Professional Documents
Culture Documents
Thermacare® TC3001
Convective Warming Unit
Service Manual
P/N 11897-000 02/06
Before you begin . . .
Symbols used within this manual:
Important
Attention: consult accompanying
• Refer to the TC3001 Convective Warming
documents
System Operating Manual for detailed
operating instructions. Read and understand
the Operating Manual and all precautions prior
to using the Convective Warming System. Dangerous voltage
38°C
43°C
46°C
Contents
Illustrations
Figure Description Page
1 Convective Warming System ............................................... 5
2A/B Power Unit Mounting ........................................................... 5
3 Pole Mounting Height Limit ................................................. 5
4 Operator Control Panel ........................................................ 6
5 TC20 Test Tool .................................................................... 9
6 Temperature Sensor Location ............................................. 10
7 Troubleshooting Chart - NO HEAT ....................................... 19
8 Troubleshooting Chart - NO AIR FLOW ................................ 20
9 Drawing/Parts List ............................................................. 24
10 Drawing/Parts List ............................................................. 25
11 Drawing/Parts List ............................................................. 26
12 TC20 Test Tool Schematic .................................................. 27
13 Wiring Diagram .................................................................. 28
Tables
Table Description Page
1 Air Temperatures ................................................................. 4
2 Functional Check/Inspection Form ....................................... 16
1
Section 1 - Safety Precautions
2
Section 2 - Repair Policy
3
Section 3 - Specifications
Bedrail
Figure 1 - Convective Warming System
Hook
CAUTION
5
Section 4 - Theory of Operation (cont’d)
6
Section 5 - Controls and Indicators
Section 6 - Preventive Maintenance
7
Section 7 - Functional Check and Safety Inspection
7.1 Enclosure
Test Equipment Examine the overall condition of the Power Unit
The following test equipment (or equivalent) is exterior:
required in order to perform the preventive 1. Unplug the power unit.
maintenance procedures:
2. Examine the enclosure, checking for cracks.
• Digital air thermistor thermometer 3. Check that exterior screws are tight.
(YSI 400 series) 4. Check that labelling and markings are
Range: 10°C to 71°C legible.
System accuracy: ± 0.6°C 5. Clean accumulated dirt from the air vents
• Temperature sensor with a vacuum cleaner.
(P/N 77948-000) 6. Check hose assembly for holes and broken
NOTE: fittings. Replace if necessary.
8
Section 7 - Functional Check and Safety Inspection (cont’d)
HEAT
9
Section 7 - Functional Check and Safety Inspection (cont’d)
4. Set the two TC20 Test Tool toggle switches as Verify that the REMOVE FROM USE light is lit.
follows:
NOTE: It is acceptable if both thermostats trip
• THERMOSTAT BYPASS -- place in center simultaneously, in which case the S2 and S3
position; indicators will both be off. If this occurs,
record the elapsed time and temperature.
• HEAT/OVERTEMP -- place in HEAT
Verify that the REMOVE FROM USE indicator is
position.
lit. Verify that both the S2 and S3 indicators
5. Locate the air temperature sensor at the center light by toggling the THERMOSTAT BYPASS
of the end of the hose (fig. 6A). Secure the switch from the S2 to S3 position. (If both
sensor with adhesive tape. Verify that the thermostats have tripped, skip steps 11-14
sensor is located at the center of the hose. and proceed to step 15.)
6. Connect the hose to a Model TC1050, TC2050, 11. Switch the TC20 THERMOSTAT BYPASS to
TC2052, or TC2054 Quilt (fig. 6B). whichever thermostat (S2 or S3) is lit. This will
short out the thermostat which opened first so
7. Turn the Power Unit on. Select the 46°C that the second thermostat can be tested.
setting.
