dimensions E Emergency heat 20-30 Vac 0.02-1.0 A
on at same time, match the installed heating/cooling equipment (see page 11).
• 3-9/16” H x 5-13/16” W x 1-1/2” D
or heat does L Heat pump reset 20-30 Vac 0.02-0.5 A
• Check to make sure heating and cooling wires are not shorted together. • 91 mm H x 147 mm W x 38 mm D
not turn off
16 17
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9