Experimental Study of CFRP Confined Low Strength R.C. Columns Under Concentric Loads PDF
Experimental Study of CFRP Confined Low Strength R.C. Columns Under Concentric Loads PDF
Article History: The paper presents results of an experimental investigation carried out on reinforced,
Received: 30/09/2015 low strength concrete columns strengthened by Carbon Fiber Reinforced Polymers
Accepted: 24/05/2016 (CFRP). The columns were tested under concentric compression until failure. The
shape and the slenderness of the column, the thickness and the configuration of
Published:10/10/2016
confinement were the basic parameters considered in the experimental program. The
Keywords: main objective of the investigation was to study the effectiveness of using CFRP as
Carbon fiber polymers; an external strengthening method to increase the ultimate load of the low concrete
Columns; strength columns. Using the CFRP enhanced the ultimate load of the columns for all
Concentric load; specimens, the increase in ultimate load ranges between 15 % and 291 % compared to
CFRP configuration; the control specimens. The partial confinement is not as effective in increasing the
Shape effect; column ultimate load as compared with full confinement. The CFRP confinement is
not as effective in increasing the ultimate load of square columns as for circular
Slenderness ratio;
columns. The gain in ultimate load increases as the number of CFRP wraps. The
Strengthening; strength behavior was affected by the cross-section shape and slenderness ratio.
Ultimate load.
*Corresponding Author:
Ali Flayeh Hassan1
alzurbati_a@yahoo.com
constructed in accordance with the ACI Code, mm diameter deformed bars. Ø 6 mm diameter
shall not be less than 17 MPa. If the deformed bars were used as transverse
strength of concrete falls below the minimum reinforcement, Table (2) shows the properties
value, it may be classified as low strength of the steel bars used in the present study.
concrete and steps shall be taken to ensure that
load-carrying capacity of the structure is not
jeopardized.
In the search of previous work on the CFRP
confinement of deficient columns (low
compressive strength concrete), it is found that
no investigation has been reported, so that, the MOULDS
aim of this study was generated from this point. Timber moulds having cross sections of 133
The purpose of this study is to evaluate the mm x 133 mm (square section) and 150 mm in
performance of using CFRP in strengthening diameter (circular section) with different three
deficient reinforced concrete columns. The heights were used for casting the specimens.
study includes studies proposed parameters,
which are stated as follow: CASTING AND CURING
1. Column cross section shape. The steel cage was positioned in the center of
2. Number of CFRP layers. the mould, then the mixture was poured in 3
3. Configuration of CFRP wrapping (Full layers each layer was given 25 blows using 18
and Partial). mm diameter standard steel rod. Later further
4. The slenderness ratio (H/D). compaction was made by striking the moulds
5. gently with a rubber hammer to exclude the
EXPERIMENTAL PROGRAM remained air bubbles. The top surface of the
CONCRETE MIX concrete then finished by the mean of trowel
Ordinary Portland cement, gravel, and the specimens were left inside the moulds
natural sand and water were used to prepare the for 24 hours to harden. After demolding the
concrete. The maximum coarse aggregate size specimens were placed in water tank and cured
was 20 mm. the water cement ratio was 0.67. at a temperature of ( ). At the end of
The concrete mix proportion is given in Table curing the specimens were removed from the
(1). water tank and left in the laboratory to dry for 3
days before wrapping with CFRP sheets.
Carbon Fibers and Epoxy Resin
The composite system consisted of carbon fiber
The concrete was cast, compacted, Sikawrap®-230 C and epoxy based resin
finished, demolded, and cured for 28 days in an Sikadur®-330 for impregnation. The carbon
ASTM standard curing room with 100% sheets, breadth 500 mm and thickness 0.166
relative humidity. The 28 day compressive mm, were supplied in rolls of 50 m. The
strength of the unconfined concrete was mechanical properties of the CFRP and epoxy
determined using standard 150.4 mm by 300.8 resin, taken from product catalogues of the
mm cylinders per ASTM 39. The 28-day manufacturer, are presented in Table (3) and
compressive strength was found to be 16 MPa. Table (4), respectively.
Steel reinforcements
All concrete specimens were reinforced with
longitudinal reinforcement consisting of Ø 8
105 Al-Attar M. and Hassan M./ ZJPAS: 2016, 28 (4): 103-112
maximum capacity of 3000 kN. The rate of horizontal strain gauges fixed at the mid-height
loading was constant and kept to 0.4 MPa/sec. of the specimens. Fig (4) shows the testing
All measurements of axial and lateral process of the specimens.
deformations were recorded using vertical and
REFERENCES
LOREZIS, D AND TAPFERS, “Comparative Study of
Models on Confinement of Concrete Cylinders with
Fiber-Reinforced Polymer Composites”, ASCE, Journal
of Composites for Construction, 219-237 (August, 2003)
ACI 440.2R-02, “Guide for the Design and Construction
of Externally Bonded FRP Systems for Strengthening
Concrete Structures, ACI committee 440, American
Concrete Institute.
ILKI, A., AND KUMBASAR, N., “Behavior of
Damaged and Undamaged Concrete Strength by Fiber
Composite Sheets”, Int. Journal of Str. Eng. and Mech.,
13 (1), 2002.
HASSAN, A.F. AND AHMED, A.S., “Stress-strain
behavior of low strength concrete cylinders confined
with CFRP”, Zanko Journal of Pure and Applied
Sciences, Vol. 27, No. 4, 2015, Salahaddin University-
CONCLUSIONS Erbil.
Based on observations of the AREEMIT N., FAEKSIN N., “Strengthening of
experimental work; the following conclusions Deficient RC Columns by Steel Angles and Battens
under Axial Load”, Hokkaido University Collection of
are made for reinforced low strength concrete Scholarly and Academic Paper, (September, 2013).
columns strengthened with CFRP strips. YEHIA, S., “Behavior of Low Compressive Strength
1. External strengthening of the columns Short Columns Strengthened with External GFRP
Strips/Jacket Techniques”, Int. Journal of Tech.
using CFRP can enhance the column Enhancement and Emerging Eng. Research, Vol. 3, No.
capacity when the CFRP is adequately 4, Issn 2347-4289, 2015.
ACI 318M-11, “Building Code Requirements for
arranged. The partial confinement is not
Structural Concrete and Commentary”, Reported by ACI
as effective in increasing the column Committee 318, 2011.
capacity as compared to full
confinement. For both types of ASTM (2007) ASTM Standards, Manual of Aggregate
and Concrete Testing, American Society for Testing
confinement, the thicker the wrap, the
Materials, Vol. 04-02.
improvement on the behavior becomes
much more significant.
2. The CFRP confinement is not as
effective in increasing the ultimate load
of square columns as compared to