Switch the TC20 from OVERTEMP to HEAT to
8. Run the Power Unit for 5 to 10 minutes at the
allow the Power Unit to return to normal
46°C setting. The temperature will oscillate. operating temperature before testing the
During this time interval, familiarize yourself second thermostat.
with the following steps 9 through 14. Have a
stopwatch ready. 12. Run the Power Unit again for 5 to 10 minutes
in the 46°C setting. The temperature will
9. Place the HEAT/OVERTEMP switch to oscillate. Have a stopwatch ready.
OVERTEMP. The temperature should start to
increase. When the air temperature reaches 13. Place the OVERTEMP/HEAT switch to
48°C, start the stopwatch. OVERTEMP. The temperature should start to
increase. When the air temperature reaches
10. Allow the Power Unit to heat until either the S2
48°C, start the stopwatch.
or S3 Test Tool thermostat indicator is lit. Stop
the stopwatch and note the highest temperature 14. Continue to monitor the TC20 Test Tool until the
displayed. This is the upper limit temperature for second thermostat indicator is lit. Stop the
one of the thermostats. Record the time and stopwatch and note the highest temperature
temperature on the INSPECTION FORM. displayed. This is the upper limit temperature for
the other thermostat. Record the time and
temperature on the INSPECTION FORM
10
Section 7 - Functional Check and Safety Inspection (cont’d)
(table 2, pp. 16-17). Plot these values on table position. Place the HEAT/OVERTEMP
2, page 18. Switch to OVERTEMP. Allow the Power
Unit to operate. When the air
Verify that the REMOVE FROM USE light is lit.
temperature reaches 48°C, start the
15. Thermostat trip acceptance stopwatch.
Both thermostats must trip within the d. Allow the Power Unit to heat until the
acceptance window (see table 2, p. 18). S3 thermostat indicator is lit. Stop the
If this condition is not met, do not put the stopwatch and note the highest
Power Unit in service. Contact your dealer for temperature displayed. This is the
assistance. upper limit temperature for the S3
thermostat. Record the elapsed time
16. Unplug the power unit. Open the enclosure and temperature.
to allow the Power Unit to cool for 5-10
minutes. e. Verify that the REMOVE FROM USE
light is lit.
17. Locate the two patient limit thermostats (item
17, fig. 11, pp. 26). Reset S2 by gently f. The S3 thermostat must trip within the
pressing the center reset button. acceptance window (see table 2, p.
18). If this condition is not met, do not
WARNING put the Power Unit in service. Call
Gaymar's Technical Service
Use care when resetting the Department for assistance (see back
thermostats. Excessive force cover for telephone numbers).
(force greater than 5 pounds) can
damage the overtemp protection g. Unplug the Power Unit.
device and/or inadvertently alter h. Open the enclosure and allow the
the trip temperature of the device. Power Unit to cool for 5-10 minutes.
i. Remove the filter retainer and nut.
Remove the filter. Remove the jumper
NOTE: Use care when resetting the from the S4 thermostat. Press the S4
thermostats since the power terminals are reset button and insure it is reset.
delicate. Avoid flexing the terminals. Replace the filter, filter retainer, and
Thermostats with loose terminals should nut.
be replaced and retested.
j. Reset both the S3 and S2 thermostats
18. Press the center reset button of S3. Verify it by pressing their center reset buttons.
has reset (indicated by an audible "click" and (The S2 thermostat may have
tactile feedback). If it "clicks", proceed to retripped.)
step 19.
19. Remove the TC20 Test Tool.
If you don't hear a "click", then what was
assumed to be the patient limit thermostat S3
WARNING
tripping was actually the heater overtemp
thermostat S4 in the same circuit. This will After performing the preceding test
rarely occur. If it has occurred, proceed as procedure, verify that the TC20 Test
follows: Tool and all jumpers have been
a. Remove the filter retainer and nut. removed before returning the Power
Remove the filter. Jumper out the S4 Unit to patient use. Failure to do so
thermostat. Replace the filter, filter may result in death, serious injury, or
retainer and nut. equipment malfunction.
b. Run the Power Unit for 5 to 10 minutes
in the 46°C setting.
20. Proceed to the FILTER SWITCH TEST
c. Bypass S2 by placing the (section 7.6, p. 14).
THERMOSTAT BYPASS switch in the S2
11
Section 7 - Functional Check and Safety Inspection (cont’d)
7.5.2 ALTERNATE Test Jumper 26. Unplug the Power Unit. Carefully separate the
enclosure slightly.
Procedure (steps 21 to 50)
21. Unplug the Power Unit. 27. Unplug the thermistor (item 12, fig. 10, p. 25)
from the back of the control board.
