You are on page 1of 20

Electronic Panel Meters

DIGEM – Preference Program


– Process control, automation & laboratory uses
– Class 0.01 to 1
– Current, Voltage, Frequency, Temperature, RPM,
Pressure, etc.
– LED/ LCD displays
– Display 1999 to 99999 digits (31/2 to 5 digits)
– DIN 43700 panel mounting cases
Electronic

5
Panel Meters

AK

BK
B5
24

24

24
Process control, automation &

x
48

96

96
laboratory uses

M
GE

GE

GE

GE
DI

DI

DI

DI
This catalogue gives you an overview Type A1125 A1375 A1275 A1215
of our preference program. You have Mechanical Data* Page 4 5 6 7
a selection from a complete program
of electronic panel meters. Front panel dimensions / mm 48 x 24 96 x 24 96 x 24 96 x 24
Panel cutout / mm 45 x 22.5 92 x 22.2 92 x 22.2 92 x 22.2
The modern product palette is care-
Installation depth / mm 93 126 141 72
fully selected on the requirements of
measurement and display technolo- Display (7 Segments)
gies, systems design and assembly Display colour red / green red red / green red / green
technologies. Character heigh / mm 8 14 14 14
GOSSEN Müller & Weigert panel – 1.999 ...1.999 (31/2 digits) • • •
meters fulfil all requirements of the – 1.999 ...9.999 (4 digits) •
European EMC guidelines without any – 19.999 ...19.999 (41/2 digits) opt. •
restrictions.
– 19.999 ...32.765 (43/4 digits)
You receive invariable high quality – 19.999 ...99.999 (5 digits)
products that are constantly controlled
Display range programmable opt.
by a strict quality control system.
Decimal point programmable opt.
Inputs
Measurement range card • •
Amount of measurement ranges 1 1 1 max. 4
Selection with Jumper
Programmable
Measuring Functions
DC voltage / DC current •/• •/• •/• •/•
0 ... 20 mA / 4 ... 20 mA •/• •/• •/• •/•
AC voltage / AC current •/• •/•
TRMS voltage / RMS voltage •/ – •/ –
TRMS current / RMS current •/ – •/ –
Frequency / Pulse counter
Thermocouple / Pt100 – /• – /•
RPM
Pressure
Outputs
Analog output
Comparator
Limit values (Relay)
BCD 5 V / 24 V (isolated)
Interface RS232 / RS485
Transducer power supply (only for 4 ... 20 mA) • •
Power Supply
DC 5 V isolated / not isolated – /•
DC 24 V / 18 ... 36 V •/• •/• – /• •/ –
DC 9 ... 60 V / 90 ... 260 V – /•
AC 230 V / 115 V •/ –
AC 24 V / 90 ... 230 V •/ – •/• •/•
AC 230 / 115 V & DC 18 ... 36 V
Miscallaneous functions
Blanking control • •
Segment test • •
Storage • • •
DATA logging

*Compulsory dimensional drawing on request

2
B5
F5

F5

5
5

C5
SN
AK

CK
B5

A5

B5
S5

72
24

24

48

48

48

48

48

48

38

38
4x
x

x
96

96

96

96

96

96

96

96

14

62

62
EM

M
GE

GE

GE

GE

GE

GE

GE

GE

GE

GE
DI

DI

DI

DI

DI

DI

DI

DI

DI

DI
A1235 A1245 A1385 A1065 A1225 A1255 A1265 A1005 A1155 A1175
8 9 10 11 12 13 14 15 16 17
96 x 24 96 x 48 96 x 48 96 x 48 96 x 48 96 x 48 96 x 48 144 x 72 62 x 38 62 x 38
92 x 22.2 92 x 45.5 92 x 45 92 x 45 92 x 45 92 x 22.2 92 x 45 138 x 68 60 x 36 60 x 36
143 143 126 130 130 143 130 145 26.5 33

red / green red red red / green red / green red / green red / green red / green red/green/ LCD red / LCD
14 14 14 14 14 14 / 20 14 20 14 / 12.7 10
• • • •

• •

• •
• • • • •
• • • • •

• • •
36 36 1 1 max. 4 9 1 or 2 1 1 1
Keys, SW Keys, SW DIP / MR Jumper Keys
• •

•/• •/• •/• •/• •/• •/• •/• •/• •/• •/•
•/• •/• •/• •/• •/• •/• •/• •/• •/•
•/• •/• •/• •/• •/• •/• •/•
•/ – •/ – •/• •/ – •/ –
•/ – •/ – •/• •/ – •/ –
•/ – •/• •/•
•/• •/• – /• •/• •/• – /•

• • • • •
2 2
opt. max. 4 2 max. 4 4
•/•
•/ – •/• •/• •/•
• • •

– /• – /•
•/• – /• •/ – •/ – – /• – /• – /• (opt.)
– /•
•/• •/• •/• •/• •/• •/•
•/ – •/ – •/ – •/ – •/• •/ –
• • •

