Medium voltage “SUPREME” cables are designed based on IEC 60502-2, SNI, SPLN
43-5 or others international standards upon request.
• CONDUCTOR
The conductor made from annealed copper wire, circular stranded com
pacted or round segmental compacted according to IEC 60228, BS 6360,
AS 1125 or SPLN41-1.
• CONDUCTOR SCREEN
The conductor screen made from extruded semi conductive compound.
• INSULATION
The conductor screen are covered with an extruded layer of XLPE
compound according to IEC 60502, AS 1429-1, BS 5464 or SPLN 41-9.
• INSULATION SCREEN
The insulation screen made from extruded semiconductive compound in
combination with the metallic screen. The metallic screen consist of
a layer of either copper tape or copper wires with copper tape binder.
• BEDDING/FILLER
The bedding and/or filler made from an layer of exruded PVC or
non-hygroscopic material which compatible with the insulation and
operating temperature of the cable.
• METALLIC SHEATH
The metallic sheath made from lead alloy material with kinds of grade
such as 1/2 C, E grade. The main function of lead sheath is to
protect the cable from physical deterioration caused by chemical liquid
such as sulfides , waste oil and to provide an impermeable water barrier.
• INNER SHEATH
The inner sheath made from a layer of extruded PVC ST2 type to IEC
60502-2 or YM/2 type to SPLN 41-2 , type 9 to BS 7655 or other
international standards.
• ARMOURING
The armouring made from either welded continuously aluminium
corrugated, galvanized round steel wire, double galvanized steel tape, round
aluminium wire or double aluminium tape.
Cables Construction 2
• OUTER SHEATH
The outer sheath made from a layer of extruded Polyethylene or PVC ST2
type to IEC 60502-2 or YM/2 type to SPLN 41-2 , type 9 to BS 7655 or
other international standards.
• Visual
• Dimensions
• Conductor resistance
1 Core
N2XSY/NA2XSY 1.8/3(3.6) IEC 60502-1 1
3.6/6(7.2) IEC 60502-2 2
6/10(12) IEC 60502-2 3
8.7/15(17.5) IEC 60502-2 4
12/20(24) IEC 60502-2/SPLN 43-5 5
18/30(36) IEC 60502-2 6
3 Cores
N2XSY/NA2XSY 1.8/3(3.6) IEC 60502-1 19
N2XSEY/NA2XSEY 3.6/6(7.2) IEC 60502-2 20
6/10(12) IEC 60502-2 21
8.7/15(17.5) IEC 60502-2 22
12/20(24) IEC 60502-2/SPLN 43-5 23
18/30(36) IEC 60502-2 24
Copper/Aluminium conductor,
XLPE insulated, N2XSY/NA2XSY
Copper wire/ tape screened, 1.8/3(3.6) kV
PVC/PE sheathed cable IEC 60502-1
Copper/Aluminium conductor,
N2XSY / NA2XSY
1.8/3(3.6) kV XLPE insulated,
IEC 60502-1 Copper wire/ tape screened,
PVC/PE
Copper / Aluminium conductor, XLPE sheathed cable
insulated,
Copper wire / tape screened, PVC sheathed cable
1
N2XSY/NA2XSY
3.6/6(7.2) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated,
Copper wire/ tape screened,
PVC/PE sheathed cable
N2XSY/NA2XSY
3.6/6(7.2) kV
IEC 60502-2
Copper/Aluminium conductor,
N2XSY / NA2XSY
3.6/6(7.2) kV XLPE insulated,
IEC 60502-2 Copper wire/ tape screened,
PVC/PE sheathed cable
Copper / Aluminium conductor, XLPE insulated,
with or without swellable tape, Copper / wire tape screened,
PVC/PE sheathed cable
DIMENSIONAL AND ELECTRICAL DATA 1 CORE
Nominal cross-sectional area
Conductor diameter (approx)
mm
mm
2
25
6.05
35
7.1
50
8.25 9.9
70
11.7
95
N2XSY / NA2XSY
120
13.1
150
14.3
185
16.3
240
18.2
300
20.9
400
23.7
500
26.6
630
30.3
800
34.2
Nominal insulation thickness
Insulation diameter (approx)
mm
mm
2.5
12.5
2.5
13.5
2.5
14.7
2.5
16.3
2.5
18.1
2.5
19.5
3.6/6(7.2) kV
2.5
20.7
2.5
22.7
2.6
24.8
2.8
27.9
3.0
31.9
3.2
36.0
3.2
39.7
3.2
43.2
Nominal outer sheath thickness mm 1.8 1.8 1.8 1.8 1.8 1.8 IEC 60502-2
1.8 1.8 1.9 2.0 2.1 2.2 2.3 2.5
Overall cable diameter (approx) mm 18.9 19.9 21.1 22.7 24.3 25.7 27.1 29.1 31.4 34.6 38.9 44.0 47.9 52.7
CU 656 779 929 Copper / Aluminium conductor, XLPE insulated,
1,175 1,440 1,711 2,049 2,454 3,078 3,775 4,737 6,046 7,564 9,242
Cable net weight ( approx) Kg/Km
AL 490 548 with or without swellable tape, Copper / wire tape screened,
620 725 813 922 1,074 1,239 1,477 1,767 2,168 2,770 3,316 3,921
Standard length per-reel m 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 500 500 500 500
Minimum bending radius mm 240 270 290 320 PVC/PE sheathed cable
360 390 410 460 510 560 620 680 780 860
Max. DC conductor resistance CU 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221
Ω/Km
at
at20
20oC
⁰C AL
DIMENSIONAL 1.20
AND ELECTRICAL 0.868DATA0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469 0.0367
Min. insulation resistance at 20 ⁰C MΩ.Km 900 800 700 2 600 500 500 500 400 400 400 400 300 300 300
Nominal cross-sectional area mm 25 35 50 70 95 120 150 185 240 300 400 5
Capacitance per phase µF/Km 0.191 0.216 0.240 0.279 0.318 0.349 0.376 0.419 0.459 0.481 0.511 0.540 0.534 0.595
Conductor
o diameter (approx) mm 6.05 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7 2
0.409 0.391 0.372 0.353 0.333 0.323 0.316 0.306 0.295 0.289 0.283 0.278 0.279 0.272
Inductance per phase oo
Nominal insulation
mH/Km thickness mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8 3.0 3
oInsulation
oo 0.594
diameter (approx) 0.575 0.556mm 0.53812.5 0.51813.5 0.50814.7 0.50116.3 0.49118.1 0.48019.5 0.47420.7 0.46822.7 0.46324.8 0.46427.9 0.45731.9 3
Max.short circuit current of CU outer sheath thickness
Nominal 3.73 5.18 7.36mm 10.261.8 13.881.8 17.491.8 21.811.8 26.861.8 34.781.8 43.411.8 57.791.8 72.161.9 90.832.0 115.232.1
conductor AL cable
Overall kA/sec 2.49
diameter (approx) 3.45 4.89mm 6.8118.9 9.1919.9 11.5821.1 14.4322.7 17.7624.3 22.9825.7 28.6727.1 38.1429.1 47.6031.4 59.9034.6 75.9638.9 4
Max.short circuit current of screen 2.26 2.43 CU 2.63 2.90 656 2.56 779 2.75 929 3.631,175 3.961,440 4.391,711 4.822,049 5.352,454 5.903,078 6.343,775 6.994,737 6
Cable net weight ( approx) Kg/Km
o CU 161 194 AL 233 291 490 353 548 406 620 459 725 526 813 620 922 7281,074 8141,239 9201,477 1,006 1,767 1,118 2,168 2
o oStandardAL length per-reel 124 150 180 m 2131,000 2741,000 3161,000 3581,000 4111,000 4881,000 5581,000 6501,000 7431,000 8031,000 893 500 5
in air
CU bending radius 190
Minimum 230 276mm 344 240 417 270 480 290 536 320 611 360 715 390 810 410 900 460 1,005510 1,087560 1,209620 6
Maximum current ooo
carrying Max. AL 146
DC conductor resistance 177 CU 214 2670.727 3260.524 3760.387 4230.268 4840.193 5720.153 6510.124 7400.0991 8370.0754 8700.0601 9670.0470 0.
A Ω/Km
o oatat2020CU
oC
⁰C 150 179 AL 210 257 1.20 3070.868 3480.641 3880.443 4380.320 5060.253 5680.206 6370.164 7170.125 7790.100 8310.0778 0.
capacity at 30 C
in o oMin. AL insulation resistance115at 20 ⁰C 137 163
MΩ.Km 200 900 238 800 271 700 302 600 343 500 398 500 449 500 510 400 574 400 622 400 663 400 3
ground CU
Capacitance per phase 171 203 238µF/Km 2900.191 3430.216 3870.240 4220.279 4720.318 5390.349 6010.376 6480.419 7740.459 8180.481 8710.511 0
ooo
AL 131 156o 185 226 269 304 335 376 434 486 536 614 654 697
0.409 0.391 0.372 0.353 0.333 0.323 0.316 0.306 0.295 0.289 0.283 0
AC test voltage InductancekV/5per phase
min oo mH/Km 12.5 (IEC) , 9 (SPLN)
ooo 0.594 0.575 0.556 0.538 0.518 0.508 0.501 0.491 0.480 0.474 0.468 0
Note : This is only general information. For current
Max.short circuit other ofspecific requirement,
CU please contact5.18
3.73 our marketing.
