You are on page 1of 3

Batteries Division

ZVEI information leaflet No. 14


May 2020

Ventilation of battery charging rooms for


lead traction batteries

1. Foreword current of 1 ampere (reference The air volume flow Q required


In order to avoid explosion temperature 25°C). for this is calculated according to
hazards sufficient ventilation of DIN EN 62485-3 for the
charging rooms for traction The ventilation of battery reference temperature of 25 °C,
batteries based on lead battery charging rooms must safely as follows:
technology is mandatory. ensure that the hydrogen
concentration does not exceed
This ZVEI information leaflet is a the lower explosion limit of 4% Q = 0.055m³/Ah n  Igas
guide to the application of the by volume. Battery charging
Q air volume flow in m3/h
DIN EN 62485-3 Safety rooms should therefore be
requirements for secondary designed so that natural 0.055 m3/Ah
batteries and battery ventilation is sufficient. If this is combines gas evolution rate,
installations – Part 3: Traction not ensured under all operating the necessary dilution factor
batteries. It contains example conditions appropriate technical of hydrogen and a general
calculations and notes for ventilation must be used. Details safety factor
application. on natural and technical
n number of cells (e.g. 40 for
ventilation are described in
2. General an 80 volt or 12 for an 24 volt
chapter 4.
During the charging of lead battery)
batteries an explosive gas Safety note: Even though
Igas hydrogen-generating electric
mixture escapes from the battery sufficient ventilation is ensured,
current in A
cells through the plug openings. the dilution of hydrogen cannot
This gas mixture results from always be guaranteed in the Note: Due to the safety factor
electrolysis of water, the main near field of the battery. this formula can also be used for
compound of the electrolyte, and Therefore according to the entire permissible operating
consists of hydrogen and DIN EN 62485-3 the safety temperature range of a battery.
oxygen (volume ratio 2:1 = distance of 0.5 meters air gap The battery related Igas values
oxyhydrogen gas. (thread dimension) must be shall be obtained from the
maintained from a possible charger manufacturer. Particular
The evolution of gasses during ignition source, starting from a characteristics, e.g. pulse-,
charging rises with the battery's cell opening (plug or valve). multi-voltage- or fast-charging
state of charge. In the final Within this safety distance no functions, must be taken into
charging phase of the battery open flames, sparks, arcs or account.
almost the entire charging glowing objects may occur
current leads to the generation (maximum surface temperature If Igas is not known or cannot get
of oxyhydrogen gas. 300°C). to know, at least 40% of the
maximum charging current (see
Towards the end of the charging 3. Dimensioning of the charger's name plate) must be
process, the electrolysis of water ventilation used for Igas.
generates 0.450 liter hydrogen Sufficient air exchange is
and 0.225 liter oxygen within necessary to dilute the In case of several batteries are
one hour and a final charging potentially explosive gas. charged simultaneously in the
same room, the required air flow

This leaflet was prepared by the Working Group Industrial Batteries of the
ZVEI – German Electrical and Electronic Manufacturers' Association, Batteries Division
rate must be calculated for each The total required air volume Example calculation required
battery. For safety reasons the flow for all batteries is calculated cross-section of the air inlet
calculation must be based on from the sum of the individual air and outlet openings:
the assumption that all batteries volume flows of the PzS and
under charge generate hydrogen PzV batteries. Using the exemplary air flow rate
at maximum gassing rate. If this calculated in chapter 3 the
cannot be excluded by technical Qges = QPzS + QPzV required opening cross-section
measures the air volume flow air in- and outlet are to be
= 462.0 m³/h + 28.8 m³/h determined as follows:
required for a charging station is
therefore calculated from the = 490.8 m³/h A = 28 cm²h/m3 x Qges
sum of the air volume flow of all 4. Design of charging rooms
batteries being charged in the = 28 cm²h/m3 x 490.8 m³/h
In order to ensure adequate
same room. ventilation there are basically = 13,742 cm²
Example calculation for air two technical solutions:
In this example this corresponds
volume flow: to a square opening with an
Scenario: Mixed operation of edge length of approx. 117cm.
Natural ventilation
PzS and PzV batteries, charged Forced ventilation
with the allocated chargers. The basic requirements for
natural ventilation are a free If the conditions for natural
room volume (total volume of the ventilation are not met forced
Ten PzS batteries 80 V 420Ah room minus the volume of ventilation must be installed to
C5, charging characteristic objects in the room) of 2.5 times ensure the necessary air flow
W0Wa with an Igas (corresponds the hourly air volume flow Q Qges.
to the final charging current) of [m³/h] to be renewed and at
least an air speed of 0.1 m/s in Batteries shall only be charged if
21A (exemplary value stated by the forced ventilation is effective.
a charger manufacturer). all inlets and outlets.
The corresponding air in- and The function and effectiveness
outlets shall each have at least a of the forced ventilation must be
Calculation of the air volume cross-section area which is to be demonstrated at commissioning
flow for one PzS battery: calculating using the following and at regular intervals.

QPzS = 0.055 m³/Ah x 40 x 21A formula: Important boundary condition


for natural and forced
= 46.2 m³/h A = 28cm²h/m³  Q ventilation
A Cross-section for air in- and The air supply must be free of
outlet [cm²] gases harmful to lead batteries,
Calculation of the air volume
flow for the ten PzS batteries: 28 cm² h/m³ such as chlorine and ammonia.
Necessary factor for Ducts and system components
QPzS = 10 x 46.2 m³/h conversion of units of the ventilation system located
= 462.0 m³/h Q Air volume flow [m³/h] in the exhaust air flow must be
designed to be acid resistant.

The air flow must ensure a Both, the natural and forced
Six PzV batteries 48 V 300Ah ventilation must be designed in
C5, charging characteristic IUIa continuous aeration of the entire
battery charging room / area e.g. such a way that the exhaust air
with an Igas (corresponds to the is emitted into the open air.
final charging current) of 3.6A the inlets should be located near
the floor and the airflow should When positioning the exhaust air
(exemplary value stated by a outlet the proximity to air intake
charger manufacturer). be directed over the batteries
and escape at outlets high as openings of air condition system
possible. This ensures optimum must be avoided. The exhaust
cross ventilation. air must not be led into active
Calculation of the air volume chimneys
flow for one PzV battery: If the air in- and outlet openings
QPzV = 0.055 m³/Ah x 24 x 3.6A are positioned at the same wall
the minimum distance between
= 4.8 m³/h the openings must be 2 meters.
Doors and windows are only
considered to be appropriate air
Calculation of the air volume
inlet and outlet opening if it is
flow for the six PzV batteries:
ensured that are constantly open
QPzV = 6 x 4.8 m³/h during the charging process and
the necessary cross-section
= 28.8 m³/h area is provided in this state.

2/3
Published by:
ZVEI – Zentralverband Elektrotechnik- und Elektronikindustrie e. V.
Batteries Division
Lyoner Strasse 9
60528 Frankfurt

Phone: +49 69 6302-283


Fax: +49 69 6302-362
E-mail: batterien@zvei.org
www.zvei.org

© ZVEI 2020
Despite the greatest care being taken, no liability can be accepted
for ensuring that this information is correct, complete and up to date.

3/3

You might also like