• •
• • • (LED)
• • • • opt. • • • •
• •

Subject to change without notice

3
The DIGEM 48 x 24 AK5 panel meter With measurements of 48 mm x 24
DIGEM 48 x 24 AK5 is a 31/2 digits display whose casing
was especially developed for grid
mm, this instrument can be fitted into
practically any grid.
Digital Indicators for Grid and applications.
Mosaic Applications Installation in a control desk is possible
The included mounting elements because of the shallow installation
Type A1125 allow for installation into all known depth of less than 100 mm.
24 mm grid systems. With the use of coded jumpers and a
❖ Display range ± 1 999 digits, The instrument has a display range of potentiometer, it is possible to adjust
Optionally ± 19 990 digits ± 1 999 digits, which can optionally the display range of the instrument.
❖ Bright LED-Display with 8 mm be extended to ± 19 990 digits by
character height The same method can be used to set
setting an additional digit hardwired
❖ Single standard mounting elements the starting point of the measuring
to zero.
for all grid types range.
❖ Suitable for installation into all Decimal points are permanently set This model is especially suited for
known grid configurations in the instrument, by means of solder display originating from measurement
❖ Extremely easy installation bridges at the display, in accordance transducers.
❖ Power supply electronically with the entries on the serial plate.
separated from measurement
circuit, 500 V test voltage

Characteristic Values, DIGEM 48 x 24 AK5


Display Power Supply Ambient Conditions
Type 7 Segment LED 18 ... 36 V DC Operating Temperature 0 ... + 50 °C
Display Colour red, optionally green 24 V AC 50 / 60 Hz Storange Temperature – 20 ... + 70 °C
Character Height approx. 8 mm Relative Humidity max. 85 %
A-D Conversion
Display Range – 1 999 ... 1 999 Contamination Level 2
Conversion Method dual slope
option: ± 19 990 Surge Voltage Category II
Integration Time approx. 100 ms
Polarity ”–“ is displayed automatically
Measurements / 3: Response time for the Casting
Decimal Point fixed
second, typical overall instrument is Protection front panel: IP 50
Overflow Display ”1 ...“
greater depending upon rear panel: IP 20
Measuring Ranges the filter at the Bezel black matt; optionally
Direct Voltage ± 200 mV to ± 50 V measuring input. grey, pebble grey or
Direct Current ± 200 µA to ± 200 mA It amounts to approx. light grey
Error Limits ± (0,05 % + 2 digits) 1 second. Installation Depth max. 98 mm
[with option: ± 19 990 (without connector)
± (0,05 % + 20 digits)] Weight 0.11 kg
Error Limits < 100 ppm / °C Terminals screw terminal blocks
Offset Drift < 0,2 digits / °C
Warm-up Time approx. 1 min.

4
The modular DIGEM 96 x 24 B5 digital The lower and upper display range
indicator is a high precision panel
meter with a programmable display
values can be adjusted with the keys
on the front of the panel.
DIGEM 96 x 24 B5
range.
4 Place Digital Indicator
The selected parameters can be pro- Type A1375
The instrument can be used for multi- tected from unauthorised adjustments
ple measuring tasks, depending upon through an external contact on the
the installed measuring module. back of the instrument.
These tasks include: ❖ Front panel dimensions 96 x 24 mm
Each instrument is equipped with a
❖ Display range – 1 999 … 9 999
❖ Direct voltage control input which allows for the
❖ Optimally adaptable to respective
❖ Direct current storage of display values to memory,
❖ Alternating voltage and which freezes the current display. measuring tasks through measuring
❖ Alternating current The measuring cycle is not influenced modules
❖ Programmable, configuration
❖ Temperature by this function.
extremely easy
The display range and decimal point In the case of the non-programmable ❖ Power supply electronically isolated
can easily be adjusted for the respec- variant, the settings are preset at from measuring circuits
tive measuring tasks. manufacturing time. It is thus only ❖ Also available with auxiliary power
possible to make subsequent changes for 2-wire measuring transducers
It is also possible to make subsequent
at the factory. ❖ Quick installation with mounting tab
adjustments on site.
❖ Also available as non-programmable
The unit of measure for the measured
The measured values are processed instrument
quantity is indicated with a small tab
by a microcomputer and displayed on
that is inserted into a pocket behind
a 7-segment display unit.
the faceplate.
This can be inserted after installation.

Characteristic Values, DIGEM 96 x 24 B5


Display Alternating Voltage 0 ... 700 V Ambient Conditions
Type 7 Segment LED Alternating Current 0 ... 200 mA, 0 ... 1 A / 5 A Operating Temperature 0 ... + 50°C
Display Colour red TRMS Voltage 0 ... 700 V Storage Temperature – 20 ... + 70°C
Character Height 14 mm TRMS Current 0 ... 200 mA, 0 ... 1 A / 5 A Contamination Level 2
Display Range – 1 999 ... 9 999 Crest Factor 6 (additional 0,5 % of Overvoltage Category II
Polarity “–“ is displayed automatically reading)
Casing
Decimal Point programmable or fixed Temperature Pt100
Protection front panel: IP 54
Overflow Display blinking – top dash – 200 ... + 800 °C
rear panel: IP 20
Measuring Ranges Power Supply Front Panel frame color black
Direct Voltage ± 60 mV to ± 300 V 90 ... 230 V AC 50 / 60 Hz Weight 0.21 kg
Direct Current ± 2 mA to ± 200 mA and 90 ... 260 V DC Installation quick mounting tabs
0 ... 20 mA or Terminals screw terminal blocks
4 ... 20 mA with power 24 V AC 50 / 60 Hz
supply for 2-wire transducer and 18 ... 36 V DC