7.36 10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.79 7
conductor AL kA/sec 2.49 3.45 4.89 6.81 9.19 11.58 14.43 17.76 22.98 28.67 38.14 4
Max.short circuit current of screen 2.26 2.43 2.63 2.90 2.56 2.75 3.63 3.96 4.39 4.82 5.35 5
o CU 161 194 233 291 353 406 459 526 620 728 814 9
oo AL 124 150 180 213 274 316 358 411 488 558 650 7
in air
CU 190 230 276 344 417 480 536 611 715 810 900 1
Maximum current ooo
AL 146 177 214 267 326 376 423 484 572 651 740 8
carrying A
o o CU 150 179 210 257 307 348 388 438 506 568 637 7
capacity at 30 C
in oo AL 115 137 163 200 238 271 302 343 398 449 510 5
ground CU 171 203 238 290 343 387 422 472 539 601 648 7
ooo
AL 131 156 185 226 269 304 335 376 434 486 536 6
AC test voltage kV/5 min 2 12.5 (IEC) , 9 (SPLN)
N2XSY/NA2XSY
6/10(12) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated,
Copper wire/tape screened,
PVC/PE sheathed cable
N2XSY/NA2XSY
6/10(12) kV
IEC 60502-2
N2XSY / NA2XSY
Copper/Aluminium conductor,
6/10(12) kV XLPE insulated,
IEC 60502-2 Copper wire/tape screened,
Copper / Aluminium condoctor, XLPEPVC/PE sheathed
insulated, cable
with or without swellable tape, Copper / wire tape Screened,
PVC/PE sheathed cable
Copper/Aluminium conductor,
XLPE insulated,
Copper wire/tape screened,
PVC/PE sheathed cable N2XSY/NA2XSY
8.7/15(17.5) kV
IEC 60502-2
Copper/Aluminium conductor,
N2XSY / NA2XSY
8.7/15(17.5) kV XLPE insulated,
IEC 60502-2 Copper wire/tape screened,
PVC/PE
Copper / Aluminium conductor, XLPE sheathed cable
insulated,
with or without swellable tape, Copper / wire tape screened,
PVC/PE sheathed cable
N2XSY/NA2XSY
12/20(24) kV
SPLN 43-5/IEC 60502-2
N2XSY/NA2XSY
N2XSY / NA2XSY
Copper/Aluminium
12/20(24) kV conductor, XLPE insulated,
12/20(24)
IEC 60502-2
with kV
or without water sealing,
Copper wire/tape screened,
SPLN conductor,
Copper / Aluminium 43-5/IEC 60502-2
XLPE insulated,
PVC/PE
with or without swellable tape, Copper / wire tape sheathed
screened, cable
Copper/Aluminium conductor, XLPE insulated,
DIMENSIONAL AND ELECTRICAL DATA with or without water sealing, 1 CORE
Nominal cross-sectional area mm
2
35 Copper
50 70 wire/tape
95 120 screened,
150 185 240 300 400 500 630 800
PVC/PE
5.5 sheathed5.5 cable
Conductor diameter (approx) mm 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7 26.6 30.3 34.2
Nominal insulation thickness mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Insulation diameter (approx) mm 19.7 20.9 22.5 24.3 25.7 26.9 28.9 31.3 33.5 36.3 39.2 44.1 48.0
Nominal outer sheath thickness mm 1.8 1.8 1.9 1.9 2.0 2.0 2.1 2.1 2.2 2.3 2.4 2.5 2.6
Overall cable diameter (approx) mm 26 27 29 31 32 34 36 38 40 44 47 53 58
Copper/Aluminium conductor,
XLPE insulated,
Copper wire/tape screened,
N2XSY/NA2XSY
PVC/PE sheathed cable 18/30(36) kV
N2XSY/NA2XSY IEC 60502-2
18/30(36)
N2XSY kV
/ NA2XSY
Copper/Aluminium conductor,
18/30(36) kV
XLPE insulated,
IEC 60502-2
IEC 60502-2 Copper wire/tape screened,
CopperCopper/Aluminium
/ Aluminium conductor, PVC/PE
conductor,
XLPE sheathed cable
insulated,
Copper / wire tape screened,
XLPE PVC sheated cable
insulated,
Copper wire/tape screened,
DIMENSIONAL AND ELECTRICAL DATA
PVC/PE sheathed N2XSY
cable / NA2XSY 1 CORE
18/30(36)
20.9 kV
2
Nominal cross-sectional area mm 50 70 95 120 150 185 240 300 400 500 630 800
Conductor diameter (approx) mm 8.25 9.9 11.7 13.1 14.3 16.3 18.2 23.7 26.6 30.3 34.2
Nominal insulation thickness
Insulation diameter (approx)
mm 8.0 8.0 8.0 8.0 8.0
IEC 60502-2
8.0 8.0 8.0 8.0 8.0 8.0 8.0
N2XSY Copper
/ NA2XSY
mm 25.9 27.5 29.3 30.7 31.9 33.9 36.3 38.5 41.3 44.2 49.1 53.0
Nominal outer sheath thickness mm 2.0 2.0/ Aluminium conductor, XLPE insulated,
2.1 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.8
Overall cable diameter (approx)
18/30(36)
Copper /kV
mm 32 34 36 37 39 41 43 46 49 52 58 62
CU 1,400 1,700 wire tape screened, PVC sheated cable
2,000 2,300 2,600 3,100 3,700 4,400 5,300 6,400 8,200 10,000
Cable net weight ( approx) Kg/Km
in air
oo AL 187 232
o o o
CU281 6323 241365 294418 348494 394564 431 654 483
747 553
807 615897 660
CU 279 348 AL421 483 188540 228615 273718 309812 341 904 384
1,011 443
1,091 495
1,213 544
Maximum current o o o AC test voltage
AL 217 270 328 kV/5 min
378 425 485 572 649 737 838 63 874 971
N2XRY/NA2XRY
1.8/3(3.6) kV
IEC 60502-1
Copper/Aluminium conductor,
XLPE insulated, Aluminium wire armoured,
PVC/PE sheathed cable
N2XRY/NA2XRY
1.8/3(3.6) kV
IEC 60502-1
N2XSRY / NA2XSRY
1.8/3(3.6) kVCopper/Aluminium conductor,
XLPE insulated, Aluminium wire armoured,
IEC 60502-1
PVC/PE
Copper / Aluminium conductor, XLPE sheathed cable
insulated,
Copper / wire tape screened, Aluminium wire armoured,
PVC/PE sheathed cable
1.8/3(3.6) kV
Nominal insulation thickness mm 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.2 2.4 2.6
Insulation diameter (approx) mm 10.3 11.3 12.5 14.1 15.9 17.3 18.5 20.5 22.9 25.1 27.9 31.2 35.3 39.6
Diameter of armour wire
Nominal outer sheath thickness
mm
mm
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8 IEC 60502-1
1.6
1.9
1.6
2.0
2.0
2.1
2.0
2.2
2.5
2.3
2.5
2.4
3.15
2.6
Overall cable diameter (approx) mm 23 24 25 27 28 Copper / Aluminium conductor, XLPE insulated,
30 31 33 36 39 42 46 53 59
CU 700 800 1,000 1,200 1,500 1,700 2,000 2,400 3,100 3,800 4,700 6,000 7,500 9,600
Cable net weight ( approx)
AL
Kg/Km
500 600 700 800 Copper / wire tape screened, Aluminium wire armoured,
900 1,000 1,100 1,300 1,500 1,900 2,200 2,700 3,500 4,500
Standard length per-reel
Minimum bending radius
m
mm
1,000
260
1,000
280
1,000
300
1,000
340
1,000
380
1,000
400
PVC/PE sheathed cable
1,000
420
1,000
46
1,000
520
500
570
500
630
500
710
500
780
500
880
Max. DC conductor resistance CU 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221
Ω/Km
at 20 ⁰C AL DIMENSIONAL1.20AND ELECTRICAL
0.868 0.641DATA0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469 0.0367
Min. insulation resistance at 20 ⁰C MΩ.Km cross-sectional
Nominal 900 700
area 700 600 mm2 500 25 400 35 400 50 400 70 300 95 300 120 300 150 300 185 200 240 200 300 400
Capacitance per phase µF/Km diameter
Conductor 0.261 (approx)
0.299 0.334 0.393mm 0.453 6.05 0.499 7.1 0.539 8.25 0.606 9.9 0.685 11.7 0.758 13.1 0.851 14.3 0.871 16.3 0.909 18.2 0.947 20.9 23.7
o
0.428 thickness
Nominal insulation 0.405 0.385 0.366mm 0.348 2.0 0.333 2.0 0.323 2.0 0.311 2.0 0.302 2.0 0.297 2.0 0.288 2.0 0.289 2.0 0.281 2.0 0.280 2.0 2.0
Inductance per phase oo
mH/Km
Insulation diameter
ooo 0.613 (approx)
0.59 0.570 0.551mm 0.533 10.3 0.518 11.3 0.508 12.5 0.495 14.1 0.487 15.9 0.582 17.3 0.473 18.5 0.474 20.5 0.465 22.9 0.465 25.1 27.9
Max.short circuit current of CU Diameter of armour
3.73 wire 5.18 7.36 10.26mm 13.88 1.6 17.49 1.6 21.81 1.6 26.86 1.6 34.78 1.6 43.41 1.6 57.79 1.6 72.16 1.6 90.83 1.6 115.23 2.0 2.0
kA/sec outer sheath thickness
Nominal
conductor AL 249 3.45 4.89 6.81 mm 9.19 1.8 11.58 1.8 14.43 1.8 17.76 1.8 22.98 1.8 28.67 1.8 38.14 1.8 47.60 1.9 59.90 2.0 75.96 2.1 2.2
o CU Overall cable 160
diameter (approx)
193 231 289 mm 350 23 403 24 456 25 523 27 616 28 723 30 808 31 913 33 998 36 1,109 39 42
oo AL Cable net 123 ( approx)
weight 149 179 CU 215Kg/Km 272 700 314 800 356 1,000 409 1,200 485 1,500 554 1,700 645 2,000 737 2,400 797 3,100 886 3,800 4,700
in air
CU 189 229 274 AL 341 414 500 476 600 532 700 607 800 710 900 804 1,000 893 1,100 997 1,300 1,0781,500 1,1981,900 2,200
Maximum current ooo Standard length
AL 145per-reel176 213 265 m 324 1,000 373 1,000 421 1,000 481 1,000 568 1,000 646 1,000 734 1,000 830 1,000 862 1,000 958 500 500
carrying A
Minimum bending
o o CU 149 radius178 209 255 mm 305 260 345 280 286 300 435 340 503 380 64 400 632 420 712 46 773 520 824 570 630
capacity at 30 C Max. DC conductor
in oo AL 115 resistance
136 162 CU 199Ω/Km 236 0.727 269 0.524 301 0.387 641 0.268 396 0.193 446 0.153 507 0.124 5690.0991 6180.0754 6580.0601 0.0470
ground CU at 20 ⁰C 170 202 236 AL 288 340 1.20 384 0.868 20 0.641 469 0.443 535 0.320 596 0.253 643 0.206 767 0.164 812 0.125 864 0.100 0.0778
