Professional Documents
Culture Documents
Also safety devices may have errors. Therefore, open the temperature chamber only when
no hazardous conditions are to be expected.
•The Temperature chamber may only be used for the purpose as described above.
Other use of the chamber can result in dangerous situations and/or damage to property.
For more information: See the operating manual of the test chamber
System
Active
1. Instrumentation.
Interface unit for setting temperature, starting and
stopping tests, etc. Contains functions for
controlling temperature.
2. Operating Panel. 1.
Power, Start/stop, Help and display buttons.
3. Overheat protector. 2.
Stops the chamber to prevent damage to specimens.
4. Forced Cooling.
The function will switch off the electrical heater so the 3.
Chamber will cool down.
5. Emergency Reset. 4.
In the event of an emergency, fire detection, gas 5.
detection or explosion a emergency relay will shut down 6.
the chamber.
After this the relay must be reset with the key switch on the 7.
front of the chamber.
6. Nitrogen Purge.
Manual flush of the test area with Nitrogen for 30-3600 sec.
7. Emergency Stop Switch. 8.
In case of an emergency the chamber can be stopped immediately
by manually push the emergency Stop Switch.
After activation the switch must be pulled back before the emergency
can reset.
8. Fire Extinguisher manual activation.
Manual activation of the CO2 fire Extinguisher.
5 7 10 11
1. Specimen temperature control sensor.
Connection for a temperature sensor to monitor and control the temperature of the
specimen. See also the Espec User manual.
2. Communication port RS-232.
For monitoring and controlling the chamber with a PC.
3. Specimen power control.
Supplies power to specimens. If chamber operations are stopped by trouble,
a contact opens to shut OFF power supply to specimens.
Time signals.
Outputs signals via a contact relay to a remote location during operation.
4. Pressure Gauge for compressed air.
Indicated the pressure of the connected compressed air supply.
5. Pressure regulator for compressed air.
6. Pressure Gauge for Nitrogen.
Indicated the pressure of the connected Nitrogen supply.
7. Pressure regulator for Nitrogen.
8. Flow meter Nitrogen.
Indication of the Nitrogen flow when the Nitrogen flush is activated.
9. Safety control display.
Monitoring of all safety equipment.
10. Acknowledge/Reset button.
Short push: Switch of the alarm buzzer when there is an alarm.
Long push (> 2 Sec.): Acknowledge the active alarms and reset the PLC to clear the
alarms.
11. Main Power Switch.
Turns primary power supply to the chamber ON/OFF.
1 2 3 4
1. Acoustic/optical warning device.
Signals when the CO2 fire extinguisher is activated.
2. Exhaust box.
Including Explosion vent.+ Break detector, Gas exhaust pipe.
3. Electro mechanical door lock.
Locks the door when the chamber is active or switched off.
4. Signal Tower.
Signals the status of the chamber with color light and sound.
All safety device are connected to a safety controller with the following functions:
• Monitoring of all safety equipment.
• Safety control display for information and alarm messages.
• Control of the electric mechanical door lock.
• Control of the acoustic and visual indicators.
• Maximum temperature raise limits of the monitoring sensors in °C/min.
• Setup of flush times with Air or Nitrogen.
• Controlling safety contact for Charge/discharge system.
If an explosion occurs inside the chamber, the blast force is released from this vent to
weaken the impact.
A brake plate is installed and will brake if the pressure is getting to high.
A sensor will detect a broken plate and will switch of the chamber.
The safety control display give’s the message:
-Espec & Charger stopped
-Alarm Expl.vent
-Emergency OFF
The spray nozzle and the thermal switch are installed inside the test area of the temperature
chamber.
When the temperature inside the chamber will be higher than 162°C the extinguisher will be
activated and CO2 is sprayed inside the test area via the nozzle.
The extinguisher can also be activated by pushing the glass on the manual tripping device in
front of the chamber.
The status of the Fire extinguisher is displayed also on the Fire control unit UE02.
When the fire extinguisher is activated by the thermal switch or the manual tripping device,
Linie 1 is active.
In case of an activation the alarm must be reset on this controller with the reset button.
