RURAL ELECTRIFICATION AGENCY
PRE-COMMISSIONING REPORT
Dh pe iy ik
TOT 3A: CONSTRUCTION OF 33KV OVERHEAD LINE FROM THE
PROJECT NAME, EXISTING 132KV OPUYO-MOROTO LINE TOTALLING TO 465.06KM AND |
338.89KM OF LV OVERHEAD USING PRE-STRESSED COCRETE POLES- |
AND INSTALLATION 5400 LAST MILE CONNECTION.REA-IDBILWRKS/15-
1600299
EMPLOYER RURAL ELECTRIFICATION AGENCY
‘CONSULTANT ‘COLENCO CONSULTING NIGERIA.LTD. re
‘CONTRACTOR ‘CEYLEX ENGINEERING (PVT) LTD.
‘OPERATOR ‘UMEME LTD
LOCATION Scheme 16 CPabona Tr er)
"TRANSFORMER PARTICULARS ‘COMMENTS
MAKE LTL SRI LANKA a
TYPE (OIL IMMERESED TRANSFORMER
RATING (KVA) Boku &
SERIAL NUMBER Tod £ 244g
YEAR OF MANUFACTURE | 9.0/4
‘% IMPEDANCE, Asl4
NUMBER OF PHASES 3
RATED VOLTAGE PRIMARY (kV) SECONDARY (V)
a3 ASS
‘OIL LEVEL Max
‘TEST RESULTS ‘COMMENTS
INSULATION RESISTANCE | HV-LV(MOQ) | HV-E_ (M|LV-E (WO)
‘TEST 2)
2718 GA | 221 aa! oh
SURGE ARRESTORS Ro) YMo) [Boro
ow cs a
EARTH RESISTANCE TEST | AV @) Lv @),
212 Bie
NO LOAD OUTPUT PHASE-PHASE(V) _| PHASE-NEUTRAL (V)
VOLTAGE (46%) RY A26v RN 936v
RE 42eu YN 93av
YB 42av BN
FINAL TAP POSITION
FUSE RATING (A) PRIMARY | SECONDARY(C
cry
- 5A. £3A
WITNESSEDBY [CONTRACTOR | REA aa OPERATOR |
Bias. FT. @_ Ushoun ka
at
Date; 14 12020‘Te Brpe lily ink
RURAL ELECTRIFICATION AGENCY
PRE-COMMISSIONING REPORT
LOT 3A: CONSTRUCTION OF 33KV OVERHEAD LINE FROM THE
PROJECT NAME EXISTING 132KV OPUYO-MOROTO LINE TOTALLING TO 465.06KM AND
338.89KM OF LV OVERHEAD USING PRE-STRESSED COCRETE POLES
‘AND INSTALLATION 5400 LAST MILE CONNECTION.REA-IDBI/WRKS/15-
1600299
EMPLOYER RURAL ELECTRIFICATION AGENCY
‘CONSULTANT ‘COLENCO CONSULTING NIGERIA.LTD
CONTRACTOR ‘CEYLEX ENGINEERING (PVT) LTD.
‘OPERATOR UMEME LTD
LOCATION acemat id= CNaeallgn yr. Canteen 0!
"TRANSFORMER PARTICULARS ‘COMMENTS
MAKE LL SRI LANKA
TYPE ‘OIL IMMERESED TRANSFORMER
RATING (kVA) Bokve
‘SERIAL NUMBER TOO 1p_44qe
YEAR OF MANUFACTURE, 20g
% IMPEDANCE Beth
NUMBER OF PHASES 3
RATED VOLTAGE. PRIMARY (kV) SECONDARY (V)
ZS AS?
‘On LEVEL Max i
[ TEST RESULTS ‘COMMENTS
INSULATION RESISTANCE | HV-LV (MQ) HV-E (M | LV-E(MQ)
‘TEST 9)
2.65 Ga | 238eal hk
‘SURGE ARRESTORS RM™O) Yo) | B™o)
XL ak ol
EARTH RESISTANCE TEST | HV (Q) Lv)
be 7 2.1 SL
NO LOAD OUTPUT
PHASE-PHASE (V) PHASE-NEUTRAL (V)
VOLTAGE (6%) RY Apt v_ [RN Q40U
RB A224 V YN 288 0
YE 4pev [BN 240v
FINAL TAP POSITION
FUSE RATING (A) PRIMARY | SECONDARY(C | SECONDARY
cm ccr)
BA G3A ban z
WHINESSEDBY | CONTRACTOR ~_ [CONSULTANT OPERATOR
Name TG Ushemle nS
Designation BE ann
signature ates:
Date 4latao290