TotalPac®3

Double interlock SUREFIRE Preaction


Self-contained system

(Optional)

DESCRIPTION Standard features

This TOTALPAC®3 integrated fire protection system by FireFlex • cULus Listed & FM Approved as an assembled unit
Systems Inc. consists of a SUREFIRE® system trim totally pre-
assembled, pre-wired and factory tested. All electrical and • Factory assembled, programmed and tested under
mechanical components of the system are contained in one ISO-9001 standards
single unit • Prewired to the Viking VFR-400 releasing control
TOTALPAC®3 preaction systems are built around the Viking trim panel.
using deluge valves model F-1. • Easy and compact installation
SUREFIRE® double interlock preaction systems use • Viking conventional trim rated at 250 psi (1724 kPa)
pneumatic supervision of the automatic sprinkler system, and
an electric detection system. The deluge valve release trim • Galvanized trim piping
uses a normally closed electric solenoid valve controlled by an
approved system releasing control panel with two initiating • Serial number for easy reference
circuits configured for "cross-zoned" operation. One initiating • Corrosion resistant cabinet with flush type handle
circuit is connected to the electric detection system, the other and lock
to a "Low-air" alarm switch. Both the electric detection system
AND "Low-air" alarm switch shall be actuated before the • No open drain cup inside the unit
system releasing control panel energizes the solenoid valve
• numerous modular options to meet the most
open, causing the deluge valve to open. Water will flow from
demanding jobsite requirements
any open sprinklers and any other opening in the sprinkler
system piping Activation of a releasing device alone or • Three styles of modular air supply options
operation of a sprinkler alone will sound an alarm but will NOT
cause the system to fill with water. • Inlet & outlet hydrostatic test ports
A special features offer perfect fail-safe modes, SUREFIRE® • User-friendly standardized operation & installation
preaction systems provide protection with or without electrical manual
power. If a condition occurs that removes both the primary and
secondary power supplies, the pneumatic actuator becomes • Free interactive simulator
the release mechanism and the system will operate as a dry
pipe system.
All the valves are rated up to a maximum of 250 psi WWP
(1724 kPa) max. and are available in the following diameters:

□ 1½" (40 mm) □ 2" (100 mm) □ 3" (80 mm)

□ 4" (100 mm) □ 6" (150 mm) □ 8" (200 mm)

1 of 18 FM-076D-0-64J
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Cabinet

The TOTALPAC®3 cabinets are made of sturdy 14 gauge steel, they are available in four (4) sizes;
23" x 25" x 77" (58.4 x 63.5 x 195.6 cm) for 1½",and 2" systems,
36" x 25" x 77" (91.4 x 63.5 x 195.6 cm) for 3" and 4" system,
46" x 25" x 77" (116.8 x 63.5 x 195.6 cm) for 6" system
54" x 31" x 81" (137.2 x 78.7 x 205.7 cm) for 8" system
All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is
provided with one or two doors, all provided with a neoprene gasket to absorb vibrations.
A field wiring electrical junction boxes is integrated with the cabinet for connection of detection system, auxiliary contacts and
signaling devices. All inputs & outputs are factory wired to a terminal strip (TBA) for contractor's field wiring.
Gauges to indicate air, water supply pressure and priming water pressure are all visible through clear Lexan windows.

IMPORTANT: TOTALPAC®3 units are NOT designed to be installed where they will be subjected to outdoors and/or freezing
conditions. Refer to environmental data for additional details. Subjecting the unit to conditions outside these limitations might
tamper the normal operation of the system.

The cabinet assembly is pre-assembled, pre-wired, and factory tested under ISO-9001 conditions.
Multiple unit installations are easily achieved by manifolding units together at their water inlets but drains shall remain separate
and open.
Sequence of operation (see trim diagram)

In a fire condition, operation of the detection system activates the first initiating circuit in the system releasing control panel, causing
an alarm to activate. When a sprinkler operates, air pressure escapes from the sprinkler piping. The low air alarm switch activates
the second initiating circuit in system releasing control panel. When BOTH initiating circuits have been activated, system releasing
control panel energizes solenoid valve (F1) open.
Pressure is released from the priming chamber of the deluge valve (A1) to the open drain manifold faster than it is supplied through
the restricted orifice (B3). The deluge valve clapper opens to allow water to flow into the system piping and alarm devices, causing
the alarm pressure switch (C1) and optional water motor alarm (C2) to activate. Water will flow from any open sprinklers and/or
other opening in the sprinkler piping.
When the deluge valve operates, the sensing end of the PORV (B9) is pressurized, causing the PORV to open. When the PORV
opens, it drains the priming water pressure to the priming chamber, preventing the deluge valve (A1) from resetting, even if the
open releasing devices close. The deluge valve can only be reset after the system is taken out of service, and the outlet

FM-076D-0-64J 2 of 18
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Systems hydraulic limitations

WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility
of the designer.
Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design.

