Professional Documents
Culture Documents
This leaflet was prepared by the Working Group Industrial Batteries of the
ZVEI – German Electrical and Electronic Manufacturers' Association, Batteries Division
rate must be calculated for each The total required air volume Example calculation required
battery. For safety reasons the flow for all batteries is calculated cross-section of the air inlet
calculation must be based on from the sum of the individual air and outlet openings:
the assumption that all batteries volume flows of the PzS and
under charge generate hydrogen PzV batteries. Using the exemplary air flow rate
at maximum gassing rate. If this calculated in chapter 3 the
cannot be excluded by technical Qges = QPzS + QPzV required opening cross-section
measures the air volume flow air in- and outlet are to be
= 462.0 m³/h + 28.8 m³/h determined as follows:
required for a charging station is
therefore calculated from the = 490.8 m³/h A = 28 cm²h/m3 x Qges
sum of the air volume flow of all 4. Design of charging rooms
batteries being charged in the = 28 cm²h/m3 x 490.8 m³/h
In order to ensure adequate
same room. ventilation there are basically = 13,742 cm²
Example calculation for air two technical solutions:
In this example this corresponds
volume flow: to a square opening with an
Scenario: Mixed operation of edge length of approx. 117cm.
Natural ventilation
PzS and PzV batteries, charged Forced ventilation
with the allocated chargers. The basic requirements for
natural ventilation are a free If the conditions for natural
room volume (total volume of the ventilation are not met forced
Ten PzS batteries 80 V 420Ah room minus the volume of ventilation must be installed to
C5, charging characteristic objects in the room) of 2.5 times ensure the necessary air flow
W0Wa with an Igas (corresponds the hourly air volume flow Q Qges.
to the final charging current) of [m³/h] to be renewed and at
least an air speed of 0.1 m/s in Batteries shall only be charged if
21A (exemplary value stated by the forced ventilation is effective.
a charger manufacturer). all inlets and outlets.
The corresponding air in- and The function and effectiveness
outlets shall each have at least a of the forced ventilation must be
Calculation of the air volume cross-section area which is to be demonstrated at commissioning
flow for one PzS battery: calculating using the following and at regular intervals.
The air flow must ensure a Both, the natural and forced
Six PzV batteries 48 V 300Ah ventilation must be designed in
C5, charging characteristic IUIa continuous aeration of the entire
battery charging room / area e.g. such a way that the exhaust air
with an Igas (corresponds to the is emitted into the open air.
final charging current) of 3.6A the inlets should be located near
the floor and the airflow should When positioning the exhaust air
(exemplary value stated by a outlet the proximity to air intake
charger manufacturer). be directed over the batteries
and escape at outlets high as openings of air condition system
possible. This ensures optimum must be avoided. The exhaust
cross ventilation. air must not be led into active
Calculation of the air volume chimneys
flow for one PzV battery: If the air in- and outlet openings
QPzV = 0.055 m³/Ah x 24 x 3.6A are positioned at the same wall
the minimum distance between
= 4.8 m³/h the openings must be 2 meters.
Doors and windows are only
considered to be appropriate air
Calculation of the air volume
inlet and outlet opening if it is
flow for the six PzV batteries:
ensured that are constantly open
QPzV = 6 x 4.8 m³/h during the charging process and
the necessary cross-section
= 28.8 m³/h area is provided in this state.
2/3
Published by:
ZVEI – Zentralverband Elektrotechnik- und Elektronikindustrie e. V.
Batteries Division
Lyoner Strasse 9
60528 Frankfurt
© ZVEI 2020
Despite the greatest care being taken, no liability can be accepted
for ensuring that this information is correct, complete and up to date.
3/3