ooo Min. insulation resistance at 20 ⁰C 184
AL 130 155 225MΩ.Km 267 900 302 700 333 700 374 600 430 500 483 400 532 400 610 400 349 300 696 300 300
AC test voltage Capacitance
kV/5 min per phase µF/Km 0.261 0.299 0.334
6.5 0.393 0.453 0.499 0.539 0.606 0.685 0.758 0.851
o
Note : This is only general information.Inductance
For other specific requirement, please contact 0.428
our 0.405
marketing. 0.385 0.366 0.348 0.333 0.323 0.311 0.302 0.297 0.288
per phase o o mH/Km
ooo 0.613 0.59 0.570 0.551 0.533 0.518 0.508 0.495 0.487 0.582 0.473
Max.short circuit current of CU 3.73 5.18 7.36 10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.79
kA/sec
conductor AL 249 3.45 4.89 6.81 9.19 11.58 14.43 17.76 22.98 28.67 38.14
o CU 160 193 231 289 350 403 456 523 616 723 808
oo AL 123 149 179 215 272 314 356 409 485 554 645
in air
CU 189 229 274 341 414 476 532 607 710 804 893
Maximum current ooo
AL 145 176 213 265 324 373 421 481 568 646 734
carrying A
o o CU 149 178 209 255 305 345 286 435 503 64 632
capacity at 30 C
in oo AL 115 136 162 199 236 269 301 641 396 446 507
ground CU 170 202 236 288 340 384 20 469 535 596 643
ooo
AL 7 130 155 184 225 267 302 333 374 430 483 532
AC test voltage kV/5 min 6.5
N2XSRY/NA2XSRY
3.6/6(7.2) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
Aluminium wire armoured,
PVC/PE sheathed cable
N2XSRY/NA2XSRY
3.6/6(7.2) kV
IEC 60502-2
N2XSRY / NA2XSRY
Copper/Aluminium conductor,
3.6/6(7.2) kV
XLPE insulated, Copper wire/tape screened,
IEC 60502-2 Aluminium wire armoured,
Copper / Aluminium conductor, XLPE insulated,
PVC/PE sheathed cable
Copper / wire tape screened, Aluminium wire armoured,
PVC/PE sheathed cable
N2XSRY / NA2XSRY
Insulation diameter (approx) mm 12.5 13.5 14.7 16.3 18.1 19.5 20.7 22.7 24.8 27.9 31.9 36.0 39.7 43.2
Diameter of armour wire mm 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 3.15 3.15
3.6/6(7.2) kV
Nominal outer sheath thickness mm 1.8 1.8 1.8 1.8 1.9 2.0 2.0 2.1 2.2 2.2 2.4 2.5 2.7 2.8
Overall cable diameter (approx) mm 25 26 27 29 30 32 33 36 39 42 47 50 58 63
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
Aluminium wire armoured,
PVC/PE sheathed cable
N2XSRY/NA2XSRY
6/10(12) kV
IEC 60502-2
N2XSRY / NA2XSRY
Copper/Aluminium conductor,
6/10(12)
XLPE kV
insulated, Copper wire/tape screened,
IEC 60502-2 Aluminium wire armoured,
PVC/PE
Copper / Aluminium conductor, XLPE sheathed cable
insulated,
Copper / wire tape screened, Aluminium wire armoured,
PVC/PE sheathed cable
Kg/Km
27
1,100
28
1,200
29
1,400
30
1,700
32
2,000
34
2,300
36
N2XSRY / NA2XSRY
2,700
38
3,200
41
3,800
44
4,600
47
5,600
50
6,800
58
8,900
62
10,800
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
Aluminium wire armoured, N2XSRY/NA2XSRY
PVC/PE sheathed cable
8.7/15(17.5) kV
IEC 60502-2
N2XSRY / NA2XSRY
Copper/Aluminium conductor,
8.7/15(17.5) kV
XLPE insulated, Copper wire/tape screened,
IEC 60502-2 Aluminium wire armoured,
Copper / Aluminium conductor, XLPEPVC/PE sheathed cable
insulated,
Copper / wire tape screened , Aluminium wire armoured,
PVC/PE sheathed cable
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
Aluminium wire armoured,
PVC/PE sheathed cable N2XSRY/NA2XSRY
12/20(24) kV
IEC 60502-2
N2XSRY / NA2XSRY
Copper/Aluminium conductor,
12/20(24) kVinsulated, Copper wire/tape screened,
XLPE
IEC 60502-2 Aluminium wire armoured,
Copper / Aluminium conductor, XLPEPVC/PE
insulated,
sheathed cable
Copper / wire tape screened, Aluminium wire armoured,
PVC/PE sheathed cable
IEC 60502-2
Insulation diameter (approx) mm 19.7 20.9 22.5 24.3 25.7 26.9 28.9 31.3 33.5 36.3 39.2 44.1 48.0
Diameter of armour wire mm 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.5 2.5 3.15 3.15 3.15 4.0
Nominal outer sheath thickness
Overall cable diameter (approx)
mm
mm
2
32
2.0
33
2.1
36
Copper / Aluminium conductor, XLPE insulated,
2.1
38
2.2
39
2.2
41
2.3
44
2.4
47
2.5
49
2.6
54
2.7
57
2.8
63
3.0
69
Copper/Aluminium conductor,
N2XSRY/NA2XSRY
XLPE insulated, Copper wire/tape screened,
Aluminium wire armoured, PVC/PE sheathed cable
18/30(36) kV
N2XSRY / NA2XSRY IEC 60502-2
18/30(36) kV
IEC 60502-2 Copper/Aluminium conductor,
XLPE insulated,
Copper / Aluminium conductor, Copper wire/tape screened,
XLPE insulated,
Aluminium
Copper / wire tape screened, wirewire
Aluminium armoured, PVC/PE sheathed cable
armoured,
PVC/PE sheathed cable
13
N2XSKY/NA2XSKY
3.6/6(7.2) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
lead sheathed, PVC sheathed cable
N2XSKY/NA2XSKY
3.6/6(7.2) kV
N2XSKY / NA2XSKY IEC 60502-2
3.6/6(7.2) kV
IEC 60502-2Copper/Aluminium conductor,
Copper / Aluminium XLPE insulated,
conductor, Copper wire/tape screened,
XLPE insulated,
lead sheathed, PVC/PE sheathed cable
Copper / wire tape screened, lead sheathed,
PVC sheathed cable
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
Lead sheathed, PVC/PE sheathed cable
N2XSKY/NA2XSKY
6/10(12) kV
IEC 60502-2
N2XSKY / NA2XSKY
6/10(12) kV Copper/Aluminium conductor,
IEC 60502-2
XLPE insulated, Copper wire/tape screened,
Lead sheathed,
Copper / Aluminium conductor, PVC/PE sheathed cable
XLPE insulated,
Copper / wire tape screened, Lead sheathed,
PVC/PE sheathed cable
in air
oo AL 15 124 149 179 215 272 314 355 408 484 553 644
CU 189 229 274 341 414 476 531 606 709 803 892
Maximum current ooo
AL 145 176 213 265 324 373 420 480 567 645 733
carrying A
N2XSKY/NA2XSKY
8.7/15(17.5) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
Lead sheathed, PVC/PE sheathed cable N2XSKY/NA2XSKY
8.7/15(17.5) kV
IEC 60502-2
N2XSKY / NA2XSKY
8.7/15(17.5)Copper/Aluminium
kV conductor,
XLPE insulated,
IEC 60502-2 Copper wire/tape screened,
Lead sheathed,
Copper / Aluminium conductor, PVC/PE sheathed cable
XLPE insulated,
Copper / wire tape screened, Lead sheathed,
PVC/PE sheathed cable
N2XSKY / NA2XSKY
2
Nominal cross-sectional area mm 25 35 50 70 95 120 150 185 240 300 400 500 630 800
Conductor diameter (approx) mm 6.05 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7 26.6 30.3 34.2
Nominal insulation thickness
Insulation diameter (approx)
mm
mm
4.5
16.5
4.5
17.5
4.5
18.7
4.5
20.3
4.5
22.1
4.5
23.5
8.7/15(17.5) kV
4.5
24.7
4.5
25.7
4.5
29.1
4.5
31.3
4.5
34.1
4.5
37.0
4.5
41.9
4.5
45.8
Nominal lead thickness
Nominal outer sheath thickness
mm
mm
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.9
1.5
1.9
1.6
2.0
1.6
2.1
IEC 60502-2
1.6
2.1
1.7
2.2
1.8
2.3
1.9
2.4
1.9
2.5
2.0
2.6
2.1
2.7
Overall cable diameter (approx) mm 28 29 30 32 Copper / Aluminium conductor, XLPE insulated,
34 36 37 39 42 44 48 51 57 62
CU 2,200 2,400 2,600 3,000 3,500 3,900 4,400 5,000 5,800 6,600 8,000 9,400 11,700 14,000
Cable net weight ( approx)
AL
Kg/Km
2,100 2,200 2,300 2,500
Copper / wire tape screened, Lead sheathed,
2,900 3,100 3,500 3,800 4,300 5,300 5,400 6,300 7,500 8,700
Standard length per-reel m 1,000 1,000 1,000 1,000 1,000 PVC/PE sheathed cable
1,000 1,000 1,000 1,000 1,000 500 500 500 500
Minimum bending radius mm 340 360 390 420 460 490 520 560 610 650 720 780 870 960
Max. DC conductor resistance CU 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221
at
at20
20oC
⁰C AL
DIMENSIONAL
Ω/Km AND
1.20
ELECTRICAL
0.868
DATA
0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469 0.0367
2
Min. insulation resistance at 20 ⁰C Nominal
MΩ.Kmcross-sectional
1,300 area
1,200 1,100 mm
1,000 900 25 800 35 700 50 700 70 600 95 600120 500150 500185 400240 400300 40
Capacitance per phase Conductor
µF/Km diameter
0.138 (approx)
0.154 0.170 mm
0.193 6.05 0.238
0.218 7.1 0.2548.25 0.281 9.9 11.7
0.314 13.1
0.344 14.3
0.382 16.3 0.428
0.421 18.2 0.476 20.9 23
o Nominal insulation
0.495thickness
0.471 0.448 mm
0.423 0.4024.5 0.389 4.5 0.3804.5 0.3654.5 0.3504.5 0.3384.5 0.3294.5 0.3184.5 0.3154.5 0.3064.5 4
Inductance per phase oo mH/Km diameter (approx)
Insulation mm 16.5 17.5 18.7 20.3 22.1 23.5 24.7 25.7 29.1 31.3 34
ooo 0.680 0.656 0.633 0.608 0.587 0.573 0.565 0.550 0.535 0.523 0.514 0.503 0.500 0.491
Nominal lead thickness mm 1.5 1.5 1.5 1.5 1.5 1.6 1.6 1.6 1.7 1.8 1.