Piping Equivalent Lengths w/o Piping Equivalent Lengths c/w


System size Usage Range
shut off valve shut off valve
(in.) (gpm)
(m.) (ft.) (m.) (ft.)
1½ 0 – 210 8.3 27.2 8.5 27.9
2 0 – 360 11.65 38.2 11.85 38.9
3 100 - 700 16.8 55.1 20.33 66.7
4 200 – 1400 21.89 71.8 25.33 83.1
6 400 - 3500 33.28 109.15 37.28 122.3
8 750 - 5250 41.15 135 44.71 146.7

System drain flow:

System size USGPM Formula


1½" & 2" 0.5 x (water pressure Psi) + 65 = USGPM
3" 1.2 x (water pressure Psi) + 130 = USGPM
4", 6" & 8" 2.7 x (water pressure Psi) + 215 = USGPM

System size LPM Formula


1½" & 2" 2 x (water pressure Psi) + 235 = LPM
3" 4 x (water pressure Psi) + 490 = LPM
4", 6" & 8" 10 x (water pressure Psi) + 800 = LPM

3 of 18 FM-076D-0-64J
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Standard equipment

Releasing control panel Deluge valve


 120 VAC / 60 Hz, 165VA. The Viking Model deluge valve is a quick-opening,
 220 VAC / 50 Hz, 185VA. differential diaphragm, flood valve with one moving
 12VDC / 12Ah batteries. (factory installed) mechanism. The deluge valve is used to control water flow
 12VDC / 18Ah batteries. (optional) in deluge and preaction sprinkler systems. The valve is held
 Single Zone detection closed by system water pressure trapped in the priming
(Activated by Zone 1 or Zone 2) chamber, keeping the outlet chamber and system piping dry.
 Crossed-Zone detection In fire conditions, when the releasing system operates,
(Activated by Zone 1 and Zone 2) pressure is released from the priming chamber. The deluge
valve clapper opens to allow water to flow into the system
The releasing control panel integrated into the TOTALPAC®3
piping.
cabinet is Viking's Model VFR-400. This panel includes four
Class B, programmable detection zones (optional Class A);
two Class B supervisory zones and four Class B,
programmable output circuits (optional Class A). It is also
provided with menu driven programming, including a specific
program assigned at the factory.
The panel is compatible with many types of fire alarm &
supervisory devices such as linear heat detectors, spot-type
heat and smoke detectors, water flow and release indicators,
low and high air pressure switches, manual pull stations.
The releasing control panel also includes an alphanumeric
display with 2 lines of 16 characters describing all the system
conditions, as well as a set of red and yellow LED lamps
individually indicating each of the alarm and trouble
conditions of the system
Easy to operate control buttons are also provided to activate
and operate the system's various functions.
Water supply control valve
Releasing circuit disable switch
The water inlet control valve is a supervised, indicating
The releasing circuit disable switch is used to disable the butterfly valve. Purpose of this vale is to manually shutoff the
releasing solenoid. When the key is set to “Disable”, the preaction system.
releasing solenoid will be disconnected from the control
panel’s releasing circuit, causing a trouble signal and
preventing accidental discharge during maintenance or
inspection.

FM-076D-0-64J 4 of 18
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Standard equipment (continued)

Preaction riser check valve Alarm pressure switch


The Viking spring loaded In-Line check valve is a general The alarm pressure switch monitors the water flow within the
purpose rubber-faced check valve approved for use in fire- sprinkler piping. Should the Deluge Valve clapper opens to
service systems. The Spring Loaded In-Line check valve is allow water to flow into the sprinkler piping. The alarm
manufactured with a brass body, brass seat, and a rubber- pressure switch will activate, indicating a water flow signal.
faced clapper assembly.
POTTER
The Viking Easy Riser® Swing check valve is a general
purpose rubber-faced check valve approved for use in fire PS10-1A
service systems. The valve is for use in preaction system
risers.