NOTE: The power resistor on the back side
WARNING
of the PC board may be hot to touch.
Always unplug the Power Unit 28. Put the enclosure back together and secure
before attaching or removing it with adhesive (duct) tape.
jumpers and when resetting
thermostats. Failure to unplug the 29. Plug in the Power Unit and turn it on. Leave
Power Unit could result in unit in 32°C temperature setting. Have a
electrical shock and cause death stopwatch ready.
or serious injury. NOTE: Do not set the TEMPERATURE
SETTINGS switch to fan only since this
setting disables the heater.
22. There are two patient limit thermostats 30. The temperature should increase. When the
within the Power Unit and each must be air temperature reaches 48°C, start the
tested. One 16 gauge insulated stranded stopwatch. The Power Unit will heat until the
wire jumper with alligator clips will be S2 thermostat trips. When this happens, the
required. To help remember to remove the blower and heater will shut off. Stop the
test jumper, label a LARGE, distinctive tag stopwatch and note the highest temperature
“REMOVE AFTER TEST” and tie the tag to displayed. This is the upper limit temperature
the jumper. for one of the thermostats. Record the time
Remove the six screws on the back of the and temperature on the INSPECTION FORM
unit. Install a jumper across thermostat S3 (table 2, pp. 16-17).
(item 17, fig. 11, p.26). Temporarily secure 31. Verify that the REMOVE FROM USE light is
the two halves of the enclosure together with lit.
adhesive (duct) tape.
32. Unplug the Power Unit.
23. Locate the air temperature sensor at the
center of the end of the hose (fig. 6A, p. 10). 33. Open the enclosure and allow the Power Unit
Secure the sensor with adhesive tape. Verify to cool for 5-10 minutes.
that the sensor is located at the center of 34. Locate the two patient limit thermostats
the hose. (item 17, fig. 11, p. 26). Gently press the
24. Connect the hose to a Model TC1050, reset button in the center of each
TC2050, TC2052, or TC2054 Quilt (fig. 6B, thermostat. Move the a jumper across
p. 10). thermostat S2.
25. Plug in the Power Unit and turn it on. Select
the 46°C setting. Run the Power Unit for
WARNING
5 to 10 minutes. The temperature will
oscillate. During this time interval, familiarize Use care when resetting the
yourself with the following steps 26 through thermostats. Excessive force
31, so that the procedure can be (force greater than 5 pounds) can
accomplished quickly, without letting the damage the overtemp protection
Power Unit cool. device and/or inadvertently alter
the trip temperature of the device.
NOTE: Perform the following steps 26
through 31 as quickly as possible, to
prevent the Power Unit from cooling
down:
12
Section 7 - Functional Check and Safety Inspection (cont’d)
NOTE: If both thermostats reset, both 43. The temperature should start to increase.
thermostats have tripped. This is When the air temperature reaches 48°C, start
acceptable. the stopwatch. Allow the Power Unit to heat
until thermostat S3 trips. Stop the stopwatch
NOTE: Use care when resetting the
and note the highest temperature displayed.
thermostats since the power terminals are
This is the upper limit temperature for
delicate. Avoid flexing the terminals.
thermostat S3. Record the time and
Thermostats with loose terminals should
temperature on the INSPECTION FORM
be replaced and retested. Be certain the
(table 2, p. 17). Plot these values on table 2,
thermostats have cooled for 5-10 minutes
page 18.
before resetting.
44. Verify that the REMOVE FROM USE light is lit.
NOTE: If thermostat S2 does not reset, the
heater overtemp thermostat has tripped. 45. Unplug the Power Unit.
In the unlikely event that this has
46. Open the enclosure and allow the Power Unit
occurred, perform the following:
to cool for 5-10 minutes.
a) remove the filter retainer and nut;
b) remove the filter; 47. Thermostat trip acceptance
c) jumper the S4 heater overtemp
Both thermostats must trip within the
thermostat; and
acceptance window (see table 2, p. 18).
d) replace the filter, filter retainer, and nut.
If this condition is not met, do not put the
Return to step 25.
Power Unit in service. Contact your dealer for
35. Reconnect the thermistor to the control assistance.
board.