Max.short circuit current of CU 3.73 5.18 7.36 10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.79 72.16 90.83 115.23
Nominal outer sheath thickness mm 1.8 1.8 1.8 1.9 1.9 2.0 2.1 2.1 2.2 2.3 2.
conductor AL kA/sec 2.49 3.45 4.89 6.81 9.19 11.58 14.43 17.76 22.98 28.67 38.14 47.60 59.90 75.96
Overall cable diameter (approx) mm 28 29 30 32 34 36 37 39 42 44 4
Max.short circuit current of screen 2.92 2.48 2.63 2.85 3.09 3.28 4.29 4.62 4.02 4.31 5.85 6.33 5.82 6.34
CU 2,200 2,400 2,600 3,000 3,500 3,900 4,400 5,000 5,800 6,600 8,0
o CU Cable net weight160( approx)197 235 Kg/Km
293 354 408 461 527 621 708 811 918 999 1,110
AL 2,100 2,200 2,300 2,500 2,900 3,100 3,500 3,800 4,300 5,300 5,4
oo AL 124 153 182 227 275 317 359 411 488 557 645 738 798 887
in air Standard length per-reel m 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 50
CU 189 230 276 348 416 478 532 608 711 805 895 1,001 1,079 1200
Maximum current ooo Minimum bending radius mm 340 360 390 420 460 490 520 560 610 650 72
AL 145 178 215 237 325 374 421 480 508 645 732 830 864 960
carrying Max. ADC conductor resistance CU 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0
o o CU 149 179 212 Ω/Km
259 309 349 390 440 508 571 640 713 774 826
capacity at 30 C at
at20
20oC
⁰C AL 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0
in oo AL 115 137 164 201 239 273 304 344 400 450 512 570 619 659
Min. insulation resistance at 20 ⁰C MΩ.Km 1,300 1,200 1,100 1,000 900 800 700 700 600 600 50
ground CU 170 203 257 289 343 387 423 473 540 602 652 768 819 865
ooo Capacitance per phase µF/Km 0.138 0.154 0.170 0.193 0.218 0.238 0.254 0.281 0.314 0.344 0.3
AL 130 156 185
o 226 268 304 335 376 434 486 537 611 650 694
AC test voltage kV/5 min per phase 0.495 0.471 0.448
30.5 0.423 0.402 0.389 0.380 0.365 0.350 0.338 0.3
Inductance oo mH/Km
ooo
Note : This is only general information. For other specific requirement, please contact0.680 0.656
our marketing. 0.633 0.608 0.587 0.573 0.565 0.550 0.535 0.523 0.5
Max.short circuit current of CU 3.73 5.18 7.36 10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.
conductor AL kA/sec 2.49 3.45 4.89 6.81 9.19 11.58 14.43 17.76 22.98 28.67 38.
Max.short circuit current of screen 2.92 2.48 2.63 2.85 3.09 3.28 4.29 4.62 4.02 4.31 5.
o CU 160 197 235 293 354 408 461 527 621 708 81
oo AL 124 153 182 227 275 317 359 411 488 557 64
in air
CU 189 230 276 348 416 478 532 608 711 805 89
Maximum current ooo
AL 145 178 215 237 325 374 421 480 508 645 73
carrying A
o o CU 149 179 212 259 309 349 390 440 508 571 64
capacity at 30 C
in oo AL 115 137 164 201 239 273 304 344 400 450 51
ground
ooo
CU 16170 203 257 289 343 387 423 473 540 602 65
AL 130 156 185 226 268 304 335 376 434 486 53
AC test voltage kV/5 min 30.5
N2XSKY/NA2XSKY
12/20(24) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
lead sheathed, PVC/PE sheathed cable
N2XSKY/NA2XSKY
12/20(24) kV
IEC 60502-2
N2XSKY / NA2XSKY
12/20(24) kV Copper/Aluminium conductor,
IEC 60502-2
XLPE insulated, Copper wire/tape screened,
Copper / Aluminium conductor, XLPE insulated,
lead sheathed, PVC/PE sheathed cable
Copper / wire tape screened, lead sheathed,
PVC/PE sheathed cable
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
N2XSKY/NA2XSKY
Lead sheathed, PVC/PE sheathed cable
18/30(36) kV
N2XSKY / NA2XSKY IEC 60502-2
18/30(36) kV
Copper/Aluminium conductor,
IEC 60502-2
XLPE insulated, Copper wire/tape screened,
Copper / Aluminium conductor, XLPE insulated,
Lead sheathed,
Copper wire / tape screened, PVC/PE sheathed cable
Lead sheathed,
PVC/PE sheathed cable
18/30(36) kV
Nominal insulation thickness mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
Insulation diameter (approx) mm 25.9 27.5 29.3 30.7 31.9 33.9 36.3 38.5 41.3 44.2 49.1 53.0
Nominal lead thickness
Nominal outer sheath thickness
mm
mm
1.6
2.0
1.6
2.0
1.6
2.1
1.7
2.2
1.7
2.2 IEC 60502-2
1.8
2.3
1.8
2.3
1.9
2.4
2.0
2.5
2.1
2.6
2.2
2.7
2.3
2.9
Overall cable diameter (approx) mm 38 40 Copper / Aluminium conductor, XLPE insulated,
42 44 45 47 50 53 56 59 65 70
CU 3,700 4,100 4,700 5,100 5,700 6,300 7,200 8,200 9,400 11,000 13,400 15,900
Cable net weight ( approx)
AL
Kg/Km
3,400 3,600 Copper wire / tape screened, Lead sheathed,
4,100 4,200 4,700 5,100 5,600 6,000 6,900 7,600 6,200 10,500
Standard length per-reel
Minimum bending radius
m
mm
1,000
470
1,000
500
1,000
540
PVC/PE sheathed cable
1,000
570
1,000
600
1,000
640
1,000
690
1,000
740
500
790
500
860
500
950
500
1,040
Max. DC conductor resistance CU 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221
Ω/Km
at
at20
20oC
⁰C DIMENSIONALAL AND ELECTRICAL
0.641 DATA
0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469 0.0367
Min. insulation resistance at 20 ⁰C MΩ.Km area1,600
Nominal cross-sectional 1,500 1,300
mm
2 1,200
50 1,200
70 1,100
95 1,000
120 900
150 800
185 700
240 600
300 600
400 500
Capacitance per phase Conductor diameterµF/Km
(approx)0.121 0.136 0.151
mm 0.163
8.25 0.173
9.9 0.190
11.7 0.209
13.1 0.227
14.3 0.250
16.3 0.274
18.2 0.288
20.9 0.317
23.7 26.6
o
Nominal insulation thickness 0.496 0.468 0.445
mm 8.0
0.429 8.0
0.419 8.0
0.401 8.0
0.385 8.0
0.373 8.0
0.359 8.0
0.348 8.0
0.341 8.0
0.330 8.0
Inductance per phase oo mH/Km
Insulation
o o o diameter (approx) 0.681 0.653 mm
0.630 25.9
0.614 27.5
0.604 29.3
0.586 30.7
0.570 31.9
0.558 33.9
0.544 36.3
0.532 38.5
0.526 41.3
0.515 44.2
Max.short circuit current of Nominal CUlead thickness 7.36 10.26 mm
13.88 1.6
17.49 1.6
21.81 1.6
26.86 1.7
34.78 1.7
43.41 1.8
57.79 1.8
72.16 1.9
90.83 2.0
115.23 2.1
conductor Nominal ALouter sheath
kA/secthickness
4.89 6.81 mm
9.19 2.0
11.58 2.0
14.43 2.1
17.76 2.2
22.98 2.2
28.67 2.3
38.14 2.3
47.60 2.4
59.90 2.5
75.96 2.6
Overall cable diameter (approx)
Max.short circuit current of screen 3.59 3.81 mm
4.04 38
4.23 40
4.39 42
4.66 44
4.97 45
5.26 47
5.64 50
6.02 53
6.78 56
7.29 59
o netCUweight ( approx) 238 CU
296 358 3,700
412 4,100
464 4,700
530 5,100
624 5,700
710 6,300
815 7,200
920 8,200
1,000 9,400
1,111 11,00
Cable Kg/Km
oo AL 185 AL
230 278 3,400
320 3,600
361 4,100
414 4,200
489 4,700
558 5,100
647 5,600
739 6,000
799 6,900
888 7,600
in air StandardCU length per-reel m 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 500 500
276 343 417 478 535 609 741 804 895 1,001 1,080 1,201
Maximum current ooo
Minimum bending radius mm 470 500 540 570 600 640 690 740 790 860
AL 215 267 325 374 421 480 561 642 729 829 865 961
carrying Max. conductor Aresistance 215
DC CU
o CU
262 313 0.387
354 0.268
294 0.193
444 0.153
514 0.124
579 0.0991
641 0.0754
714 0.0601
775 0.0470
826 0.036
o
capacity at 30 C Ω/Km
at
ato20
20oC
o ⁰C AL 166 AL
203 243 0.641
275 0.443
308 0.320
347 0.253
405 0.206
455 0.164
513 0.125
571 0.100
620 0.0778
660 0.060
in ground Min. insulation resistance at 20 ⁰C MΩ.Km 1,600 1,500 1,300 1,200 1,200 1,100 1,000 900 800 700
CU 238 291 344 390 427 478 547 609 653 770 814 866
ooo
Capacitance
AL per phase 186 225 µF/Km
270 0.121
306 0.136
337 0.151
380 0.163
438 0.173
490 0.190
538 0.209
612 0.227
651 0.250
695 0.27
o
AC test voltage kV/5 min 0.496 0.468 0.445 63 0.429 0.419 0.401 0.385 0.373 0.359 0.34
Inductance per phase o o mH/Km
Note : This is only general information. For other specific requirement,
ooo please contact
0.681our marketing.