Low air supervisory switch


The low pressure switches monitors the pressure within the
sprinkler piping should a loss pressure of the air below 25PSI
occurs, the pressure switch contacts transfer indicating low
air supervisory signal. Should a loss pressure of the air
below 23PSI occurs, the pressure switch contacts transfer
indicating low air alarm signal.

Solenoid valve
The high pressure solenoid valve is a two-way type with one POTTER
inlet and one outlet. It is a packless, internal pilot operated PS40-2A
valve, suitable for use in releasing water pressure from the
priming chamber of Viking deluge valves. The solenoid valve
has floating diaphragm construction, which requires a
minimum pressure drop across the valve to operate
properly.

IN OUT

Pneumatic actuator
Used in conjunction with the solenoid valve, the Viking
Pneumatic Actuator is a spring loaded, rolling diaphragm
and piston operated valve. It is used wherever a combination
is required between the detection and system’s loss of air.

5 of 18 FM-076D-0-64J
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Optional mechanical equipment

 Shut-off valve & sight glass option  Fire department connection


The Shut-off valve & sight glass option is intended to be used The fire department connection option consists of a grooved
for applications where testing of the system operation tee fitting installed at the outlet of the deluge valve (A1). An
without filling the sprinkler piping network is desirable and access hole of the proper diameter is factory pre-drilled on
where it is critical that all functions of the preaction system the side of the TOTALPAC®3 enclosures for connection of the
be tested under actual discharge conditions. Examples of piping going to the fire department connection.
such applications are freezers, ovens, museums, data
processing and other hazards where the possibility of water Note: The fire department connection hardware itself
leaking from the piping system is to be avoided at all costs. (drain, Siamese, etc.) is NOT provided with this option and
shall be provided by the installing contractor. Refer to NFPA-
Warning: Shut-off valve & sight glass option is not 13 Standard for additional information about the equipment
available on 8" systems. layout and installation.

Warning: Fire department connection is not available on


8" systems.

Main drain
valve (D3) Supervised
shut-off valve (D4)
Sight glass
assembly (D5)
Towards fire department
Supervised Grooved tee fitting connection (hardware by
main water with coupling & cap contractor)
Point flash supply valve (D1)
light here

FM-061H-0-75C

FM-061H-0-76C

FM-076D-0-64J 6 of 18
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Optional mechanical equipment (continued)

 Semi and full flanged option  Anti-column device option


When required by the user, TOTALPAC®3 units can be The model LD-1 anti-column device is an optional trim
provided in either a semi-flanged of full flanged component designed for use with preaction sprinkler
configuration. systems. The anti-column device automatically prevents an
The semi flanged option provides flanged fittings only on the unwanted water column from establishing within the system
water inlet pipe (side needs to be specified at the time of riser. On preaction sprinkler systems the anti-column device
order) and on the system riser outlet. The drain manifold is prevents water from columning downstream of the easy riser
then provided with a threaded end that also needs to have check valve.
its side specified (left or right). The rest of the fittings are the
same as usual with the main components being provided in
the standard grooved -grooved configuration.
The full flanged option is the same as above but goes a step
further with the main components being also provided with a From sprinkler riser
flanged-flanged configuration.
When provided, the face of the flanges will always be
situated 6 inches from the outside face of the mounting base
or cabinet surface.

Flanged fitting outside cabinet


(when provided)

To drain collector FM-061H-0-146A

 OSHPD option
Threaded end Pre-approved construction, under OSP-0341-10, using
specific components.
Field connection
to open drain
(specify side)

Field connection
to water supply
(specify side)
Flanged fitting outside cabinet
(when provided) FM-061H-0-77C

7 of 18 FM-076D-0-64J
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Air supply

 Direct air compressor (Style “A”) Compressor Amperage (amps)


Used only for the sprinkler piping network of the preaction Compressor 220Vac / 240Vac /
system. Air supply style "A" includes the air compressor Size (Kw) 50Hz 50Hz
mounted inside the TOTALPAC®3 cabinets with its FLA 1.3 1.3
supervisory trim and options. Compressors are of the 0.12
Start-up 9.1 9.1
tankless, oiless piston type and are factory piped to the FLA 2.5 2.6
sprinkler system riser, all within the TOTALPAC®3 cabinets. 0.25
Start-up 15.5 18.2
FLA 4.0 4.5
Compressors are available in eleven (11) sizes: 0.56
Start-up 28.0 31.5
☐ 1/6HP ☐ 1/2HP ☐ 1-1/2HP FLA 6.0 6.0
1.2
☐ 1/3HP ☐ 1HP ☐ 2HP Start-up 42.0 42.0
☐ 0.12Kw ☐ 0.25Kw ☐ 0.56Kw FLA 6.3 6.0
1.5
☐ 1.2Kw ☐ 1.5Kw Start-up 44.1 42.0

