DESCRIPTION
The EQ3710AIM 8 Channel Analog Input Module
expands the input capability of the Det-Tronics Eagle
Quantum Premier® System.
APPROVED
Ex nA nL nC IIC Gc EN60079-29-1
POWER REQUIREMENTS— DEMKO 03 ATEX 136207U
Module power consumption: 6 watts. Tamb = –40°C to +85°C.
When supplying power to three-wire transmitters:
Maximum current at power input: 7.4 amperes. IECEx: IECEx ULD 10.0004U.
Output current: 900 mA per channel maximum. Ex nA nL nC IIC Gc.
Tamb = –40°C to +85°C.
INPUT/OUTPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not SIL: IEC 61508:2000
cause damage to the equipment. Certified SIL 2 Capable.
Applies to specific models –
TEMPERATURE RANGE— Refer to the SIL 2 Certified
Operating: –40°C to +85°C (–40°F to +185°F). EQP Safety manual (95-8599).
Storage: –55°C to +85°C (–67°F to +185°F).
HUMIDITY RANGE—
0 to 95% RH, non-condensing.
VIBRATION—
FM 3260-2000 (clause 4.9).
1.35 2.5
(3.4) (6.4)
1 6 1 6 1 6 1 6
5.02
(12.7)
4.5
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 (11.3)
4.5
A B C A B C A B C A B C A B C A B C A B C A B C (11.3) A B C A B C A B C A B C A B C A B C A B C A B C
5.2
5.2 1.66 (13.2) 1.9
A2449 (13.2) (4.2) (4.8)
2.2 2 90-1183
INSTALLATION Power Connector — Terminals 1 to 6
24 Vdc Power Input
MOUNTING 1 — +
24 VDC
The Analog Input Module must be properly installed 2 — –
in a suitable enclosure that is rated for the location. 3 — Shield*
The enclosure must provide space to install and wire 4 — +
24 VDC
the device and must also provide for ground wire 5 — –
termination. Access into the enclosure must be gained 6 — Shield*
by using a special tool to open the enclosure. The
enclosure should be rated for the temperature range of *Shields on power wires are optional unless required
the location plus the temperature rise of all equipment by local codes.
installed inside the enclosure. The enclosure must
be rated for electrical equipment that is going to be Connect the module power supply to terminals 1 and
installed. 2. If additional terminals are required for powering
other devices, these devices should be connected
NOTE to terminals 4 and 5. Shields are to be connected to
It is recommended to maintain a minimum of 4 terminals 3 and 6.
inches clearance between the module and other
equipment to provide adequate room for wiring COM Connector — Terminals 1 to 6
and ventilation. LON Terminals
Be sure to observe polarity when wiring the LON.
WIRING 1 — “A” side of signaling circuit for COM 1
2 — “B” side of signaling circuit for COM 1
All electrical connections are made to the field wiring 4 — “A” side of signaling circuit for COM 2
connectors furnished with the module. (Connectors 5 — “B” side of signaling circuit for COM 2
accept up to 12 AWG wire.) Refer to Figure 2 for 3 & 6 — shield connections (shields required).
identification of module wiring terminals.
EQ3710AIM
COMMON C 24
4-20 MA IN B 23 CHANNEL 8
SHLD 6 COM 2 SHLD + SUPPLY A 22
LON FROM
B 5 COM 2 B
PREVIOUS DEVICE
A 4 COM 2 A COMMON C 21
COMMON C 15
4-20 MA IN B 14 CHANNEL 5
+ SUPPLY A 13
TO
EARTH
GROUND COMMON C 12
4-20 MA IN B 11 CHANNEL 4
+ SUPPLY A 10
COMMON C 9
4-20 MA IN B 8 CHANNEL 3
+ SUPPLY A 7
SHLD* 6 SHLD
24 VDC
– 5 – COMMON C 6
INPUT VOLTAGE
+ 4 + 4-20 MA IN B 5 CHANNEL 2
SHLD* 3 SHLD + SUPPLY A 4
24 VDC
– 2 –
INPUT VOLTAGE
+ 1 + COMMON C 3
2.2 3 90-1183
CHANNEL 1 CHANNEL 1 TRANSMITTER
TRANSMITTER
COMMON C 3 COMMON C 3 –
+ SUPPLY A 1 + + SUPPLY A 1 +
A2235 A2236
Figure 3—Two-Wire Transmitter / Detector — Non-Isolated 4 to 20 Figure 5—Three-Wire Transmitter / Detector — Non-Isolated 4 to 20
mA Current Output (Sourcing) mA Current Output (Sourcing)
+ SUPPLY A 1 4 1 + + SUPPLY A 1 4 1 +
A2238 A2239
Figure 4—Two-Wire Transmitter / Detector with HART Interface Figure 6—Three-Wire Transmitter / Detector with HART Interface
Module — Non-Isolated 4 to 20 mA Current Output (Sourcing) Module — Non-Isolated 4 to 20 mA Current Output (Sourcing)