0.653 0.630 0.614 0.604 0.586 0.570 0.558 0.544 0.53
Max.short circuit current of CU 7.36 10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.79 72.1
conductor AL kA/sec 4.89 6.81 9.19 11.58 14.43 17.76 22.98 28.67 38.14 47.6
Max.short circuit current of screen 3.59 3.81 4.04 4.23 4.39 4.66 4.97 5.26 5.64 6.02
o CU 238 296 358 412 464 530 624 710 815 920
oo AL 185 230 278 320 361 414 489 558 647 739
in air
Maximum current ooo
CU 18276 343 417 478 535 609 741 804 895 1,00
AL 215 267 325 374 421 480 561 642 729 829
carrying A
o o CU 215 262 313 354 294 444 514 579 641 714
N2XSY/NA2XSY
1.8/3(3.6) kV
IEC 60502-1
Copper/Aluminium conductor,
XLPE insulated, Copper wire/tape screened,
PVC/PE sheathed cable
N2XSY/NA2XSY
1.8/3(3.6) kV
IEC 60502-1
Copper/Aluminium conductor,
N2XSY / NA2XSY
XLPE insulated,
1.8/3(3.6) kV Copper wire/tape screened,
IEC 60502-1 PVC/PE sheathed cable
Copper / Aluminium conductor, XLPE insulated,
Copper wire / tape screened, PVC/PE sheathed cable
19
N2XSEY/NA2XSEY
3.6/6(7.2) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated,
Copper tape screened,
PVC/PE sheathed cable N2XSEY/NA2XSEY
3.6/6(7.2) kV
IEC 60502-2
Copper/Aluminium conductor,
N2XSEY / NA2XSEYXLPE insulated,
3.6/6(7.2) kVCopper tape screened,
IEC 60502-2
PVC/PE sheathed cable
Copper / Aluminium conductor, XLPE insulated,
with or without swellable tape, Copper wire / tape screened,
PVC/PE sheathed
20
N2XSEY/NA2XSEY
6/10(12) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated,
Copper tape screened,
PVC/PE sheathed cable N2XSEY/NA2XSEY
6/10(12) kV
IEC 60502-2
N2XSEY / NA2XSEY
Copper/Aluminium conductor,
6/10(12) kV
XLPE insulated,
IEC 60502-2
Copper tape screened,
Copper / Aluminium conductor, XLPE insulated
PVC/PE
with or without swellable tape, Copper wire / tapesheathed
screened cable
PVC/PE sheathed cable
21
N2XSEY/NA2XSEY
8.7/15(17.5) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated
Copper tape screened,
PVC/PE sheathed cable
N2XSEY/NA2XSEY
8.7/15(17.5) kV
IEC 60502-2
N2XSEY / NA2XSEY
8.7/15(17.5)Copper/Aluminium
kV conductor,
XLPE insulated
IEC 60502-2
Copper tape screened,
Copper / Aluminium conductor, XLPE insulated
PVC/PE sheathed cable
with or without swellable tape, Copper / wire tape screened
PVC/PE sheathed cable
Copper/Aluminium conductor,
XLPE insulated, with or without water sealing,
Copper wire screened,
PVC/PE sheathed cable N2XSEY/NA2XSEY
12/20(24) kV
SPLN 43-5/IEC 60502-2
N2XSEY / NA2XSEY
12/20(24) kV
Copper/Aluminium conductor,
IEC XLPE
60502-2
insulated, with or without water sealing,
Copper
Copper / Aluminium conductor, XLPE wire screened,
insulated,
PVC/PE
with or without swellable tape, Copper wire sheathed
/ tape screened,cable
PVC/PE sheathed cable
N2XSEY / NA2XSEY
DIMENSIONAL AND ELECTRICAL DATA 3 CORES
2
Nominal cross-sectional area mm 35 50 70 95 120 150 185 240 300 400
Conductor diameter (approx)
Nominal insulation thickness
mm
mm
7.1
5.5
8.25
5.5
9.9
5.5
11.7
5.5
13.1
5.5
12/20(24) kV
14.3
5.5
16.3
5.5
18.2
5.5
20.9
5.5
23.7
5.5
Insulation diameter (approx) mm 19.7 20.9 22.5 24.3 25.7 IEC 60502-2
26.9 28.9 31.3 33.5 36.3
Nominal outer sheath thickness mm 1.8 1.8 1.9 1.9 2.0 2.0 2.1 2.1 2.2 2.3
Overall cable diameter (approx) mm 53 56 Copper / Aluminium conductor, XLPE insulated,
60 64 67 70 75 80 85 91
Copper/Aluminium conductor,
XLPE insulated, Copper tape screened,
PVC/PE sheathed cable
N2XSEY/NA2XSEY
18/30(36) kV
IEC 60502-2
N2XSEY / NA2XSEY
18/30(36)Copper/Aluminium
kV conductor,
XLPE insulated, Copper tape screened,
IEC 60502-2
Copper / Aluminium conductor, PVC/PE sheathed cable
XLPE insulated
Copper wire / tape screened, PVC/PE sheathed cable
DIMENSIONAL AND ELECTRICAL DATA 3 CORES
2
Nominal cross-sectional area mm 50 70 95 120 150 185 240 300 400
Conductor diameter (approx) mm 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
Insulation diameter (approx) mm 25.9 27.5 29.3 30.7 31.9 33.9 36.3 38.5 41.3
Nominal outer sheath thickness mm 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.4 2.5
Overall cable diameter (approx) mm 68 71 75 79 81 86 91 97 103
Copper/Aluminium conductor,
XLPE insulated, Galvanized double
steel tape armoured,
PVC/PE sheathed cable N2XBY/NA2XBY
1.8/3(3.6) kV
IEC 60502-1
N2XBY / NA2XBY
1.8/3(3.6) kV
Copper/Aluminium conductor,
XLPE insulated, Galvanized double
IEC 60502-1
Cooper / Aluminium conductor, XLPEsteel tape armoured,
insulated,
PVC/PE sheathed cable
Galvanized steel tape armoured, PVC/PE sheathed cable
N2XSEYBYCopper/Aluminium
/ NA2XSYBY conductor, XLPE insulated,
3.6/6(7.2) kV Copper tape screened,
SPLN 43-5 / Galvanized
IEC 60502-2double steel tape armoured,
Copper / Aluminium conductor, XLPE insulated,
PVC/PE sheathed cable
with or without swellable tape, Copper wire / tape screened,
Glavanized steel tape armoured, PVC/PE sheathed cable
DIMENSIONAL AND ELECTRICAL DATA 3 CORES
2
Nominal cross-sectional area mm 25 35 50 70 95 120 150 185 240 300 400
Conductor diameter (approx) mm 6.05 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness
Insulation diameter (approx)
mm
mm
2.5
12.5
2.5
13.5
2.5
14.7
2.5
N2XSEYBY / NA2XSYBY
16.3
2.5
18.1
2.5
19.5
2.5
20.7
2.5
22.7
2.6
24.8
2.8
27.9
3.0
31.9
Nominal tape armour thickness
Nominal outer sheath thickness
mm
mm
0.5
2.2
0.5
2.3
0.5
2.4
0.5
2.5
0.5
2.6
3.6/6(7.2) kV
0.5
2.7
0.5
2.8
0.5
2.9
0.5
3.1
0.5
3.3
0.8
3.6
Overall cable diameter (approx) mm 39 42 45 49 SPLN 43-5 / IEC 60502-2
53 53 59 64 70 76 85
CU 2,800 3,200 3,800 4,700 5,800 6,800 7,900 9,400 11,700 14,100 18,300
Cable net weight ( approx)
AL
Kg/Km
2,300 2,600 Copper / Aluminium conductor, XLPE insulated,
2,900 3,400 4,000 4,600 5,100 5,900 7,000 8,300 10,900
Standard length per-reel
Minimum bending radius
m 500 with or without swellable tape, Copper wire / tape screene
500 500 500 500 500 500 500 350 350 350
mm 340 370 400 440 490 520 550 600 670 730 820
Max. DC conductor resistance CU 0.727 0.524
Glavanized steel tape armoured, PVC/PE sheathed cab
0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
Ω/Km
at 20 ⁰C AL 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778
Min. insulation resistance at 20 ⁰C DIMENSIONAL
MΩ.Km AND ELECTRICAL
900 800 DATA
700 600 500 500 500 400 400 400 400
Capacitance per phase µF/Km
Nominal 0.191
cross-sectional 0.216
area 0.240 0.279
mm
2 0.318
25 0.349
35 0.376
50 0.41970 0.45995 0.481
120 0.511
150 185
Inductance per phase mH/km diameter
Conductor 0.322(approx)
0.308 0.298 0.284
mm 0.273
6.05 0.266
7.1 0.261
8.25 0.254
9.9 0.249
11.7 0.246
13.1 0.243
14.3 16.3
Max.short circuit current of CU Nominal insulation
3.73thickness
5.18 7.36 10.26
mm 13.88
2.5 17.49
2.5 21.81
2.5 26.86
2.5 34.78
2.5 43.41
2.5 57.79
2.5 2.5
conductor kA/sec diameter
AL Insulation 2.49(approx)
3.45 4.89 6.81
mm 9.19
12.5 11.58
13.5 14.43
14.7 17.76
16.3 22.98
18.1 28.67
19.5 38.14
20.7 22.7
Max.short circuit current of screen 1.90 thickness
Nominal tape armour 2.05 2.21 2.44
mm 2.69
0.5 2.89
0.5 3.05
0.5 3.330.5 3.70
0.5 4.06
0.5 4.51
0.5 0.5
CU Nominal outer sheath
139 thickness
172 205 256
mm 3122.2 3592.3 4092.4 4682.5 5522.6 6272.7 7582.8 2.9
Maximum current in air
AL Overall cable diameter
102 132
(approx) 159 198
mm 23939 27742 31445 36049 42053 47953 59159 64
carrying A
o CU 132 170 201CU 245 294
2,800 334
3,200 375
3,800 424
4,700 492
5,800 552
6,800 623
7,900 9,400
capacity at 30 C in ground
AL Cable net weight101( approx) 130 155AL Kg/Km
190 228
2,300 259
2,600 291
2,900 330
3,400 384
4,000 412
4,600 493
5,100 5,900
AC test voltage kV/5 min
Standard length per-reel m 12.5
500 (IEC) 500
, 9 (SPLN) 500 500 500 500 500 500
Note : This is only general information. ForMinimum
other specific
bendingrequirement,
radius please contact our
mmmarketing.