115 / 208 / 230 Vac 60Hz air compressor selection Table:


CFM System capacity to System capacity to
H.P @ fill system to 35 PSI fill system to 55 PSI
Pressure relief valve
40 PSI in 30 minutes * in 30 minutes **
1/6 1.52 154 gal. 81 gal.
This section replaced
by Dehydrator option
(when used) 1/3 3.03 265 gal. 149 gal.
Copper tubing
E4 1/2 4.43 454 gal. 253 gal.
(plugged with SureFire or
non interlock preaction trim)
1 7.46 796 gal. 458 gal.
TO OPTIONAL ACCELERATOR
(plugged when not used) 1-1/2 11.10 1060 gal. 650 gal.
2 14.85 1660 gal. 950 gal.
2 TO DRAIN COLLECTOR
220 / 240 Vac 50Hz air compressor selection Table:
1 TO SPRINKLER RISER

3 CONTRACTOR'S LPM System capacity to System capacity to


TO PNEUMATIC ACTUATOR HYDROSTATIC TEST PORT
@ fill system to 35 PSI fill system to 55 PSI
(plugged when not used) (system side) Kw
FM-061H-0-118C (241 kPa) in 30 (379 kPa) in 30
40 PSI minutes * minutes **
WARNING 1-1/2H, 2HP and 1.5Kw compressors are only 0.12 35.4 462 L 220 L
available for 8" system.
0.25 68 1003 L 492 L
0.56 103 1351 L 723 L
Compressor Amperage (amps)
1.2 178 2316 L 1317 L
Compressor 115Vac / 208Vac / 230Vac /
Size (HP) 60Hz 60Hz 60Hz 1.5 260 3407 L 1912 L
FLA 5.0 2.3 2.5 * For systems with maximum water supply pressure of
1/6
Start-up 35 16.1 17.5 175 PSI (1206 kPa)
FLA 7.4 3.5 3.7
1/3 ** For systems with water supply pressure between
Start-up 51.8 24.5 25.9
FLA 10.0 4.9 5.0 175 PSI (1206 kPa) and 250 PSI (1724 kPa)
1/2
Start-up 70 34.3 35
FLA 18.0 7.7 9.0 WARNING The information contained herewith is for
1 estimation and evaluation purposes only. Its use remains
Start-up 126 53.9 63
FLA 16.6 8.2 8.3 the responsibility of the designer.
1-1/2
Start-up 116.2 57.4 58.1
FLA N/A 11.6 11.0
2
Start-up N/A 81.2 77

FM-076D-0-64J 8 of 18
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Air supply (continued)

 Air Pressure Maintenance Device (Style “B”)  Direct air, external compressor (Style “D”)
Used only for the sprinkler piping network of the preaction Mainly used with Preaction systems protecting refrigerated
system, when an external air supply is provided by others spaces and freezers, where a special dry external air supply
(tank mounted compressor, plant air or dry nitrogen unit is piped directly to the system riser inside the freezer
cylinders) and piped to the air inlet port of the unit. Air supply itself, as shown in NFPA-13. Air supply Style "D" provides
style "B" provides an Air Pressure Maintenance Device only an air supervisory and shut-off trim.
(APMD) trim, factory mounted in the TOTALPAC®3 cabinets.
This section replaced
Warning: When air supplies style "B" or "D" is selected, the
by Dehydrator option air supply should be provided and installed by the sprinkler
(when used)
contractor OUTSIDE of the TOTALPAC®3 cabinet. It is NOT
provided with the unit.
E4 E4
(plugged with SureFire or (plugged with SureFire or
non interlock preaction trim) non interlock preaction trim)

Contractor external Air Contractor external air


or Nitrogen connection or Nitrogen connection
TO PNEUMATIC
ACTUATOR
TO PNEUMATIC TO OPTIONAL ACCELERATOR
(plugged when 3 TO OPTIONAL ACCELERATOR
(plugged when not used) ACTUATOR (plugged when not used)
not used) 3
(plugged when
not used)
1 TO SPRINKLER RISER 1 TO SPRINKLER RISER

CONTRACTOR'S
CONTRACTOR'S HYDROSTATIC TEST PORT
HYDROSTATIC TEST PORT (system side)
FM-061H-0-121A
FM-061H-0-119B (system side)

9 of 18 FM-076D-0-64J
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Optional air supply equipments

 Dehydrator option
The Viking Dehydrator is a manually regenerated desiccant-type air dryer. The desiccant acts as a moisture indicator by changing
color, and is visible through the required bowl guard and transparent plastic bowl.
The Dehydrator directs the incoming air down through the silica gel desiccant. The silica gel absorbs the moisture without
physically changing. As the relative humidity increases, the silica gel begins to change color from dark blue to light pink, indicating
the desiccant must be replaced.