5
The digital display measuring instru- The DIGEM 96 X 24 BK5 consists of a
DIGEM 96 x 24 BK5 ment, DIGEM 96 X 24 BK5 is suited
for general use in industrial environ-
precision DC voltmeter that can be
adjusted to the required measuring
3.5 or 4.5 Place Digital ments and is optimally equipped for task by the installed measuring
Indicator with LED Display the respective measurement tasks by module.
Type A1275 means of modules on the measuring
A suitable measuring module is fitted
inputs.
to each instrument. This is detailed on
❖ Front panel dimensions 96 x 24 mm This instrument series contains the serial plate.
❖ Red or green LED display, modules for the following measure-
The power supply is electronically
14 mm high ment tasks:
isolated from the measuring circuit and
❖ Max. display range, depending on ❖ Direct current and voltage amounts to, depending on the model,
model, ± 1 999 and ± 19 999 measurements 90…230 V AC or 18…36 V DC /
❖ Can be optimally adapted to ❖ Direct current 4 … 20 mA with 24 V AC.
required measurement task with auxiliary power for 2-wire
various measurement modules The extra functions, display hold,
measuring transducers
❖ Power supply is electronically segment test and brightness control
❖ Alternating current and voltage
isolated from measuring circuit are all included in each instrument.
measurements, sinusoidal
❖ Also available with auxiliary power The inputs for the control of these
❖ Alternating current and voltage
for 2-wire measuring transducers functions are electronically connected
measurements, TRMS to the meter input.
❖ Temperature measurements

Characteristic Values, DIGEM 96 x 24 BK5


Display Alternating Voltage 0 ... 2 V to 0 ... 250 V Ambient Conditions
Type 7 Segment LED TRMS Voltage 0 ... 2 V to 0 ... 250 V Operating Temperature 0 ... + 50 °C
Display Colour red, optionally green Alternating Current 0 ... 200 mA, 0 ... 1 A / 5 A Storage Temperature – 20 ... + 70 °C
Character Height 14 mm TRMS Current 0 ... 200 mA, 0 ... 1 A / 5 A Relative Humidity max. 85%
Display Range 3 1/2 digit ± 1 999 Temperature Pt100 Contamination Level 2
4 1/2 digit ± 19 999 – 50 ... 199,9°C Overvoltage Category II
Polarity “–“ is displayed automatically and
Casing
Decimal Point internally fixed – 200 ... 800°C
Protection front panel: IP 50
Overflow Display 3 1/2 digit: “1....“
Power Supply rear panel: IP 20
4 1/2 digit : display blinking
90 ... 230 V AC 50 / 60 Hz Material polycarbonate
Measuring Range or Bezel black, optionally grey,
Direct Voltage ± 60 mV to ± 300 V 18 ... 36 V DC / 24 V AC light grey or pebble
Direct Current ± 2 mA to ± 200 mA grey
0 ... 20 mA Installation Depth max. 141 mm
4 ... 20 mA with power Weight max. 0.22 kg
supply for 2-wire transducer Installation Metal slider
Terminals screw terminal blocks
option: flat plug

6
The DIGEM 96 x 24 S5 is a high The display range pre-selection is
precision panel meter, ideally suited for
use in the DC Current tasks (option D)
accomplished by means of clearly
arranged coded jumpers at the back of
DIGEM 96 x 24 S5
or the DC Voltage tasks (option S). the case.
3.5 Place Digital Indicator
with LED Display
The available measurement ranges The zero point and final value can be
consists of standard signals, so that adjusted with a potentiometer Type A1215
stock keeping can be reduced. The instrument can optionally be
❖ Front panel dimensions 96 x 24 mm
This universal implementation indi- supplied with a brightness control and
❖ Red or green LED display,
cator can be interfaced with different a HOLD-digital signal.
auxiliary power supplies. 14 mm high
❖ Measurement ranges changeable
The casing has a very shallow installa- via jumpers
tion depth, even at a power supply of ❖ Zero point and final value adjustable
230 V AC. ❖ IP 54 protection at front panel
❖ Installation depth 72 mm

Characteristic Values, DIGEM 96 x 24 S5


Display Measuring Ranges Ambient Conditions
Type 7 Segment LED Option S: Operating Temperature 0 ... + 50 °C
Display Colour red, optionally green Direct Voltage 0 ... 200 mV Storage Temperature – 40 ... + 80°C
Character Height 14 mm 0 ... 2 V Relative Humidity max. 85%
Display Range 3 1/2 digit ± 1 999 0 ... 20 V Contamination Level 2
Polarity “–“ is displayed 0 ... 200 V Overvoltage Category II
automatically Option D:
Casing
Decimal point fixed Direct Current 0 ... 2 mA
Protection front panel: IP 54
Overflow Display “1 ...“ 0 ... 20 mA
rear panel: IP 20
4 ... 20 mA
Bezel black
0 ... 200 mA
Installation Depth 72 mm
Power supply
Weight max. 0.21 kg
230 V AC 50 / 60 Hz
Installation srew clamp
24 V DC
Terminals screw terminal blocks
5 V DC not isolated

7
The DIGEM 96 x 24 MF5 is a very The DIGEM 96 x 24 MF5 is equipped
DIGEM 96 x 24 MF5 compact DIN size instrument.
The wide range of additional functions
with the following functions:
5 Place Digital Indicator built in to the DIGEM 96 x 24 MF5
❖ Scalability of the display with
with Limit Values and Outputs internally stored functionality
makes this a universal instrument for ❖ Analog output
Type A1235 high performance automation and ❖ Measurement value assessment
measurement tasks. ❖ Display formation
❖ Front panel dimensions 96 x 24 mm The instrument can be used for ❖ Alarm configuration
❖ Red LED display, 14 mm high multiple measuring tasks, depending ❖ DATA logging
❖ Free scalable measurement ranges upon the chosen equipment. ❖ Cascading and LOOP operation
❖ Up to 2 open collector outputs These tasks include: The instrument is designed for applica-
❖ Analog output ❖ Direct voltage tions that require monitoring and eval-
❖ RS232 Interface ❖ Direct current uation of measurement values, as well
❖ IP 54 protection at front panel ❖ Alternating voltage as forwarding via analog output or
❖ Alternating current serial interface. This also includes 2
❖ Temperature limit values that can be distributed
over the measurement range.
The display range and decimal point
can easily be adjusted for the respec-
tive measuring tasks, and is freely
scalable. It is also possible to make
subsequent adjustments on site.
The operation and parameterisation of
the instrument can be adjusted with
two keys, or through the interface
with the supplied PC-Software.