Via the operation off switch the fire extinguisher system can be switched off.
In this case the temperature chamber cannot be used for a test.
The SH-WAD gas detection units are located behind the glass door on the left side of the
temperature chamber.
The SH-WAD unit is a wall mount model, suction type, gas detection unit equipped with
integrated membrane pump to draw in the air/gas mixture, and designed for the continuous
monitoring of these mixtures.
These units have a 2 fixed alarm levels and are connected to the safety controller.
When the alarm levels are reached a alarm will sound and the safety controller displays the
active alarm.
The gas sensors need to be calibrated every 6 months.
For more information about the gas detections see also the Operation Guide of the SH-
1003WAD.
2 product temperature sensors are installed in the test area of the temperature chamber.
These sensors can be placed on the product and will measure the temperature of the
product.
With the safety control display a max. allowed temperature increase can be set so when the
temperature is rising to fast the chamber will have an alarm and forced cooling is activated.
See 5.8. for the explanation of forced cooling.
The temperature increase can be set between 0,5 to 10°C/min.
On normal operation of the temperature chamber the temperature is controlled with the
temperature controller. This temperature controller will activate the cooling system or the
electrical heaters when needed.
When the set point of the chamber is <62°Cthe cooling system is always running.
In this case the electrical heater are used to control the chamber.
The forced cooling option will deactivate the electrical heaters so the chamber will cool
down automatically without changing this set point.
This option can be switched on with a button on the front of the chamber.
Forced Cooling can also be activated by the product temperature sensors.
When the temperature of the product will rise faster than the set point the forced cooling is
activated.
The temperature chamber is equipped with an electric mechanical door lock and 2 manual
door locks.
The electric mechanical door lock will lock the door when the chamber is switched off, while
running and in case of an alarm.
The door can only be opened after a test when there is no alarm.
The mechanical door locks must always be locked before starting the chamber.
The chamber is equipped with a Air connection and Nitrogen connection for
flushing the test area and are located on the back of the chamber.
8mm Push-in connection.
These connection must be made before a test can be started.
Both connections have a pressure sensor that will give an alarm if the
pressure is too low.
Setting of pressure sensor: 1 Bar.
• Set the desired temperature at the control display of the temperature chamber or select a
program.
• Position the temperature sensors in the test room or on the test product and set the
required alarm parameters on the additional safety control display.
• Connect the release contact from the external charging station to the test chamber or
create a bridge across the appropriate terminals.
• Connect the potential-free alarm contact of the charging station to the test chamber or
create a bridge across the appropriate terminals.
• The test chamber can only be put into operation when the door handle is fully pushed.
• Start the selected program on control display of the temperature and humidity chamber.
• The chamber stops and the test area will be flushed with N2 for the amount of time that is
set on the safety control display.
• After flushing the door lock is released and the door can be opened.
Reset Procedure:
- Push/Pull Emergency switch.
- Use Key switch.
- Push acknowledge/reset
button >2sec.
- Explosion vent activated. - Chamber controller switching ALARM EMERG.STOP/
off. ALARM EXPL.VENT.
- Red light flashing. ESPEC & CHARGER
- Pulse tone. **EMERGENCY OFF **
Reset Procedure:
- Push/Pull Emergency switch.
- Use Key switch.
- Push acknowledge/reset
button >2sec.
- Alarm product sensor 1. - Red light flashing. S1 FORCED COOLING.
- Pulse tone. **CHARGER STOP**
- Heater is switched off.
Reset Procedure:
- Cool down the chamber.
- Push acknowledge/reset
button >2sec.
- Alarm product sensor 2. - Red light flashing. S2 FORCED COOLING.
- Pulse tone. **CHARGER STOP**
- Heater is switched off.
Reset Procedure:
- Cool down the chamber
- Push acknowledge/reset
button >2sec.
Reset Procedure:
- Push acknowledge/reset
button >2sec.
- CO Alarm 1. - Chamber stays in operation. WARNING CO ALARM 1
Sensor range: 0-200ppm. - Orange light flashing. **CHARGER STOP**
Alarm 1 at: 25%. - Constant tone.