From air supply

To air Style "B" trim From air supply

To sprinkler riser Dehydrator bowl

Dehydrator bowl
Desiccant sight glass

FM-061H-0-124B-1 Desiccant sight glass

FM-061H-0-124B-2
To drain collector

Shown on Direct air compressor (Style “A”) Air Pressure Maintenance Device (Style “B”)

 Accelerator option
The Viking Model E-1 Accelerator is a quick-opening device.
The Viking Model E-1 Accelerator may be used without the
Anti-flood device to speed the action of a pneumatic release
system on a preaction system.

Upper chamber
pressure gauge

Accelerator

Isolation valve

To air line

Drain plug
FM-061H-0-125B

FM-076D-0-64J 10 of 18
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Details & field wiring diagrams

Cabinet with main components - Configuration with releasing control panel, shown with air style "A"

Optional Air Compressor Cable Entry


Isolating Switch

Junction box
Optional Air Compressor TBA & TBB
(behind Control Panel)
Release
Control Panel
Release Solenoid
Disconnect Switch

Riser Outlet to
Sprinklers Network

Riser Check Valve

Straight Through
Deluge Valve

Water Supply
Control Valve

Drain Outlet
(either side)

Water Inlet
(either side)

FM-061H-0-166B

11 of 18 FM-076D-0-64J
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Trim diagram

E4 FIELD CONNECTION TO
E9 SPRINKLER PIPING NETWORK
F5

To Air Supply System Trim 1


D2
B9

F4
B10
C1
F2
D3
F1
A1
F3
B8 B5 B11
C2

D1
B7
To Air Supply
System Trim B6

B13

B12 B3
FIELD CONNECTION B4
TO OPEN DRAIN
(on both sides)

B2

B1
FIELD CONNECTION
TO WATER SUPPLY CONTRACTOR'S
(on both sides) HYDROSTATIC TEST PORT
(water supply side)
T OTALPAC 3 Base
(shown without enclosure) FM-061H-0-107C

Trim Components:
A1 Deluge valve C1 Alarm pressure switch
B1 Priming valve C2 Connection to water motor gong (strainer supplied
B2 Strainer by contractor)
B3 1/16" Restricted orifice D1 Water supply control valve
B4 Spring loaded check valve D2 Riser check valve
B5 Alarm test valve D3 Main drain valve
B6 Flow test valve E4 Air supervisory pressure switch
B7 Drip check valve E9 Float-check assembly
B8 Drain check valve F1 N.C. Solenoid valve – 24Vdc
B9 Pressure operated relief valve (PORV) F2 N.O. Solenoid valve – 24Vdc
B10 Emergency release valve F3 Pneumatic actuator
B11 Priming pressure water gauge & valve F4 Pneumatic actuator pressure gauge
B12 Water supply pressure gauge & valve F5 5/64" Restricted orifice
B13 Clapper check valve

FM-076D-0-64J 12 of 18
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Field wiring diagrams, Double interlock Electric, Self-Contained:


WIRING OF INPUT POWER SOURCES
TBB OPTIONAL WIRING IN LEGEND
CLASS A / STYLE D
1 LINE

PULL STATIONS
CONTROL 120VAC, 60Hz, 165VA MAX SMOKE DETECTOR
2 NEUTRAL PANEL

DETECTION
220VAC, 50Hz, 185VA MAX
3 GROUND HEAT DETECTOR

MANUAL
ZONE 1

ZONE 4
4 GROUND
AIR 115VAC, 60Hz, 1.5HP MAX
5 NEUTRAL COMPRESSOR MANUAL RELEASE
208/230VAC, 60Hz, 2HP MAX
6 LINE
220/240VAC, 50Hz, 1.5KW MAX
WITH AIR OPTION "A" ONLY BELL OR HORN
Refer to Local Electrical Codes for wiring size.
DRY CONTACT
Branch circuit for air compressor shall not be the same
as the control panel power source.
END OF LINE RESISTOR

WIRING IN

TBA
CLASS B / STYLE Y

2
3
4
5
6
7
8
1
WIRING IN
CLASS B / STYLE B
SUPERVISORY
SILENCEABLE

SILENCEABLE
PULL STATIONS

NOTES:
Class A / Style D requires CA2Z modules.
DETECTION

ALARM

End-of-line devices are not required for


MANUAL

NAC1

NAC2
ZONE 1

ZONE 4

Class A / Style D wiring.