Characteristic Values, DIGEM 96 x 24 MF5


Display Temperature Pt100 Ambient Conditions
Type 7 Segment LED – 200 ... + 850 °C Operating Temperature 0 ... + 50 °C
Display Colour red Connection type: 2, 3 or 4 wire Storage Temperature – 40 ... + 80 °C
Character Height approx. 14 mm Thermocouples: Relative Humidity max. 85%
Display Range – 19 999 ... 99 999 Type B, E, J, K, L, N, R, S, T, U Contamination Level 2
Polarity “–“ is displayed – 260 ... + 1820 °C Overvoltage Category II
automatically Shearing pin available
Casing
Decimal Point programmable
Interface Protection front panel: IP 54
Overflow Display programmable, blinking
Limit value: 2 open collector rear panel: IP 20
Measuring Ranges Analog output: max. Bezel black
Direct Voltage ± 200 mV to ± 650 V Resolution 4050 steps Installation Depth 143 mm
Direct Current ± 20 mA to ± 200 mA RS232 Weight 0.22 kg
0 ... 20 mA; 4 ... 20 mA Installation screw clamp
Power Supply Terminals screw terminal blocks
Alternating Voltage 0 ... 650 V
230 V / 115 V AC 50 / 60 Hz direct screw terminals
Alternating Current 0 ... 200 mA
and 18 ... 36 V DC (Measurement input)
Wide range power supply

8
The DIGEM 96 x 48 MF5 is a very The DIGEM 96 x 48 MF5 can optio-
convenient DIN-size display instrument. nally be equipped with the following
The wide range of extra functions built functions:
DIGEM 96 x 48 MF5
in to the DIGEM 96 x 48 MF5 makes
5 Place Digital Indicator
❖ Scalability of the display with inter-
this a universal instrument for high with Limit Values and Outputs
nally stored functionality
performance automation and measure- ❖ Analog output Type A1245
ment tasks. ❖ BCD output
The instrument can be used for multi- ❖ Measurement value assessment ❖ Front panel dimensions 96 x 48 mm
ple measuring tasks, depending upon ❖ Display formation ❖ Red LED display, 14 mm high
the chosen equipment. ❖ Alarm configuration ❖ Free scalable measurement ranges
These tasks include: ❖ DATA logging ❖ Up to 2 open collector outputs and
❖ Cascading and LOOP operation optionally 4 Relays
❖ Direct voltage
❖ Analog output
❖ Direct current The instrument is designed for appli-
❖ RS232 or RS485 Interface
❖ Alternating voltage (TRMS) cations that require monitoring and
❖ IP 54 protection at front panel
❖ Alternating current (TRMS) evaluation of measurement values, as
❖ Temperature well as forwarding via analog
output or serial interface. This also
The display range and decimal point
includes 4 limit values that can be
can easily be adjusted for the respec-
distributed over the measurement
tive measuring tasks, and is freely
range and freely assigned to the
scalable.
output variables.
It is also possible to make subsequent
adjustments on site.
The operation and parameterisation of
the instrument can be adjusted with 2
or 4 keys, or through the interface
with the supplied PC-Software.

Characteristic Values, DIGEM 96 x 48 MF5


Display Temperature Pt100 Ambient Conditions
Type 7 Segment LED – 200 ... + 850 °C Operating Temperature 0 ... + 50 °C
Display Colour red Connection type: 2, 3 or 4 wire Storage Temperature – 40 ... + 80 °C
Character Height approx. 14 mm Thermocouples: Relative Humidity max. 85%
Display Range – 19 999 ... 99 999 Type B, E, J, K, L, N, R, S, T, U Contamination Level 2
Polarity “–“ is displayed autom. – 260 ... + 1820 °C Overvoltage Category II
Decimal Point programmable Shearing pin available
Casing
Overflow Display programmable, blinking
Interface Protection front panel: IP 54
Measure Ranges Limit value: max. 4 relays (opt.) rear panel: IP 20
Direct Voltage ± 200 mV to ± 650 V or 2 open collector outputs Bezel black
Direct Current ± 20 mA to ± 200 mA Analog output: Installation Depth 143 mm
0 ... 20 mA; 4 ... 20 mA max. Resolution 4050 steps Weight 0.38 kg
Alternating Voltage 0 ... 650 V RS232 or RS485 Installation screw clamp
Alternating Current 0 ... 200 mA Terminalls screw terminal blocks
TRMS Measurement Crest factor 4 (max. peak Power Supply
direct screw terminals
values + 50 % of measure- 230 V / 115 V AC 50 / 60 Hz
(Measurement input)
ment value) Frequency 18 ... 36 V DC / 24 V DC
influence: 5 ... 5000 Hz 18 ... 36 V DC and 230 V / 115 V AC
– 0,1 % to max. – 5 % Wide range power supply

