Professional Documents
Culture Documents
DESCRIPTION
The 8 Channel Relay Module is specially designed to
expand the Output capability of the Det-Tronics Eagle
Quantum Premier® System.
LED INDICATORS
LEDs on the front panel of the relay module are
provided for indicating device status. The LED’s are
tested upon power-up to verify their operation.
FEATURES
The relay module has two LEDs for the device and
two LEDs for each channel. On the device level, one • Expands the output capabilities of the Det-Tronics
green LED indicates power, while the other amber Eagle Quantum Premier® system
LED indicates a LON communication fault. For each
channel, one red LED indicates channel activation • Individual channel LEDs indicate Active status
and the other amber LED indicates that the module • Provides remote output capabilities via LON/SLC
operating voltage is low or that the module has not
been configured (all eight channel LEDs blink). • Panel or DIN rail mounting
• Power LED display
MOUNTING • Plug-in wiring connectors
The relay module is DIN rail or direct panel mountable • RFI and EMI hardened (CE Marked)
for configurations requiring installation in NEMA or
• Programmable normally energized/de-energized
IP enclosures. DIN rail and mounting clip options
contacts
must be specified at the time of order. Refer to the
“Specifications” section for mounting arrangements and • Programmable failed state on loss of communication
dimensions. with controller (Fail on / Fail off / Hold last state).
SHIPPING WEIGHT— FM ®
1.35 2.5
(3.4) (6.4)
1 6 1 6 1 6 1 6
5.02
(12.7)
4.5
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 (11.3)
4.5
A B C A B C A B C A B C A B C A B C A B C A B C (11.3) A B C A B C A B C A B C A B C A B C A B C A B C
5.2
5.2 1.66 (13.2) 1.9
A2449 (13.2) (4.2) (4.8)
3.1 2 90-1181
INSTALLATION Connector P1, Terminals 1 to 6
24 Vdc Power Input
MOUNTING ENCLOSURE 1— +
2— –
The Relay Module must be properly installed in a 3 — Shield*
suitable enclosure that is rated for the location. The 4— +
enclosure must provide space to install and wire the 5— –
relay module and must also provide for ground wire 6 — Shield*
termination. Access into the enclosure must be gained
by using a special tool to open the enclosure. The *Shields on power wires are optional unless required
enclosure should be rated for the temperature range of by local codes.
the location plus the temperature rise of all equipment
installed inside the enclosure. The enclosure must Connect the module power supply to terminals 1 and
be rated for electrical equipment that is going to be 2. If additional terminals are required for powering
installed. other devices, these devices should be connected
to terminals 4 and 5. Shields are to be connected to
terminals 3 and 6 — chassis (earth) ground terminals.
NOTE
It is recommended to maintain a minimum of 4
Connector P2, Terminals 1 to 6
inches clearance between the module and other
LON Terminals
equipment to provide adequate room for wiring
and ventilation. Be sure to observe polarity when wiring the LON.
1 — “A” side of signaling circuit for COM 1
2 — “B” side of signaling circuit for COM 1
WIRING 4 — “A” side of signaling circuit for COM 2
All electrical connections are made to the field wiring 5 — “B” side of signaling circuit for COM 2
connectors furnished with the module. (Connectors 3 & 6 — shield connections (shields required).
accept up to a single 12 AWG wire.) Refer to Figure 2
for identification of module wiring terminals.
EQ3720RM
NC C 24
NO B 23 CHANNEL 8
SHLD 6 COM 2 SHLD COMMON A 22
LON FROM
B 5 COM 2 B
PREVIOUS DEVICE
A 4 COM 2 A NC C 21
NC C 15
NO B 14 CHANNEL 5
COMMON A 13
TO
EARTH
GROUND NC C 12
NO B 11 CHANNEL 4
COMMON A 10
NC C 9
NO B 8 CHANNEL 3
COMMON A 7
SHLD* 6 SHLD
24 VDC
– 5 – NC C 6
INPUT VOLTAGE
+ 4 + NO B 5 CHANNEL 2
SHLD* 3 SHLD COMMON A 4
24 VDC
– 2 –
INPUT VOLTAGE
+ 1 + NC C 3
POWER NO B 2 CHANNEL 1
COMMON A 1
* SHIELDS ON POWER WIRES ARE OPTIONAL
UNLESS REQUIRED BY LOCAL CODES. C2206
3.1 3 90-1181
Connectors P3 and P4 ORDERING INFORMATION
Unsupervised Output Ancillary Applications
(Unrelated to Fire Detection/Protection) When ordering, please specify:
Connect external wiring to the appropriate terminals on EQ3720RM 8 Channel Relay Module
the relay module terminal block. See Figure 2.
Options Panel Mount
CONFIGURATION DIN Rail Mount
Setting Relay Module Network Address For additional information or for assistance in designing
One unique network address must be assigned to a system to meet the needs of a specific application,
each relay module. The address is set by the 8 switch please contact:
DIP assembly on the relay module.
Detector Electronics Corporation
When using the switches located on the relay module, 6901 West 110th Street
the address is binary coded and is the sum of all Minneapolis, Minnesota 55438 USA
switches placed in the “closed” position. Operator: +1 (952) 941-5665 or +1 (800) 765-FIRE
Customer Service: +1 (952) 946-6491
Each discrete point of a relay module has a tag number Fax: (952) 829-8750
and a descriptor for unique identification. Web site: www.det-tronics.com
E-mail: det-tronics@carrier.com
Det-Tronics S3 Safety System Software is used
for device configuration. The following shows the
minimum software/firmware releases:
2.01 2.8.0.0
90-1181