CHICAGO OPTION

5.1K 5.1K LOS ANGELES OPTION


5.1K 5.1K EOLR EOLR
EOLR EOLR OPTIONAL
24VDC RESETTABLE
SUPERVISORY

SUPERVISORY

SUPERVISORY
RS485
WATER FLOW

MAIN VALVE

SHUT-OFF
RESETTABLE
TROUBLE

24VDC NON
ALARM

VALVE
120

SHIELD
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC
C

C
TBA

TBC
10

11
12

13
14
15

16
17
18
19
20
21
22
23
24

10
11
2
3
4
5
6
7
8
9

2
3
4
5

6
7
8

9
1

CONTACTS RATED 3A, 30VDC RESISTIVE


CONTACTS RATED:
5A, 1/6HP, 125/250VAC
POWER LIMITED 4-WIRE DETECTION CIRCUIT 5.1K 0.5A, 250VDC 0.25A, 250VDC
EOLR
NOTE:
Contact provided for connection to
the building's central Fire Alarm Panel.
24VDC 24VDC
PAM-4
COM COM
Power Supervisory
Relay (EOL Relay) NOTES:
Control panel AC power source is supervised and non-power limited.
TBA

23
24

UL-Listed
2
1

All devices are shown in their normal supervisory state.


24VDC, 4-Wire Smoke Detectors
Use dry contacts with power limited circuits only.
FM-061H-0-209A

Power limited (supervised) initiating device circuits Power limited (supervised) notification appliance
Zones 1 (detection), 2 (detection) and 4 (manual circuits
release): Output circuits 1, 2 and 4:
Max. loop resistance: 100Ω Maximum operating voltage: 27Vdc (ripple: 0.3Vdc)
End of line: 5.1KΩ, 1/4W Maximum usable current per circuit: 1.0A
Leave ELR (provided) on all unused circuits. Total current available (all circuits): 2.5A
Refer to the VFR-400 release control panel manual for End of line: 5.1KΩ, 1/4W
device compatibility. Leave ELR (provided) on all unused circuits.
Polarity is reversed in supervisory condition.
Auxiliary power 24Vdc regulated source
Total current available: 0.2A Refer to the VFR-400 release control panel manual for
Resettable for 4 wires smoke detectors device compatibility

13 of 18 FM-076D-0-64J
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Optional electrical equipments

 Relay module ARM-44  Class A initiating device module CA2Z


The ARM-44 is an auxiliary relay module designed to The Model CA2Z Class A Module is designed to be used
operate with the Viking VFR-400 releasing control panel to with the Viking VFR-400 releasing control panel to convert
provide 4 independent form C relay outputs. The 4 output from two (Class B) initiating device circuits to two (Class A)
circuits each have a dedicated relay. Each relay is rated for circuits.
3 amps at 24 volts DC resistive load. The relay module The module is to be mounted in the upper right hand corner
mounts directly to the back of the cabinet and is connected of the panel. All the connections are wired back to the field
to the main board. All of the relay terminals are wired back wiring junction box.
to the field wiring junction box. A disable switch is available
for disabling the relays when the system is being tested or
serviced.

24Vdc RS-485

 Remote Annunciator RA-4410-RC


The RA-44410-RC remote annunciator is designed to
operate with the Viking VFR-400 releasing control panel.  CLASS A INDICATING APPLIANCE CIRCUIT
There are 34 LED's to indicate a change in panel status. MODULE
There is a buzzer on the annunciator that sounds for any The Model CAM Class A Module is designed to be used with
trouble or supervisory condition. The release control panel the Viking VFR-400 releasing control panel to convert a
supervises and communicates with the annunciator via single (Class B) indicating appliance circuit to a (Class A)
separate connections for the RS-485 communication and circuit (one module is required for each indicating appliance
the 24VDC power requirement of the RA-4410-RC. circuit). After installing the CAM, the indicating circuit should
Separate cables should be used for power and be activated to ensure proper operation and connections.
communication. Shielded cable MUST be used for the RS- The module is provided with double-sided foam tape and
485 communication line. should be mounted in the field wiring junction box so that the
terminals are accessible.
RA-4410-RC
ZONE 1 OUTPUT 1
ZONE 1 OUTPUT 1