9
The modular DIGEM 96 x 48 B5 The measured values are processed
DIGEM 96 x 48 B5 installation measurement instrument
is extremely easy to program.
by a microcomputer and displayed on
a 7-segment display unit.
4 Place Digital Indicator
Type A1385 The instrument can be used for Upper and lower display range values,
multiple measuring tasks, depending relay switching performance, limit
upon the installed measuring module. values and hysteresis can all be
These tasks include: adjusted with the front panel keys.
❖ Front panel dimensions 96 x 48 mm ❖ Direct voltage The selected parameters can be
❖ Display range – 1 999 … 9 999 ❖ Direct current protected against unauthorised
❖ Can be optimally adapted to ❖ Alternating voltage alteration with an external contact at
required measurement task with ❖ Alternating current the back of the instrument.
various measurement modules ❖ Temperature
❖ Two separately adjustable limit If limit values need to be adjusted
values (option) The display range can be adapted for during operation, protection can be
❖ Extremely easy programming the 4 … 20 mA and 0 .. 20 mA disabled.
❖ Power supply is electronically measuring ranges without a calibrator, Each instrument is equipped with a
isolated from measuring circuit even after installation of the instru- control input which allows for the
❖ Also available with auxiliary power ment. storage of display values to memory,
for 2-wire measuring transducers The measuring instrument is thus also and which freezes the current display.
❖ Casing suitable for grid mounting suitable for applications that require The measuring cycle is not influenced
❖ Quick installation with mounting frequent, on-site adjustments to the by this function.
slider display.
The DIGEM 96 x 48 B5 is a high
precision DC voltmeter, which is
adapted to the required measuring
task by the installed measuring
module.

Characteristic Values, DIGEM 96 x 48 B5


Display Alternating Voltage 0 ... 2 V to 0 ... 700 V Ambient Conditions
Type 7 Segment LED Alternating Current 0 ... 200 mA, 0 ... 1 A / 5 A Operating Temperature 0 ... + 50 °C
Display Colour red TRMS Voltage 0 ... 700 V Storage Temperature – 20 ... + 70 °C
Character Height 14 mm TRMS Current 0 ... 200 mA, 0 ... 1 A / 5 A Contamination Level 2
Display Range – 1 999 ... 9 999 Crest factor 6 (additional 0,5 % of Overvoltage Category II
Polarity “–“ is displayed automatically measurement value)
Casing
Decimal Point programmable Temperature Pt100
Protection front panel: IP 54
Overflow Display blinking – top dash – 200 ... + 800 °C
rear panel: IP 20
Measuring Ranges Power Supply Bezel black
Direct Voltage ± 60 mV to ± 300 V 230 V / 115 V AC 50 / 60 Hz Weight 0.3 kg
Direct Current ± 2 mA to ± 200 mA or Installation quick mounting tabs
and 18 ... 36 V DC / 24 V AC Terminals screw terminal blocks
0 ... 20 mA
4 ... 20 mA with power
supply for 2-wire transducer

10
Display ranges can easily be adjusted Display range pre-selection is
with coded jumpers and potentio-
meter.
accomplished by means of clearly
arranged coded jumpers inside the
DIGEM 96 x 48 AK5
instruments.
3.5 Place Digital Indicator
These measuring instruments can be Type A1065
used for all industrial applications The corresponding potentiometers for
thanks to their robust metal casings. fine adjustment can be accessed by
Measuring ranges are preset at the removing the display filter from the
factory in accordance with the respec- front panel. ❖ Robust metal casing
❖ Power supply electrically isolated
tive measuring task. These measuring instruments are thus
suitable for applications that require from measuring circuit
Depending on the model, the follo- ❖ Also available with auxiliary power
wing measuring ranges are available: on-site display range adjustments.
for 2-wire measuring transducers
❖ 4 … 20 mA with auxiliary power for Complete scaling within the ❖ Display range max. ± 1 999
2-wire measuring transducer 4 … 20 mA measuring range can be
❖ Direct current and direct voltage accomplished only with the standard
measurement 4 mA signal.
❖ Alternating voltage measurement
❖ Alternating current measurement in
combination with current transformer
❖ Temperature measurement
❖ Frequency measurement

Characteristic Values, DIGEM 96 x 48 AK5


Display Alternating Voltage 0 ... 199,9 V; 0 ... 700 V Ambient Conditions
Type 7 Segment LED TRMS Voltage 0 ... 100,0 V; 0 ... 700 V Operating Temperature 0 ... + 50 °C
Display Colour red, optionally green Alternating Current Storage Temperature – 20 ... + 70 °C
Character Height approx. 14 mm through current 0 ... 1 A / 5 A Relative Humidity max. 85 %
Display Range ± 1 999 transformer Contamination Level 2
Polarity “–“ is displayed automatically TRMS Current 0 ... 1 A / 5 A Overvoltage Category II
Decimal Point internally adjustable Frequency 0 ... 500,00 Hz
Casing
Overflow display blinking – top dash Temperature Pt100
Protection front panel: IP 40
0 ... 199,9 °C
Measuring Ranges rear panel: IP 20
and
Direct Voltage ± 200 mV to ± 300 V Bezel black
– 200 ... 800 °C
± 60 mV; ± 150 mV Weight 0.4 kg
Thermocouples Typ J 0 ... 760 °C
and ± 300 mV Installation screw clamp
or
Direct Current ± 200 µA to ± 200 mA Terminals flat plug or
Typ K 0 ... 1260 °C
0 ... 20 mA screw terminal blocks
4 ... 20 mA with power supply Power Supply
for 2-wire transducer 230 V AC 50 / 60 Hz
115 V AC 50 / 60 Hz
24 V DC / AC

11
The DIGEM 96 x 48 MB5 is an Display and measurement range
DIGEM 96 x 48 MB5 overview display in DIN-casing that
allows for a wide measurement range
pre-selection is accomplished by
means of a DIP switch, placed at the
3.5 Place Digital Indicator for current and voltage. back of the case.
Type A1225
This instrument is available in two The decimal point and final values are
models: also adjustable with this DIP switch.
❖ as option F for direct voltage or The instrument can optionally be
❖ Front panel dimensions 96 x 48 mm ❖ as option AC for alternating voltage equipped with a HOLD digital signal.
❖ Red or green LED display, and alternating current
14 mm high
❖ Wide, freely selectable, setting range The final value of the display can be
❖ Decimal point and final value adjusted in range 1:10 for DC
adjustable measurements. This makes the
DIGEM 96 x 48 MB5 suitable for
many measuring tasks.
The wide setting range guarantees an
uncomplicated adjustment to the
measured variable.