48. Remove the jumper from the patient limit
36. Put the enclosure back together and secure thermostat.
it with tape.
If a jumper was used on the S4 heater
37. Plug in the Power Unit. Turn it on. overtemp thermostat, remove the filter
retainer, nut, and filter. Remove the jumper
38. Run the Power Unit for 5-10 minutes in the
from S4. Reset S4 (indicated by an audible
46°C setting to stabilize the system
"click" and tactile feedback). Replace the filter,
temperature.
filter retainer, and nut.
NOTE: Perform the following steps 39 through
44 as quickly as possible, to prevent the Power WARNING
Unit from cooling down:
After performing the preceding test
procedure, verify that all test jumpers
39. Unplug the Power Unit. Carefully separate
have been removed before returning
the enclosure slightly.
the Power Unit to patient use.
40. Unplug the thermistor (item 12, fig. 10, p. Failure to remove the test jumper
25) from the back of the control board. may result in death, serious injury, or
equipment malfunction.
41. Put the enclosure back together and secure
it with tape.
42. Plug in the Power Unit and turn it on. Leave 49. Reconnect the thermistor connector.
unit in 32°C temperature setting. Have a
stopwatch ready. (continued)
13
Section 7 - Functional Check and Safety Inspection (cont’d)
50. Reset the thermostats by gently pressing the 6. Unplug the Power Unit. Install filter. (Install
center reset buttons. new filter every 1000 operating hours or 12
months, whichever occurs first.) Replace the
WARNING
filter only with the Gaymar P/N listed (see
parts list, fig. 9, p.24). Record the hour timer
Use care when resetting the reading onto the new filter label. Reattach
thermostats. Excessive force filter retainer and nut.
(force greater than 5 pounds) can
damage the overtemp protection CAUTION
device and/or inadvertently alter
the trip temperature of the device. The HEPA filter must be seated
properly. Failure to install the filter
correctly will prevent it from
NOTE: Use care when resetting the functioning properly, and could
thermostats since the power terminals are allow unfiltered air to reach the
delicate. Avoid flexing the terminals. patient and cause injury.
Thermostats with loose terminals should
be replaced and retested.
7. Replace the six screws holding the
enclosure together.
7.6 Filter Replacement and Filter
Switch Test (every 12 months or 1000 7.7 Quilt Temperature
operating hours, whichever occurs first)
Verify temperature output at each heat setting:
1. Unplug the Power Unit. Separate the two
halves of the enclosure. Lay the Power Unit 1. Prepare the Power Unit test setup, if it has
on its back. not been previously prepared:
2. Remove the filter retainer and nut. Remove a. Locate the air temperature sensor at
the filter. the center of the end of the hose (fig.
6A, p. 10). Secure the sensor with
3. Put the enclosure back together and secure it adhesive tape. Verify that the sensor
with tape. is located at the center of the hose.
4. Plug in the Power Unit. Turn it on. Verify that b. Connect the hose to a Model TC1050,
the blower does not start and that the TC2050, TC2052, or TC2054 Quilt
REMOVE FROM USE light is lit. (fig. 6B, p. 10).
5. A timer which counts total running hours is c. Plug in the Power Unit and turn it on.
located inside the Power Unit for use by
service personnel. Timer readings may be 2. Set the TEMPERATURE SETTINGS switch to
used to track HEPA filter usage intervals. To 32°C. Run the Power Unit for 5 minutes.
read the hour timer: After 5 minutes, note the two highest and two
a. Unplug the Power Unit. Separate the two lowest temperature readings. Record the
halves of the enclosure again. Locate the average of these four temperatures on the
hour timer (see figure 10, p. 25). Plug in INSPECTION FORM (table 2, p. 17).
the Power Unit and turn it on. Read the Allowable 32°C temperature:
hour timer and record the total running 30.6°C to 33.9°C average
hours on the INSPECTION FORM.
3. Repeat step 2 for 38°C setting. Average
b. Turn the Power Unit off. temperatures and record.