Reset Procedure:
- Push acknowledge/reset
button >2sec.
- CO Alarm 2. - Orange light flashing. CO GAS ALARM 2
Sensor range: 0-200ppm. - Constant tone. **CHARGER STOP**
Alarm 2 at: 50%.
Reset Procedure:
- Push acknowledge/reset
button >2sec.
- H2 Error. - Chamber stays in operation. ERROR GAS DETECTION
- Orange light flashing. **CHARGER STOP**
- Constant tone.
Reset Procedure:
- Push acknowledge/reset
button >2sec.
- H2 Alarm 1. - Chamber stays in operation. SYSTEM ACTIVE
Sensor range: 0-4 vol%(LEL) - Compressed air will flush for
Alarm 1 at: 25%. 120 sec.
Reset Procedure:
- Use Key switch.
- Push acknowledge/reset
button >2sec.
Reset Procedure:
- Use Key switch.
- Push acknowledge/reset
button >2sec.
Reset Procedure:
- Push/Pull Emergency switch.
- Use Key switch.
Push acknowledge/reset button
>2sec.
- Batec Fault. - Chamber stays in operation. FAILURE FIRE EXT.
- Orange light flashing. **CHARGER STOP**
- Constant tone.
Reset Procedure:
-Push acknowledge/reset
button >2sec.
- Batec OFF. - Chamber stops operation ALARM EMERG.STOP
- Red light flashing. ALARM FIRE EXTING.
- Pulse tone. ESPEC & CHARGER
*EMERGENCY OFF**
Reset Procedure:
- Push/Pull Emergency switch.
- Use Key switch.
- Push acknowledge/reset
button >2sec.
- Pressure Nitrogen. - Orange light flashing. FAILURE NITROGEN
Alarm setting: 1 Bar - Constant tone. **CHARGER STOP**
Reset Procedure:
- Push acknowledge/reset
button >2sec.
- Pressure Air. - Orange light flashing. FAILURE AIR SUPPLY
Alarm setting: 1 Bar - Constant tone. **CHARGER STOP**
Reset Procedure:
- Push acknowledge/reset
button >2sec.
The alarm sound is automatically switched off after 10 minutes. The alarm light stays on.
With a long press (> 2 sec.) on the acknowledgment button all active alarms are cleared (to
confirm it sounds once), active messages are still displayed.
When the emergency stop switch is used or the explosion vent has activated the emergency
relay. This must be reset with the key switch located on the front of the chamber.
The status display is only informative, operating conditions are displayed together with
indicator lights.
The exact assignment of the control inputs and outputs can be found in the attached circuit
diagram.
• In operating mode, the display shows the time and the switching states of the digital inputs
and outputs.
• Warnings and error messages in text, displayed alternating with the messages on the
display. Several active faults are displayed in sequence.
Changeable parameters can be selected in the display mode using the arrow keys.
The release for changing a parameter is done with the OK button to flash the value starts to
change.
The flashing value can be changed using the arrow keys within the specified limits.
The confirmation of the settings is done by pressing the OK button.
When there is no key input for 5 minutes or by pressing the ESC key, the controller will
return to the status page.
123456789ABCDEFG
Status display
123456789A
15:30
Other parameters of
the chamber data
>>>Menu 2 Manual
A-button pressed 2 times
Offset and Flush Time
Delays Button B Nitrogen: 60 sec
>>Press Button B (30-3600 Seconds)
Other parameters of
the chamber data
123456789ABCDEFG
123456789A
15:30
To trigger the flushing, the next keys must be pressed simultaneously: and
When using this combination the electric door lock will be deactivated.
The chamber can be controlled with the software of the charger system.
For more info see the manual of the charge system.
The temperature and humidity chamber has several options to connect the charger.
In cause of an emergency the charger and chamber can be stopped.
The charger will be stopped in the following situation:
- Emergency stop button is pressed.
- Explosion vent is activated.
- CO or H2 Gas detection.
- The Espec chamber has an alarm.
The contact is located on Terminal X5-17 and X5-18 of the electric panel.
For other possible connections see the wiring diagram.