ZONE 2 OUTPUT 2
ZONE 2 OUTPUT 2
ZONE 3 OUTPUT 3

ZONE 4 OUTPUT 4
ZONE 3 OUTPUT 3
AC POWER SUPERVISORY

POWER SUPERVISORY LAMP TEST


TROUBLE TROUBLE
COMMON ALM. SILENCE
SYSTEM
TROUBLE ALM. SILENCE
GROUND STEADY : DISCHARGED
ZONE 4 OUTPUT 4
FAULT FLASHING : PRE-DISCHARGE

FM-076D-0-64J 14 of 18
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Dimensions and weights


Figure 1 – Cabinet dimensions:

D E

P TBA, TBB & TBC Q

TBB TBA & TBC

OPTIONAL
SHUT-OFF VALVE

ØB
SCH.40 GROOVED OUTLET

SCH.40 GROOVED OUTLET


SPRINKLER RISER

SPRINKLER RISER
OPTIONAL FIRE DEP'T
CONNECTION OUTLET
(DRILLED ONLY WHEN
F ORDERED)

T
(W)
S
(V)

J
L
ØC
N N
DRAIN - SCH.40 GROOVED OUTLET U

ØA
M WATER INLET M
SCH.40 GROOVED OUTLET
K

FM-061H-0-278A
R

Table 1 - Cabinet dimensions - dimensions are in inches (mm)


Unit
size
A B C D E F G H J K L M N P Q R S T U V W
1½" 2" 1½" 2" 23" 25" 77" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 8" 11½" 27" 37½" 41½" 34¼" 43½" 47"
(40) (51) (38) (51) (584) (635) (1956) (102) (222) (292) (349) (95) (70) (70) (203) (292) (686) (953) (1054) (870) (1105) (1194)
2" 2" 2" 2" 23" 25" 77" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 8" 11½" 27" 38" 42" 34¾" 44½" 48½"
(50) (51) (51) (51) (584) (635) (1956) (102) (222) (292) (349) (95) (70) (70) (203) (292) (686) (965) (1067) (883) (1130) (1232)
3" 4" 3" 2" 35¾" 25" 77" 4" 10" 11½" 13¾" 3¾" 2¾" 2¾" 11¾" 11½" 39¾" 44" 47¾" 37" 51" 54¾"
(80) (102) (76) (51) (908) (635) (1956) (102) (254) (292) (349) (95) (70) (70) (298) (292) (1010) (1118) (1213) (940) (1295) (1391)
4" 4" 4" 2" 35¾" 25" 77" 4" 10" 11½" 13¾" 3¾" 2½" 2½" 12" 11½" 39¾" 48½" 53" 42" 56½" 61"
(100) (102) (102) (51) (908) (635) (1956) (102) (254) (292) (349) (95) (64) (64) (305) (292) (1010) (1232) (1346) (1499) (1435) (1549)
6" 6" 6" 2" 46" 25" 77" 4" 11" 11½" 13¾" 3¾" 5¼" 5¼" 17¾" 11½" 50" 59¼" 65¼" 51½" 70¼" 76¼"
(150) (152) (152) (51) (1168) (635) (1956) (102) (279) (292) (349) (95) (133) (133) (451) (292) (1270) (1505) (1657) (1308) (1784) (1937)
8" 8" 8" 2" 54" 31" 81" 4" 12" 13¼" 17" 3¾" 9" 6¾" 27" 13¼" 58" 70" 75¼"
N/A N/A N/A
(200) (203) (203) (51) (1372) (787) (2057) (102) (305) (337) (432) (95) (229) (171) (686) (337) (1473) (1778) (1911)

Notes:
1. Dimensions are nominal and may vary ±¼" (±5mm).
2. Dimensions U, V & W are for optional fire department connection.