340 370 400 440 490 520 550 600
Max. DC conductor resistance CU 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.099
Ω/Km
at 20 ⁰C AL 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.16
Min. insulation resistance at 20 ⁰C MΩ.Km 900 800 700 600 500 500 500 400
Capacitance per phase µF/Km 0.191 0.216 0.240 0.279 0.318 0.349 0.376 0.41
Inductance per phase mH/km 0.322 0.308 0.298 0.284 0.273 0.266 0.261 0.25
Max.short circuit current of CU 3.73 5.18 7.36 10.26 13.88 17.49 21.81 26.8
conductor AL kA/sec 2.49 3.45 4.89 6.81 9.19 11.58 14.43 17.7
Max.short circuit current of screen 1.90 2.05 2.21 2.44 2.69 2.89 3.05 3.33
CU 139 172 205 256 312 359 409 468
Maximum current in air
AL26 102 132 159 198 239 277 314 360
carrying A
o CU 132 170 201 245 294 334 375 424
capacity at 30 C in ground
N2XSEBY/NA2XSEBY
6/10(12) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated,
Copper tape screened,
Galvanized double steel tape armoured,
PVC/PE sheathed cable
N2XSEBY/NA2XSEBY
6/10(12) kV
IEC 60502-2
N2XSEYBY / NA2XSEYBY
Copper/Aluminium conductor,
6/10(12) kV
XLPE insulated,
SPLN 43-5 / IEC 60502-2 Copper tape screened,
Galvanized
Copper / Aluminium conductor, XLPEdouble steel tape armoured,
insulated,
PVC/PE
with or without swellable, Copper wire / tape sheathed
screened, cable
Galvanized steel tape armoured, PVC/PE sheathed cable
DIMENSIONAL AND ELECTRICAL DATA 3 CORES
2
Nominal cross-sectional area mm 25 35 50 70 95 120 150 185 240 300 400
Conductor diameter (approx) mm 6.05 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
Insulation diameter (approx) mm 14.3 15.3 16.5 18.1 19.9 21.3 22.5 24.5 26.9 29.1 31.9
Nominal tape armour thickness mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.8
Nominal outer sheath thickness mm 2.3 2.4 2.5 2.6 2.8 2.9 3.0 3.1 3.3 3.4 3.7
Overall cable diameter (approx)
Kg/Km
44
3,200
46
3,700
49
4,300 N2XSEYBY / NA2XSEYBY
53
5,200
57
6,400
61
7,400
64
8,500
68
10,000
74
12,300
79
14,600
87
18,700
N2XSEBY/NA2XSEBY
8.7/15(17.5) kV
IEC 60502-2
N2XSEYBY / NA2XSEBY
Copper/Aluminium
8.7/15(17.5) kV conductor, XLPE insulated,
Copper tape screened,
SPLN 43-5 / Galvanized
IEC 60502-2double steel tape armoured,
Copper / Aluminium conductor, XLPE insulated,
PVC/PE sheathed cable
with or without swellable tape, Copper wire / tape screened,
Galvanized steel tape armoured, PVC/PE sheathed cable
N2XSEBY/NA2XSEYBY
12/20(24) kV
SPLN 43-5/IEC 60502-2
N2XSEYBY / NA2XSEYBY
Copper/Aluminium
12/20(24) kV conductor, XLPE insulated,
with or without water sealing,
SPLN 43-5 / IEC 60502-2
Copper wire screened,
Copper / Aluminium conductor,
GalvanizedXLPE insulated,
double steel tape armoured,
with or without swellable tape, Copper wire / tape
PVC/PE sheathed screened,
cable
Galvanized steel tape armoured, PVC/PE sheathed cable
N2XSEBY/NA2XSEBY
18/30(36) kV
N2XSEYBY / NA2XSEBY
IEC 60502-2
18/30(36)Copper/Aluminium
kV conductor,
IEC 60502-2
XLPE insulated, Copper tape screened,
Galvanized
Copper / Aluminium double
conductor, XLPEsteel tape armoured,
insulated,
PVC/PE sheathed cable
Copper wire / tape screened, Galvanized steel tape armoured,
PVC/PE sheathed cable
DIMENSIONAL AND ELECTRICAL DATA 3 CORES
2
Nominal cross-sectional area mm 50 70 95 120 150 185 240 300 400
Conductor diameter (approx) mm 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
Insulation diameter (approx) mm 25.9 27.5 29.3 30.7 31.9 33.9 36.3 38.5 41.3
N2XSEYBY / NA2XSEBY
Nominal tape armour thickness mm 0.5 0.5 0.5 0.8 0.8 0.8 0.8 0.8 0.8
Nominal outer sheath thickness mm 3.2 3.3 3.5 3.6 3.7 3.9 4.0 4.2 4.4
Overall cable diameter (approx)
Kg/Km
72
7,300
75
8,400
80
9,700 18/30(36) kV
84
11,700
87
12,900
92
14,800
98
17,300
103
20,000
110
23,500
Copper/Aluminium conductor,
XLPE insulated,
Galvanized flat steel wire armoured,
PVC/PE sheathed cable
N2XFGbY/NA2XFGbY
1.8/3(3.6) kV
IEC 60502-1
N2XFGbY/NA2XFGbY
Copper/Aluminium conductor,
1.8/3(3.6) kV XLPE insulated,
IEC 60502-1Galvanized flat steel wire armoured,
Copper / Aluminium conductor, XLPE insulated,
PVC/PE sheathed cable
Copper wire / tape screened, Galvanized flat steel wire armoured,
PVC/PE sheathed cable
31
N2XSEFGbY/
NA2XSEFGbY
3.6/6(7.2) kV
IEC 60502-2
N2XSEYFGbY/NA2XSEFGbY
Copper/Aluminium conductor, XLPE insulated,
3.6/6(7.2) kV Copper tape screened,
SPLN 43-5 / IECGalvanized
60502-2 flat steel wire armoured,
PVC/PE
Copper / Aluminium conductor, XLPE sheathed cable
insulated,
with or without swellable tape, Copper wire / tape screened,
Galvanized flat steel wire armoured, PVC/PE sheathed cable
Copper/Aluminium conductor,
XLPE insulated,
Copper tape screened,
Galvanized flat steel wire armoured,
N2XSEFGbY/
PVC/PE sheathed cable NA2XSEFGbY
8.7/15(17.5) kV
IEC 60502-2
N2XSEYFGbY/NA2XSEFGbY
Copper/Aluminium conductor,
8.7/15(17.5) kV
XLPE insulated,
IEC 60502-2 Copper tape screened,
Galvanized
Copper / Aluminium conductor, flat steel wire armoured,
XLPE insulated,
PVC/PE
with or without swellable tape, Copper wire / tapesheathed
screened, cable
Galvanized flat steel wire armoured, PVC/PE sheathed cable
Copper/Aluminium conductor,
XLPE insulated, N2XSEFGbY/
with or without water sealing,
Copper wire screened, NA2XSEYFGbY
Galvanized flat steel wire armoured, 12/20(24) kV
PVC/PE sheathed cable
SPLN 43-5/IEC 60502-2
N2XSEYFGbY/NA2XSEYFGbY
Copper/Aluminium conductor,
12/20(24) kV
XLPE insulated,
IEC 60502-2 with or without water sealing,
Copper / Aluminium conductor,Copper wire screened,
XLPE insulated,
with or without swellable tape,Galvanized
Copper wireflat steelscreened,
/ tape wire armoured,
Galvanized flat steel wire armoured, PVC/PE sheathedcable
PVC/PE sheathed cable
Copper/Aluminium conductor,
XLPE insulated,
N2XSEFGbY/
Copper tape screened, NA2XSEFGbY
Galvanized flat steel wire armoured,
PVC/PE sheathed cable
18/30(36) kV
IEC 60502-2
N2XSEYFGbY/NA2XSEYFGbY
Copper/Aluminium conductor,
18/30(36) kV
XLPE insulated,
IEC 60502-2
Copper tape screened,
Copper / Aluminium conductor, XLPE
Galvanized insulated,
flat steel wire armoured,
Copper wire / tape screened, Galvanized flat steel wire
PVC/PE armoured
sheathed cable
PVC/PE sheathed cable
IEC 60502-2
Conductor diameter (approx) mm 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
Insulation diameter (approx) mm Copper / Aluminium
25.9 27.5 31.9 conductor,