Characteristic Values, 96 x 48 MB5


Display Measuring Ranges Ambient Conditions
Type 7 Segment LED Option F: Operating Temperature 0 ... + 50 °C
Display Colour red, optionally green Direct Voltage 0 ... 2 V Storage Temperature – 40 ... + 80 °C
Character Height 14 mm 0 ... 20 V Relative Humidity max. 85%
Display Range 3 1/2 digit ± 1999 0 ... 200 V Contamination Level 2
Polarity “–“ is displayed automatically 0 ... 500 V Overvoltage Category II
Decimal Point fixed Option AC:
Casing
Overflow Display “1 ...“ Alternating Voltage 0 ... 500 V
Protection front panel: IP 40
Alternating Current 0 ... 1 A
rear panel: IP 20
0 ... 5 A
Bezel black
Power Supply Installation Depth 130 mm
230 V / 115 V AC 50 / 60 Hz Weight max. 0.5 kg
24 V AC 50 / 60 Hz Installation screw clamp
24 V DC Terminals screw terminal blocks

12
The DIGEM 96 x 48 SN5 is a standard The display range and decimal point
display in DIN-casing that allows for a
wide adjustable measurement range
pre-selection is accomplished by
means of clearly arranged coded
DIGEM 96 x 48 SN5
for current and voltage. jumpers at the back of the case.
3.5 Place Digital Indicator
Type A1255
The DIGEM 96 x 48 SN5 is perfectly The initial and final values are adjust-
suited for interfacing with different able with potentiometers located at
auxiliary powers because of its wide the front of the instrument.
range power packs (option). ❖ Front panel dimensions 96 x 48 mm
❖ Red or green LED display
The final value can be adjusted in the
❖ Digit height: 14 mm or 20 mm
range 1:3. This feature, including the
❖ Wide, freely selectable, setting range
high level of protection, makes
❖ Decimal point and final value
measurement tasks in robust environ-
ments possible. adjustable
❖ Brightness control
❖ Zero point offset
❖ IP 54 protection at front panel

Characteristic Values, DIGEM 96 x 48 SN5


Display Measuring Ranges Ambient Conditions
Type 7 Segment LED Direct Voltage ± 1 V to ± 300 V Operating Temperature 0 ... + 50 °C
Display Colour red, optionally green Direct Current 0 ... 1 mA Storange Temperature – 40 ... + 80 °C
Character Height 14 mm or 20 mm 0 ... 20 mA Relative Humidity max. 85%
Display Range 3 1/2 digit ± 1999 0 ... 200 mA Contamination Level 2
Polarity “–“ is displayed automatically Overvoltage Category II
Power Supply
Decimal Point externally selectable
230 V / AC 50 / 60 Hz or Casing
Overflow Display “1 ...“
115 V / AC 50 / 60 Hz or Protection front panel: IP 54
24 V AC 50 / 60 Hz or rear panel: IP 20
18 ... 36 V DC and Bezel black
230 V/115 V AC 50 / 60 Hz Installation Depth 143 mm
Wide range power supply Weight max. 0.5 kg
Installation screw clamp
Terminals screw terminal blocks

13
❖ Automatic alignment at pressure These instruments can be equipped
DIGEM 96 x 48 CK5 ❖
measurement
Storage of min./max. measurement
for the following measurement tasks:
Digital Indicator with Limit values
❖ Direct current and voltage
Value and LED Display measurements
❖ Power supply is electronically ❖ Alternating current and voltage
Type A1265 isolated from the other circuits measurements
❖ Also available with auxiliary power ❖ Temperature measurements
for 2-wire measuring transducers ❖
❖ Front panel dimensions 96 x 48 mm Frequency and RPM measurements
❖ RS232 and RS485 interface
❖ Max. display range - 19 999 ❖ Pressure measurements
(optionally) ❖
to + 32 765 Pulse counter
❖ Analog output (optionally)
❖ Flexible through modular plug-in ❖ Display in cos ϕ
❖ Casing suitable for grid mounting
system ❖ Non-linear input quantities
❖ Easy adjustment The DIGEM 96 x 48 CK5 is a The instrument is optionally also
❖ As an option max. 4 limit values precision, modular panel meter. designed for applications which require
possible The instrument can be equipped with monitoring and evaluation of
❖ Adjustable to client specific a multitude of various measuring measurement values, as well as
characteristic curve modules for a variety of measuring forwarding these via analog output or
❖ Addition, subtraction of two tasks. serial interface.
measurement values
❖ Multiplication, division of two Scale graduations and set points are
measurement values easy to adjust with the keys at the
❖ Automatic TARE function front panel, even after the instrument
has been installed.
Furthermore, the extensive additional
functions expand the range of applica-
tions so that the measuring instru-
ments can be adapted optimally to
the required task.