Allowable 38°C temperature:
36.1°C to 39.4°C average
14
Section 7 - Functional Check and Safety Inspection (cont’d)
4. Repeat step 2 for 43°C setting. Average 7.10 Completing the Functional Check
temperatures and record. and Safety Inspection
Allowable 43°C temperature: If the Power Unit has passed the FUNCTIONAL
41.7°C to 45.0°C average CHECK AND SAFETY INSPECTION for all
requirements of procedures 7.1 through 7.9, the
5. Repeat step 2 for 46°C setting. Power Unit should be considered operational and
Allowable 46°C temperature: suitable for return to service.
44.7°C to 47.5°C average
This completes the recommended FUNCTIONAL
6. If the temperatures in steps 2 through 5 are CHECK AND SAFETY INSPECTION for the TC3001
not correct, do not put the Power Unit into series Power Unit.
service. Contact your dealer for assistance.
7. Unplug the Power Unit.
15
Section 8 - Inspection Form
T C3001 Po we r Unit Functio nal Che ck and Safe ty Inspe ctio n Fo rm
Location _________________________________________________ Initials _______________ Date _____________________
Hour timer (total hours) _____________ Replaced HEPA Filter: Yes _______ N o _______ Serial N umber ______________________
P rocedure (s) Done? Action Results **
(check) (circle selection)
38 Run the Power U nit for 5-10 minutes in the 46°C setting to stabilize.
47 Verify that the time/temperature values in steps 30 and 43 for both thermostats fall within the Pass Fail
acceptance window on page 3 of the IN SP ECTION FORM.
48 R e mo ve the jumpe r( s) fro m the patie nt limit the rmo stat and he ate r o ve rte mp the rmo stat.
4 P lug in Power U nit. Verify the blower does not turn on. Pass Fail
Filter replacement
7.6 and filter switch Verify the REMOVE FROM U SE indicator lights. Pass Fail
test
5 Unplug Po we r Unit. Se parate e nclo sure . Plug in Po we r Unit, turn it o n, and re ad ho ur time r.
R e co rd to tal running ho urs o n ne w filte r labe l and INSPECT ION FOR M. Turn o ff Po we r Unit.
6 Unplug Po we r Unit. Install ne w filte r if ne ce ssary. R e co rd ho ur time r re ading o nto ne w filte r labe l.
R e place filte r re taine r and nut.
1 P repare test setup. Mount air temperature sensor at the center of the end of the hose. P lug in Power U nit.
2 Turn on Power U nit. Set HEAT SETTIN GS to 32°C. Run Power U nit for 5 minutes. N ote 2 highest Pass Fail
and 2 lowest temperatures. Average the 4 readings. Record value : ___________°C
[Average of 32°C values must be between 30.6°C and 33.9°C]
3 Repeat step 2 for 38°C setting. Record value: __________°C Pass Fail
[Average of 38°C values must be between 36.1°C and 39.4°C.]
7.7 Quilt temperature
4 Repeat step 2 for 43°C setting. Record value: __________°C Pass Fail
[Average of 43°C values must be between 41.7°C and 45.0°C.]
5 Repeat step 2 for 46°C setting. Record value: __________°C Pass Fail
[Average of 46°C values must be between 44.7°C and 47.5°C.]
1 Unplug the Po we r Unit. Me asure and re co rd gro und re sistance : _________ o hms Pass Fail
7.8 Ground resistance
[ Gro und re sistance must be le ss than 0.5 o hms.]
Open N ormal
Closed N ormal
Closed Reverse
2 Verify current leakage does not exceed 100 µA for all above conditions. Pass Fail
* If both thermostats trip simultaneously (i.e., at the same time and temperature), record the same results in 43 as in 30.
** Circling "Fail" indicates ser vice or repair is required. Contact your local dealer for assistance.
68
66
Fail (Thermostat trip point too high)
64
62
60
Section 8 - Inspection Form (cont’d)
58
PASS (Safe range)
56
48
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190
Time (Seconds)
Section 9 - Troubleshooting
SYMPTOM: NO HEAT
DOES NO
GO TO NO AIR FLOW
QUILT
SYMPTOM
INFLATE?
YES
PRESS
EACH SETTING NO
BUTTON. DOES CONTACT
YOUR DEALER
CORRESPONDING
LED LIGHT?
YES
UNPLUG UNIT;
MEASURE HEATER
RESISTANCE
IS
HEATER NO
RESISTANCE
REPLACE HEATER
BETWEEN 7.5
AND 8.3
OHMS?