29.333.9 36.3 XLPE
30.7 38.5insulated,
41.3
mm
Nominal flat wire armour thickness
Nominal outer sheath thickness mm
0.8
3.2
0.8
3.3
0.8
Copper wire / tape screened,
3.7
0.8
3.5
0.8
3.8
0.8
0.8
Galvanized3.6
4.0
0.8 0.8
flat4.1steel wire
4.4
arm
Overall cable diameter (approx) mm 72 76 PVC/PE
86 80sheathed
91 97 cable
83 102 109
CU 7,500 8,600 10,000 11,200 12,400 14,100 16,600 19,200 22,700
Cable net weight ( approx) Kg/Km
AL 6,600 7,300 8,100 8,900 9,500 10,600 11,900 13,400 15,300
DIMENSIONAL AND ELECTRICAL DATA
Standard length per-reel m 500 500 500 350 350 350 300 300 300
Nominal cross-sectional area mm2 50 70 95 120 150 185
Minimum bending radius mm 600 640 690 720 750 810 870 920 1,000
Conductor diameter (approx) mm 8.25 9.9 11.7 13.1 14.3 16.3
Max. DC conductor resistance CU 0.387 0.268 0.193 0.153 8.00.124 0.0991
8.0 0.0754
8.0 0.0601
8.0 0.0470
8.0 8.0
o
Nominal insulation
Ω/Km thickness mm
at 20 C AL 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778
Insulation diameter (approx) mm 25.9 27.5 29.3 30.7 31.9 33.9
Min. insulation resistance at 20 oC MΩ.Km 1,600 1,500 1,300 1,200 1,200 1,100 1,000 900 800
Nominal flat wire armour thickness mm 0.8 0.8 0.8 0.8 0.8 0.8
Capacitance per phase µF/Km 0.121 0.136 0.151 0.163 0.173 0.190 0.209 0.227 0.250
Nominal outer sheath thickness mm 3.2 3.3 3.5 3.6 3.7 3.8
Inductance per phase mH/km 0.429 0.404 0.383 0.369 0.359 0.344 0.330 0.319 0.307
Overall cable diameter (approx) mm 72 76 80 83 86 91
Max.short circuit current of CU 7.36 10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.79
CU 7,500 8,600 10,000 11,200 12,400 14,100
conductor Cable
AL net weight
kA/sec ( approx)4.89 6.81 9.19 Kg/Km11.58 14.43 17.76 22.98 28.67 38.14
AL 6,600 7,300 8,100 8,900 9,500 10,600
Max.short circuit current of screen 3.77 4.00 4.25 4.45 4.62 4.9 559 5.54 5.93
Standard length per-reel m 500 500 500 350 350 350
CU 207 258 314 361 411 470 554 630 766
Maximum current in air Minimum bending radius mm 600 640 690 720 750 810
AL 162 205 246 283 320 365 426 482 594
carrying Max. DC conductor
A resistance CU 0.387 0.268 0.193 0.153 0.124 0.0991
o CU o 203 247 296 Ω/Km336 377 426 488 555 626
capacity at 30 C in ground at 20 C AL 0.641 0.443 0.320 0.253 0.206 0.164
AL 155 187 224 256 284 322 373 415 496
Min. insulation resistance at 20 oC MΩ.Km 1,600 1,500 1,300 1,200 1,200 1,100
AC test voltage kV/5 min 63
Capacitance per phase µF/Km 0.121 0.136 0.151 0.163 0.173 0.190
Note : This is only general information. For Inductance
other specific
per requirement,
phase please contact our marketing.
mH/km 0.429 0.404 0.383 0.369 0.359 0.344
Max.short circuit current of CU 7.36 10.26 13.88 17.49 21.81 26.86
conductor AL kA/sec 4.89 6.81 9.19 11.58 14.43 17.76
Max.short circuit current of screen 3.77 4.00 4.25 4.45 4.62 4.9
CU 207 258 314 361 411 470
Maximum current in air
AL 162 205 246 283 320 365
carrying A
CU 203 247 296 336 377 426
capacity at 30 oC in ground
AL 155 187 224 256 284 322
AC test voltage
36 kV/5 min 63
N2XKBY/NA2XKBY
1.8/3(3.6) kV
IEC 60502-1
Copper/Aluminium conductor,
XLPE insulated, Copper tape screened, N2XSEKBY/
Lead sheathed, Galvanized double
steel tape armoured, PVC/PE sheathed cable
NA2XSEKBY
3.6/6(7.2) kV
IEC 60502-2
N2XSEKBY / NA2XSEKBY
Copper/Aluminium conductor,
3.6/6(7.2) kV
XLPE insulated, Copper tape screened,
IEC 60502-2
Lead
Copper / Aluminium conductor, sheathed,
XLPE Galvanized double
insulated,
steel tape
Copper wire / tape screened, armoured,
Lead sheathed, PVC/PE sheathed cable
Galvanized steel tape armoured, PVC/PE sheathed cable
Copper/Aluminium conductor,
XLPE insulated,
Copper tape screened, Lead sheathed,
Galvanized double steel tape armoured, N2XSEKBY/
PVC/PE sheathed cable NA2XSEKBY
8.7/15(17.5) kV
IEC 60502-2
N2XSEKBY / NA2XSEKBY
Copper/Aluminium conductor,
8.7/15(17.5) kV
XLPE insulated,
Copper tape screened, Lead sheathed,
IEC 60502-2
Galvanized
Copper / Aluminium conductor, XLPE double
insulated,steel tape armoured,
PVC/PE
Copper wire / tape screened, Lead sheathed cable
sheathed,
Galvanized steel tape armoured, PVC/PE sheathed cable
N2XSEKBY/
NA2XSEKBY
18/30(36) kV
N2XSEKBY / NA2XSEKBY
IEC 60502-2
18/30(36) kV
Copper/Aluminium conductor, XLPE insulated,
IEC 60502-2
Copper tape screened, Lead sheathed,
Galvanized
Copper / Aluminium conductor, double
XLPE steel tape armoured,
insulated,
PVC/PE sheathed
Copper wire / tape screened, Lead sheathed, cable
Galvanized steel tape armoured, PVC/PE sheathed cable
IEC 60502-2
AL 14,700 16,000 17,700 19,200 20,200 22,500 25,000 27,700 31,300
Standard length per-reel m 500 500 500 350 350 350 250 250 250
Minimum bending radius
Max. DC conductor resistance CU
mm 680
0.387
Copper / Aluminium conductor, XLPE insulated,
730
0.268
780
0.193
820
0.153
850
0.124
900
0.0991
970
0.0754
1,030
0.0601
1,100
0.0470
o
at 20 C AL
Ω/Km
0.641 Copper wire / tape screened, Lead sheathed,
0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778
Min. insulation resistance at 20 oC MΩ.Km 1,600
Galvanized steel tape armoured, PVC/PE sheathed cab
1,500 1,300 1,200 1,200 1,100 1,000 900 800
Capacitance per phase µF/Km 0.121 0.136 0.151 0.163 0.173 0.190 0.209 0.227 0.250
Inductance per phase mH/km 0.402 0.381 0.363 0.352 0.343 0.330 0.317 0.308 0.297
Max.short circuit current of DIMENSIONAL
CU AND ELECTRICAL 7.36 DATA
10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.79
2
conductor NominalAL cross-sectional
kA/sec area4.89 6.81 9.19mm 11.58 50 14.43 70 17.76 95 22.98120 28.67150 38.14185
Max.short circuit current of screen Conductor diameter (approx) 3.77 4.00 4.25mm 4.45 8.25 4.62 9.9 4.9 11.7 559 13.1 5.54 14.3 5.93 16.3
NominalCUinsulation thickness 204 254 309mm 355 8.0 405 8.0 463 8.0 546 8.0 620 8.0 754 8.0
Maximum current in air
Insulation
AL diameter (approx) 159 202 242mm 279 25.9 315 27.5 359 29.3 419 30.7 475 31.9 585 33.9
carrying A
NominalCUlead thickness 200 243 291mm 331 2.6 371 2.7 419 2.8 485 2.9 546 2.9 616 3.1
capacity at 30 oC in ground
NominalALtape armour thickness 152 184 220mm 252 0.8 280 0.8 317 0.8 367 0.8 409 0.8 488 0.8
AC test voltage Nominal outerkV/5
sheathminthickness mm 3.6 63 3.7 3.9 4.0 4.1 4.2
Note : This is only general information.Overall cable
For other diameter
specific (approx) please contact our marketing.