Characteristic Values, DIGEM 96 x 48 CK5


Display Crest Factor 6 (additionally 0,5 % of Power Supply
Type 7 Segment LED Measurement value) 90 ... 230 V AC 50 / 60 Hz
Display Colour red, optionally green Temperature Pt100 90 ... 260 V DC or
Character Height approx. 14 mm – 200 ... + 800 °C 18 ... 36 V DC /
Display Range – 19 999 ... 32 765 – 328 ... + 1473 °F 24 V AC 50 / 60 Hz
Polarity “–“ is displayed Thermocouples Type J, K, R, S
automatically 0 ... + 1.600°C Ambient Conditionns
Decimal point programmable – 310 ... + 2 300 °F Operating Temperature 0 ... + 50 °C
Overflow Display blinking – top dash Resistance 0 ... 10 000 Ω Storage Temperature – 20 ... + 70 °C
Frequency 0 ... 200,00 kHz Relative Humidity max. 85 %
Measuring Ranges Resolution max. 0,1 Hz Contamination Level 2
Direct Voltage ± 60 mV to ± 300 V Pressure min. 2 mV / V Overvoltage Category II
Direct Current ± 2 mA to ± 200 mA max. 20 mV / V
0 ... 20 mA Casing
Pulse Counter up-counter, down-counter Protection front panel: IP 40
4 ... 20 mA with power
supply for 2-wire transducer Interface rear panel: IP 20
Alternating Voltage 0 ... 700 V Limit value: max. 4 relays Bezel black
Alternating Current 0 ... 200 mA; 0 ... 1 A / 5 A Analog output (optionally) Weight 0.9 kg
TRMS Voltage 0 ... 700 V Serial Interface (optionally) Installation mounting tabs
TRMS Current 0 ... 200 mA; 0 ... 1 A / 5 A RS232 or RS485 Terminals screw terminal blocks

14
The DIGEM 144 x 72 C5 is suited for The MESSCONTACTER model allows
applications that require more than
two limit values, or where simul-
for the configuration of four limit
values. Alarm messages are read out
DIGEM 144 x 72 C5
taneous use of outputs and interfaces via four relays. Alarms are also
Digital Indicator with Limit
is necessary. signalled with LED’s. Value and LED Display
The modular measuring input can be Additional features of this model Type A1005
equipped for the following measuring include.
tasks: ❖
❖ Adaptation to customer specific
Adjustable switching hysteresis
❖ Direct current and voltage ❖ Adjustable limit value time delay characteristic
❖ Modular connectors for flexible use
measurements ❖ Storage of an alarm message to
❖ Calibration and special functions can
❖ Alternating current and voltage memory
measurements be selected with keys
❖ Power supply electrically isolated
❖ Temperature measurements
❖ Frequency and RPM measurements from measuring circuit
❖ IP 54 protection at front panel
❖ Pulse counter
❖ Up to 4 limit values
❖ Display in cos ϕ
❖ Analog output (option)
❖ Non-linear input quantities ❖ Front panel dimensions: ❖ BCD output (option)
144 x 72 mm ❖ RS232 and RS485 (option)
❖ Red or green LED display interface
❖ Display range: ± 19 990 digits for ❖ Suitable for installation into grid
current and voltage measurement systems

Characteristic Values, DIGEM 144 x 72 C5


Display TRMS Voltage 0 ... 500 V Power Supply
Type 7 Segment LED TRMS Current 0 ... 200 mA; 0 ... 1 A / 5 A 230 V AC 50 / 60 Hz
Display Colour red, optionally green Crest Factor 6 (additionally 0,5 % of 115 V AC 50 / 60 Hz
Character Height approx. 20 mm Measurement value) 18 ... 36 V DC / 24 V AC
Display Range max. ± 19 999 Temperature Pt100
Ambient Conditions
Polarity “–“ is displayed – 200 ... + 800 °C
Operating Temperature 0 ... + 50 °C
automatically – 328 ... + 1 473 °F
Storage Temperature – 20 ... + 70 °C
Decimal Point programmable Resistance 0 ... 10 000 Ω
Relative Humidity max. 85 %
Overflow Display blinking – top dash Frequency 0 ... 200,00 kHz
Contamination Level 2
Resolution max. 0,1 Hz
Measuring Ranges Overvoltage Category II
Pulse Counter up-counter, down-counter
Direct Voltage ± 200 mV to ± 300 V
Casing
Direct Current ± 2 mA to ± 200 mA Interface
Protection front panel: IP 54
± 1 A; ± 2 A Limit value: max. 4 relays
Analog output (optionally) rear panel: IP 20
0 ... 20 mA; 4 ... 20 mA
BCD or analog Bezel black
Alternating Voltage 0 ... 500 V
Serial Interface (optionally) Weight 0.8 kg
Alternating Current 0 ... 200 mA
RS232 or RS485 Installation screw clamp
Terminals screw terminal blocks

15
Depending on the model, these
Accessories
DIGEM 62 x 38 A5 measuring instruments can be
equipped with a bright LED display or Power Packs for the
3.5 Place Digital Indicator a reflective LCD display. DIGEM 62 x 38 A5
with LED or LCD Display
The LCD is optionally available with Power Supply electrically isolated
Type A1155 additional illumination (transflective). from measuring
circuit
The instrument is suited for the
❖ Display range: ± 1 999 Test Voltage 500 V
measurement of direct current or
❖ Minimal installation depth of only Primary Voltage depending on
direct voltage.
26.5 mm model
❖ 5 V supply power Measuring and display ranges are 4.75 V ... 15 V DC
❖ Power pack available as accessory preset at the factory. or 18 ... 36 V DC
❖ Simple installation with snap The instrument requires a supply Secondary Voltage 5V±5%
fasteners voltage of 5 V that is electrically Load Capability max. 250 mA
connected to the measuring circuit. Residual Ripple < 200 mV
Power Consumption
Power packs for 18 V to 36 V DC and at Max. Load 3W
4.75 V to 15 V are available as
accessories. Terminals 14 pole plug
These power packs are snapped onto connector
the rear panel of the measuring
instrument.