YES
UNPLUG RT1
THERMISTOR NO SUSPECT PC
ASSY. TURN
BOARD; CONTACT
POWER ON.
TECHNICAL SERVICE
DOES
UNIT HEAT?
YES
REPLACE RT1
THERMISTOR ASSY
ENSURE UNIT IS
PLUGGED IN
YES
NO
IS CALL
RFU LIT? YOUR DEALER
YES
UNPLUG
UNIT AND
OPEN IT
IS FILTER NO
REINSTALL
INSTALLED
FILTER
CORRECTLY?
YES
NO YES
S4 HAS
PERFORM FUNCTION CHECK--
TRIPPED
RUN UNIT IN NO POSSIBLE CAUSES:
DOES RFU
32°C SETTING 1. TOO HIGH STORAGE TEMP
REOCCUR?
FOR 10 MINUTES 2. UNIT OUT OF CAL.
3. LOW SPEC ON S2, S3
RESET S4 YES
POSSIBLE CONTROLLER
FAILURE; CALL
YOUR DEALER
IS THERE A
POWER UP NO YES REMOVE BLOCKAGE;
BLOCKED,BENT,
UNIT. REPLACE/ALIGN
OR MISALIGNED
AIRFLOW? BLOWER WHEEL
BLOWER WHEEL?
YES NO
REPAIR/REPLACE
MOTOR
PERFORM
FUNCTIONAL
CHECK
10.0 Repair Procedures 4. Remove the ten screws securing the filter
inlet plate.
WARNING
5. Remove the screw and lock washer securing
the ground wire to the backing plate.
Use only Gaymar replacement parts as Remove the two screws securing the
identified in the parts lists (pp. 24-27). terminal block.
Use of substitute parts could result in
power unit malfunction or patient 6. Carefully lift the filter inlet plate, exposing the
injury. blower wheel.
7. Remove the blower wheel using 1/8" hex
wrench through hole in one blade of blower
To identify replacement parts, refer to figures wheel.
9-11 (pp. 24-27). To order replacement parts, 8. Remove the two #6 screws holding the
contact Gaymar's Export Department: heater to the motor bracket.
Telephone: (716) 662-8636 9. Disconnect the short wire from the heater to
Fax: (716) 662-0730 the motor.
10. Remove the red heater wire from terminal
10.1 Replacing the Patient Limit block location TB1-3 (see figure 11).
Remove wire ties.
Thermostat(s) (S2 & S3)
To replace either thermostat (item 17, fig. 11): 11. Remove the heater.
2. Remove the six screws securing the 13. Reroute the red wire through the 4-hole
enclosure. Open the enclosure. grommet.
3. Carefully unplug the terminals from the 14. Reconnect both wires. Refer to TB1
thermostat. designators in the schematic (figure 13) and
terminal block wiring designators in figure
4. Remove the two #4 nuts from the 11. Install wire ties.
thermostat.
15. Reinstall the blower wheel, making sure
5. Replace the thermostat. Reinstall the nuts. there is 2.5 mm clearance between the
6. Carefully replace the terminals. wheel and the blower inlet ring (see fig. 9).
(NOTE: the hex screw must be aligned with
7. Perform the FUNCTIONAL CHECK AND the flat on the motor shaft.)
SAFETY INSPECTION (section 7, pp. 8-15).
16. Place the filter inlet plate back on top of the
scroll. Secure the ten screws.
10.2 Replacing the Heater 17. Replace the terminal block. Reconnect the
To replace the heater (item 3, fig. 9): ground wire to the backing plate; make sure
the lock washer is reinstalled.
1. Unplug the Power Unit.
18. Replace the HEPA filter. Secure it with the
2. Remove the six screws securing the filter retainer and nut.
enclosure. Open the enclosure.
19. Perform the FUNCTIONAL CHECK AND
3. Remove the filter retainer and nut. Remove SAFETY INSPECTION (section 7, pp. 8-15).
the HEPA filter.