requirement, mm 83 87 92 96 99 104
CU 15,600 17,400 19,600 21,600 23,100 26,100
Cable net weight ( approx) Kg/Km
AL 14,700 16,000 17,700 19,200 20,200 22,500
Standard length per-reel m 500 500 500 350 350 350
Minimum bending radius mm 680 730 780 820 850 900
Max. DC conductor resistance CU 0.387 0.268 0.193 0.153 0.124 0.0991
o Ω/Km
at 20 C AL 0.641 0.443 0.320 0.253 0.206 0.164
Min. insulation resistance at 20 oC 42 MΩ.Km 1,600 1,500 1,300 1,200 1,200 1,100
Capacitance per phase µF/Km 0.121 0.136 0.151 0.163 0.173 0.190
Inductance per phase
N2XALCAY/
NA2XALCAY
1.8/3(3.6) kV
IEC 60502-1
44
N2XSEALCAY/
NA2XSEALCAY
6/10(12) kV
IEC 60502-2
45
N2XSEALCAY/
NA2XSEALCAY
8.7/15(17.5) kV
IEC 60502-2
46
N2XSEALCAY/
NA2XSEALCAY
12/20(24) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated, Copper tape screened, N2XSEALCAY/
Aluminium corrugated tape armoured,
PVC/PE sheathed cable
NA2XSEALCAY
18/30(36) kV
IEC 60502-2
N2XSEalcaY / NA2XSEalcaY
18/30(36) kV
Copper/Aluminium conductor,
IEC 60502-2
XLPE insulated, Copper tape screened,
Aluminium
Copper / Aluminium conductor, corrugated tape armoured,
XLPE insulated,
PVC/PE
Copper wire / tape screened, Welded continuously sheathed
corrugarted cable
armoured,
PVC/PE sheathed cable
49
NF2XSY/NFA2XSY
12/20(24) kV
SPLN 43-5/IEC 60502-2
R
R S T
d or or
2d 2d S T
Load factor = 1.0
Maximum operating conductor temperature :
C ( PVC insulation ) and C ( XLPE insulation )
No other heat sources installed near the group of cables.
Cable laying :
in air : - Ambient temperature
- The cable have to protected against heat radiation of the sun as well as
sufficiently large and ventilated rooms whose temperature is not percep-
tibly increased by the heat dissipating from the loaded cable.
NOTE :
If the actual installed conditions are different from the above mentioned condition, the tabulated
current ratings should be multiplied by the appropriate derating factors as shown in tables on
the next pages.
53
DERATING FACTORS
A. Grouping in the ground.
Ground temperatures (
20 25 30 35 40 45 50
XLPE insulation 1.08 1.04 1.00 0.96 0.91 0.87 0.82
PVC insulation 1.12 1.07 1.00 0.94 0.87 0.79 0.71
2 Variation in thermal resistivity of soil.
Thermal resistivity of soil
Number 0f grouping
1 2 3 4 5 6 8 10
XLPE insulation 1.00 0.86 0.76 0.71 0.67 0.64 0.60 0.57
PVC insulation 1.00 0.85 0.75 0.68 0.64 0.60 0.56 0.53
d d
Number 0f grouping
1 2 3 4 5 6 8 10
XLPE insulation 1.00 0.89 0.82 0.78 0.75 0.73 0.70 0.68
PVC insulation 1.00 0.90 0.82 0.79 0.76 0.74 0.71 0.69
Number 0f grouping
1 2 3 4 5 6 8 10
XLPE insulation 1.00 0.87 0.77 0.73 0.70 0.68 0.65 0.63
PVC insulation 1.00 0.87 0.78 0.74 0.70 0.68 0.65 0.63
54
B. Grouping in air.
1 Variation in air temperature.
20 25 30 35 40 45 50 55
XLPE insulation 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76
PVC insulation 1.12 1.07 1.00 0.93 0.87 0.79 0.71 0.61
2 2 d c c c d
um er of
2 cm
d
Derating factor
d
d
troughs
1 0.92 0.89 0.88
cm
Touching
d
55
B. Grouping in air ( continued )
2.2 Trefoil formation.
Derating factor
2
2d d
2d
2
0.95 0.90 0.88
2d
2d d
Number of Derating factor
troughs
1 0.95 0.90 0.88
2 0.90 8.85 0.83
2
is 2.0 cm.
56
B. Grouping in air (continued ).
3 Multicore cables in three phase system and single core cables in DC system.
3.1 Minimum distance from the wall is 2.0 cm.
Clearance between cables = Cable diameter (d)
umber of system
1 2 3 6 9
d
2 0.90 0.85 0.83 0.81 0.80
3 0.88 0.83 0.81 0.79 0.78
cm
d
6 0.86 0.81 0.79 0.77 0.76
d
d
1.00 0.93 0.90 0.87 0.86
cm
57
B. Grouping in air ( continued ).
Number of system
1 2 3 6 9
Derating factor
2 cm
58
CONVERSION TABLE
Nominal cross
Nominal cross Wire gauge sectional area Wire gauge
sectional area
Circular Equivalent Circular Equivalent
mm2 Inc2 Mils Metric AWG BWG SWG mm2 Inc2 Mils Metric AWG BWG SWG
( CM ) CSA ( CM ) CSA
0.0005 644 0.325 22 - - 0.0290 36,874 18.68 - - 6
0.0006 487 0.397 - 22 22 0.0324 41,217 20.88 - 6 -
0.0006 821 0.416 21 - - 0.0326 41,750 21.15 4 - -
0.50 0.0008 987 - - - - 0.0353 44,948 22.77 - - 5
0.0008 1,021 0.517 20 - - 0.0380 48,402 24.52 - 5 -
0.0008 1,025 0.519 - 21 21 25 0.0388 49,350 - - - -
0.0009 1,198 0.607 - 20 - 0.0413 52,627 26.66 3 - -
0.0010 1,289 0.653 19 - - 0.0423 53,831 27.27 - - 4
0.0010 1,297 0.657 - - 20 0.0445 56,654 28.70 - 4 -
0.0013 1,601 0.811 - - 19 0.0499 63,523 32.18 - - 3
0.75 0.0012 1,481 - - - - 0.0521 66,386 33.63 2 - -
0.0013 1,625 0.823 18 - - 0.0527 67,096 33.99 - 3 -
0.0014 1,765 0.894 - 19 - 35 0.0543 69,090 - - - -
1.0 0.0016 1,974 - - - - 0.0598 76,196 28.60 - - 2
0.0016 2,053 1.040 17 - - 0.0633 80,677 40.87 - 2 -
0.0016 2,304 1.167 - - 18 0.0657 83,717 42.41 1 - -
0.0019 2,402 1.217 - 18 - 0.0707 90,014 45.60 - 1 1
0.0020 2,584 1.309 16 - - 50 0.0775 98,700 - - - -
1.5 0.0023 2,961 - - - - 0.0824 404,997 53.19 - - 1/0
0.0025 3,137 1.589 - - 17 0.0829 105,589 53.49 1/0 - -
0.0026 3,257 1.650 15 - - 0.0908 115,637 58.58 - 1/0 -
0.0026 3,366 1.705 - 17 - 0.0951 121,125 61.36 - - 2/0
0.0032 4,096 2.075 - - 16 0.1045 133,087 67.42 2/0 - -
0.0032 4,108 2.081 14 - - 70 0.1085 138,180 - - - -
0.0033 4,226 2.141 - 16 - 0.1087 138,417 70.12 - - 3/0
2.5 0.0039 4,935 - - - - 0.1134 144,438 73.17 - 2/0 -
0.0040 5,180 2.624 13 - - 0.1257 160,032 81.07 - - 4/0
0.0040 5,186 2.627 - 15 15 0.1318 167,849 85.03 3/0 - -
0.0050 6,402 3.243 - - 14 0.1419 180,660 91.52 - 3/0 -
0.0051 6,532 3.309 12 - - 0.1466 186,661 94.56 - - 5/0
0.0054 6,891 3.491 - 14 - 95 0.1473 187,530 - - - -
4 0.0062 7,896 - - - - 0.1616 206,086 104.40 - 4/0 -
0.0065 8,236 4.172 11 - - 0.1691 211,613 107.20 4/0 - -
0.0066 8,466 4.269 - - 13 0.1860 215,363 109.10 - - 6/0
0.0071 9,072 4.573 - 13 - 120 0.1860 236,880 - - - -
0.0082 10,387 5.262 10 - - 0.1963 249,987 126.64 - - -
0.0085 10,819 5.481 - - 12 0.1964 250,106 126.70 - 5/0 7/0
0.0093 11,883 6.020 - 12 - 0.2091 266,332 134.92 5/0 - -
6 0.0093 11,844 - - - - 150 0.2325 296,100 - - - -
0.0103 13,092 6.632 9 - - 0.2356 300,048 152.00 - - -
0.0106 13,459 6.816 - - 11 0.2642 336,488 170.46 6/0 - -
0.0113 14,404 7.297 - 11 - 185 0.2868 365,190 - - - -
0.0129 16,388 8.302 - - 10 0.3142 400,150 202.71 - - -
0.0130 16,518 8.368 8 - - 240 0.3720 473,760 - - - -
0.0141 17,959 9.098 - 10 - 0.3927 500,113 253.35 - - -
10 0.0155 19,740 - - - - 300 0.4650 592,200 - - - -
0.0163 20,766 10.520 - - 9 0.4712 600,096 304.00 - - -
0.0164 20,826 10.550 7 - - 0.5498 700,198 354.71 - - -
0.0172 21,911 11.100 - 9 - 400 0.6200 789,600 - - - -
0.0201 25,603 12.970 - - 8 0.6283 800,161 405.35 - - -
0.0206 26,254 13.300 6 - - 500 0.7750 987,000 - - -
0.0214 27,241 13.800 - 8 - 0.7854 1,000,246 506.71 - - -
0.0243 30,992 15.700 - - 7 625 0.9688 1,233,750 - - - -
16 0.0248 31,584 - - - - 630 0.9765 1,243,620 - - - -
0.0255 32,413 16.420 - 7 - 800 1.2400 1,597,200 - - - -
0.0260 33,104 16.770 5 - - 1,000 1.5500 1,974,000 - - -- --