Characteristic Values, DIGEM 62 x 38 A5


Display Mesuring Ranges Ambient Conditions
Type 7 Segment LED Direct Voltage ± 2 V to 200 V Operating Temperature 0 ... + 50 °C
with 14 mm character height and additionally ± 200 mV Storage Temperature – 20 ... + 70 °C
or LCD reflective Direct Current ± 200 µA to ± 200 mA Relative Humidity max. 85%
with 12.7 mm character height Auxiliary Power 5V±5%
Casing
Polarity “–“ is displayed
Protection front panel: IP 50
automatically
rear panel: IP 0
Decimal Poit externally adjustable
Installation snap mounting
or fixed
Terminals plug connector,
Overflow Display “1 ...“
appropriate plug
is included with
instrument

16
Depending on the model, these The power supply is 5 V ± 5 % and is
measuring instruments can be
equipped with a bright LED display or
electrically connected to the measu-
ring input.
DIGEM 62 x 38 B5
a reflective LCD display.
4.5 Place Digital Indicator
By removing a link, the measuring with LED or LCD Display
The instruments have been especially instrument can have a differential
equipped to meet the requirement of input, in which case no more than Type A1175
the equipment manufacturers. + 2 V may be applied between the
measurement input and the 0 V power ❖ Display range: ± 1 999
Connection is accomplished with a
supply terminal. ❖ Installation depth of max. 33 mm
14-pin plug connector.
❖ 5 V supply power
The required plug is included with the
❖ Simple installation with snap
instrument.
fasteners
The instrument has been designed for
the measurement of direct current and
direct voltage.
The measuring and display ranges are
preset at the factory in accordance
with the required measuring task.

Characteristic Values, DIGEM 62 x 38 B5


Display Measuring Ranges Ambient Conditions
Type 7 Segment LED Direct Voltage ± 2 V to 200 V Operating Temparature 0 ... + 50 °C
with 10 mm character height Direcz Current ± 200 µA to ± 200 mA Storage Temparature – 20 ... + 70 °C
or LCD reflective Auxiliary Power 5 V ± 5 % Relative Humidity max. 85%
with 10 mm character height
Casing
Polarity “–“ is displayed
Protection front panel: IP 50
automatically
rear panel: IP 0
Decimal Point externally adjustable
Installation snap mounting
Overflow Diplay blinking
Terminals plug connector,
appropriate plug
is included with
instrument

17
PRODUCT TABLE Sender:
To be copied, checked
and sent back
Fax: +49(0)911/3502-307

❖ Complete measurement family for


Product group current, voltage, power, power factor,
Analog Display frequency, bimetal current
measurements
Instruments ❖ DIN casing in square and
rectangular shape
❖ Changeable scales
❖ Subassembly and built-in devices

❖ For all heavy current and process


Product group variables
Measurement ❖ According to DIN EN 60688
Transducers ❖ Programmable, up to 4 outputs
❖ Class 0.5
❖ Compact style 22.5 / 100 mm
❖ Screw or DIN rail mounting

❖ Current, voltage, temperature and


Product group process
Digital Panel ❖ LED and LCD displays
Instruments ❖ 2 000 to 40 000 digits
❖ DIN size panel mounting housing
❖ 39 different device types

❖ Meets VDE 0701 / 0702 standards


Product group ❖ Panel mounting and portable
Electrical Equipment ❖ Analog or digital display
Tester ❖ Protective conductor resistance
❖ Insulation test
❖ Substitute leakage current
measurement / residual current

18
❖ For all electrical variables
Product group ❖ Pt 100 and Thermo elements
Indicator / Controllers ❖ 1 or 2 values
❖ Switching behaviour quiescent
current and load current principle
❖ 7 Casing sizes

❖ 4 Different versions
Product group ❖ 1 and 2 lines
Text Display / Printer ❖ 16 / 80 Characters
❖ Protocol printer
❖ Paper roll-up mechanism

❖ Analog and digital displays


Product group ❖ 1 and 2 measurement channels
Bargraph Displays ❖ Display flourescent or LED’s
❖ Up to 4 adjustable limit values
❖ Band display or printer indication
❖ Installation casing according to DIN

❖ Differential probes up to 1,5 kV


Product group ❖ Passive probes up to 450 MHz
Probes ❖ SMT probes and measuring
accessories
❖ Modular oscilloscope probes
❖ High voltage probe up to 40 kV
❖ HF and demodulation probes

❖ Current transformers class 0.5


Product group up to 2000 A
Accessories ❖ Shunt resistance according
to DIN 43703
❖ Measuring device switches
❖ Switch position indicators
❖ Power supplies

19
Datasheets and operating manuals
INTERNET
We look forward for the products introduced in this catalogue
to welcome you on can be found on our website at
our website.
Digital Panel Instruments.
Contact addresses can be found under
Agencies.

w. de
w.g -m
ww w .d e
o @ g- m
inf

2786700026 DRO 10.03 3.000

GOSSEN Müller & Weigert


Kleinreuther Weg 88 · D-90408 Nuremberg, Germany
Phone: +49(0)91135 02-0 · Fax: +49(0)91135 02-3 07
Internet: http://www.g-mw.de · e-mail: info@g-mw.de