15 of 18 FM-076D-0-64J
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Figure 2 - Floor anchoring dimensions Table 2 - Floor anchoring


dimensions
A A
Unit size A B
5" (51mm) 5" (51mm) 1½ 25" 15"
(40mm) (635mm) (380mm)
2" 25" 15"
TOP VIEW TOP VIEW (50mm) (635mm) (380mm)
B B
3" 37¾" 15"
Ø ¾" (19mm) TYP. Ø ¾" (19mm) TYP. (80mm) (959mm) (380mm)
4" 37¾" 15"
(100mm) (959mm) (380mm)
6" 48" 15"
(1220mm) (380mm)
FRONT FRONT
1" (25mm) 1" (25mm)
FM-061H-0-128A-2
(150mm)
8" 56" 21"
(200mm) (1422mm) (530mm)

Figure 3 - Cabinet & doors clearance detail Table 3 - Cabinet clearance dimensions
Unit size A B C
1½ 24" 12" 48"
(610mm) (305mm) (1219mm)
B min.
(40mm)
2" 24" 12" 48"
(50mm) (610mm) (305mm) (1219mm)
3" 24" 12" 60"
(80mm) (610mm) (305mm) (1524mm)
T OTALPAC 3 TYPICAL
MECHANICAL C min. 4" 24" 12" 60"
UNIT
ROOM (100mm) (610mm) (305mm) (1524mm)
6" 24" 12" 70"
(150mm) (610mm) (305mm) (1778mm)
8" 32" 12" 78"
(200mm) (813mm) (305mm) (1981mm)
B min.
Note : Minimum dimensions are according to
door clearance and external piping
requirements.
A min.

FM-061H-0-275A
Table 4 - System weight in cabinet

Figure 4 - Knockouts details System size Weight 1


1½" (40mm) 450 lb (204 kg)
Top of Cabinet
2" (50mm) 455 lb (206 kg)

9" High voltage 3" (80mm) 655 lb (297 kg)


(230mm)
Low voltage 4" (100mm) 730 lb (331 kg)
3"
(75mm) 6" (150mm) 1080 lb (490 kg)
8" (200mm) 1445 lb (655 kg)
2½" Typ.
8½" 2½" (65mm)
(215mm) (65mm)
Combined ½ & ¾ knockouts

FM-061H-0-68B-12

FM-076D-0-64J 16 of 18
TotalPac®3
Double interlock SUREFIRE Preaction
Self-contained system

Table 5 - Manifold dimensions


Figure 5 - Open drain details for single unit
Unit size A B C
1½ 8¾" 13¾" 2"
(40mm) (222mm) (350mm) (50mm)
T OTALP AC 3 Unit
Shown Without 2" 8¾" 13¾" 2"
Front Doors (50mm) (222mm) (350mm) (50mm)
Unit Drain Pipe
(dia. = C) 3" 10" 13¾" 2"
(80mm) (255mm) (350mm) (50mm)
Air Gap
4" 10" 13¾" 2"
Water Supply Pipe (100mm) (255mm) (350mm) (50mm)
4'' (100mm) 6" 11" 13¾" 2"
min.
B (150mm) (280mm) (350mm) (50mm)

A
8" 12" 17½" 2"
(200mm) (305mm) (445mm) (50mm)

Drain Pipe (pipe diameter


per drain flow calculation)

Single Unit Detail FM-061H-0-139A

Figure 6 - Open drain details for multiple units


(refer to dimensions in table 5)
12''
(305mm)
min.

T OTALPAC 3 Unit T OTALPAC 3 Unit


Shown Without Shown Without
Front Doors Front Doors Unit Drain Pipe
(dia. = C)
DO NOT MANIFOLD !
Water Supply Pipe
(Can Be Manifolded)
Typical Air Gap

4'' (100mm) min.


B

Drain Collector running


between wall and units
(pipe diameter per
Multiple Units Detail drain flow calculations)

FM-061H-0-140A

Notes:
1. Water supply and drain pipes can be connected on either sides of cabinet.
2. All pipes and fittings should meet applicable codes.
3. Actual drain collector diameter shall be determined with detailed hydraulic calculations and is the responsibility of the system designer.
.

17 of 18 FM-076D-0-64J
1935, Lionel-Bertrand Blvd.
Boisbriand QC Canada J7H 1N8
Tel.: 450-437-3473 • Fax: 450-437-1930
Toll Free: 866-347-3353
Email: info@fireflex.com • Web: www.fireflex.com

Copyright © 2019 FireFlex Systems Inc.


All Rights Reserved
While all reasonable efforts have been taken in the preparation of this datasheet to assure its accuracy, FireFlex Systems Inc
assumes no liability resulting from any errors or omissions in this datasheet, or from the use of the information contained herein.
FireFlex Systems Inc. reserves the right to make changes to this datasheet herewith at any time, without prior notification.
TOTALPAC® is a registered trademark of FireFlex Systems Inc.

FM-076D-0-64J 18 of 18