21
Section 10 - Repair Procedures (cont’d)
8. Depending on the method of mounting, either 10. Remove the two #8 screws and two #8
use wire cutters to remove the spring clip, or nuts from the bottom of motor.
loosen the speed nut securing the thermistor 11. Loosen the two #8 screws on top of motor.
assembly to the filter inlet plate. Slide filter support bracket off. Loosen
9. Replace the thermistor assembly. Secure it corresponding screws on new motor and
with the new speed nut supplied with the replace filter support bracket. Tighten
thermistor assembly. screws.
10. Place filter inlet plate back on top of the 12. Remove and replace the motor.
scroll. Secure the ten screws. 13. Secure with mounting hardware.
11. Replace the terminal block. Reconnect the 14. Reconnect the terminals.
ground wire to the backing plate. Make sure
the lock washer is reinstalled. 15. Secure wire harness to motor with a wire tie.
12. Plug the thermistor assembly into the control 16. Reinstall the blower wheel, making sure
board. Use the tie wraps supplied with the there is 2.5 mm clearance between the
thermistor assembly to hold the thermistor wheel and the blower inlet ring (see fig. 9).
wires to the PC board wire harness and NOTE: the hex screw must be aligned with
enclosure standoff. the flat on the motor shaft.
13. Replace the HEPA filter. Secure it with the 17. Place the filter inlet plate back on top of the
filter retainer and nut. scroll. Secure the ten screws.
14. Perform the FUNCTIONAL CHECK AND 18. Replace the terminal block. Reconnect the
SAFETY INSPECTION (section 7, pp. 8-15). ground wire to the backing plate; make sure
the lock washer is installed.
19. Replace the HEPA filter. Secure it with the
filter retainer and nut.
22
Section 10 - Repair Procedures (cont’d)
20. Perform the FUNCTIONAL CHECK AND 3. Cut the four cable ties which secure the PC
SAFETY INSPECTION (section 7, pp. 8-15). board wires together.
4. Unplug the following wires from the PC
10.5 Replacing the I. V. Pole Mount board assembly at the terminal block (item
Bracket 23, fig. 11):
To replace the I. V. pole mount bracket: • Yellow wire from TB1-1C
1. Unplug the Power Unit. • Gray wire from TB1-2C
2. Remove the six screws securing the • Red wire from TB1-3C
enclosure. Open the enclosure. • White wire from TB1-4C
3. Remove the two screws securing the • Black wire from TB1-5C
terminal block from the backing plate.
5. Unplug the main harness (5-pin connector)
4. Remove the two screws and the lock washer from PC board.
holding the I. V. pole mount bracket to the
backing plate. 6. Unplug the 2-pin harness from the PC board.
5. Remove the I. V. pole mount bracket from 7. Remove the six screws securing the PC
the rear half of the enclosure. board assembly.
6. Insert new I. V. pole mounting bracket into 8. Remove the old PC board assembly and
rear half of the enclosure. install the new PC board assembly.
7. Replace the two screws and the lock washer 9. Reassemble in reverse order.
into the backing plate and I. V. pole mounting 10. Perform the FUNCTIONAL CHECK AND
bracket. SAFETY INSPECTION (section 7, pp. 8-15).
8. Replace the terminal block.
9. Perform the FUNCTIONAL CHECK AND
SAFETY INSPECTION (section 7, pp. 8-15).
WARNING
23
Section 11 - Drawings/Parts Lists
4 6
3
7
2.5 mm
24
Section 11 - Drawings/Parts Lists (cont’d)
11
TEST PLUG
10
12
HOUR TIMER
13
S2 S3
Figure 10 - THERMOSTAT
BYPASS
HEAT
25
Section 11 - Drawings/Parts Lists (cont’d)
20 21
19
29
18
22
S3
S2
To release wires from
terminal block, insert a
small screwdriver in
slot nearest wire and
17 pull towards center.
23
24
16 S4
WARNING
25
15
26
27
wire tie
28
26
Section 11 - Drawings/Parts Lists (cont’d)
17 Patient lim it therm ostats (S2, S3) 91323-005 25 Hose w arning label 09038-000
ATTENTION
Static-Sensitive
Devices
27
Section 13 - Wiring Diagram
ATTENTION
Static-Sensitive
Devices
28
Section 13 - Wiring Diagram (cont’d)
29
®
Phone:
(716) 662-8636
FAX:
(716) 662-0730