You are on page 1of 3

Totally Integrated

Automation Portal

Project6 / PLC_1 [CPU 1214C DC/DC/DC] / Program blocks


Main [OB1]
Main Properties
General
Name Main Number 1 Type OB Language LAD
Numbering Automatic
Information
Title "Main Program Sweep (Cy‐ Author Comment Family
cle)"
Version 0.1 User-defined ID

Main
Name Data type Default value Comment
Input
Initial_Call Bool Initial call of this OB
Remanence Bool =True, if remanent data are available
Temp
Constant

Network 1:

%I0.0 %Q0.0
"Start" "Motor1"
S

%M0.0 %M2.6 %M0.4


"M_Start" "MANUAL" "Auto"

%M2.6 %M2.7 %M0.4


"MANUAL" "MAN_Motor1" "Auto"

Network 2:

%Q0.0 %I0.3 ADD


"Motor1" "SS1" Auto (Int)
P EN ENO
%M0.5 %MW100 %MW100
"Pre_I_SS1" "DemSP1" "DemSP1"
IN1 OUT
1 IN2
%M0.4 %M0.3
"Auto" "M_SS1"
P
%M0.6
"Pre_M_SS1"

Network 3:

%DB7
"IEC_Timer_0_
DB_6"

%Q0.0 TON %Q0.0


"Motor1" Time "Motor1"
IN Q R
T#5s PT ET T#0ms
%DB1
"IEC_Timer_0_DB"
%M0.4 TON %M2.3
"Auto" Time "Motor2"
IN Q S
T#15s PT ET T#0ms

%M2.6 %M3.0
"MANUAL" "MAN_Motor2"

Network 4:
Totally Integrated
Automation Portal

%M2.3 %I0.4 ADD


"Motor2" "SS2" Auto (Int)
P EN ENO
%M1.7 %MW108 %MW108
"Pre_I_SS2" "DemSP2" "DemSP2"
IN1 OUT
1 IN2
%M1.5 %M0.4
"M_SS2" "Auto"
P
%M2.0
"Pre_M_SS2"

Network 5:

%DB8
"IEC_Timer_0_
DB_7"

%M2.3 TON %M2.3


"Motor2" Time "Motor2"
IN Q R
T#5s PT ET T#0ms

%DB2
"IEC_Timer_0_
DB_1"

%M0.4 TON %M2.4


"Auto" Time "Motor3"
IN Q S
T#15s PT ET T#0ms

%M2.6 %M3.1
"MANUAL" "MAN_Motor3"

Network 6:

%M2.4 %I0.5 ADD


"Motor3" "SS3" Auto (Int)
P EN ENO
%M2.1 %MW110 %MW110
"Pre_I_SS3" "DemSP3" "DemSP3"
IN1 OUT
1 IN2
%M1.6 %M0.4
"M_SS3" "Auto"
P
%M2.2
"Pre_M_SS3"

Network 7:

%DB9
"IEC_Timer_0_
DB_8"

%M2.4 TON %M2.4


"Motor3" Time "Motor3"
IN Q R
T#5s PT ET T#0ms

%DB3
"IEC_Timer_0_
DB_2"

%M0.4 TON %Q0.0


"Auto" Time "Motor1"
IN Q S
T#15s PT ET T#0ms

Network 8:

%FC1
"Block_1"
EN ENO

Network 9:
Totally Integrated
Automation Portal

%I0.1 %Q0.0
"Stop" "Motor1"
R

%M0.1 %M0.4 MOVE


"M_Stop" "Auto" EN ENO
0 IN %MW100
OUT1 "DemSP1"

%I0.1 %M2.3
"Stop" "Motor2"
R

%M0.1 %M0.4 MOVE


"M_Stop" "Auto" EN ENO
0 IN %MW108
OUT1 "DemSP2"

%I0.1 %M2.4
"Stop" "Motor3"
R

%M0.1 %M0.4 MOVE


"M_Stop" "Auto" EN ENO
0 IN %MW110
OUT1 "DemSP3"

Network 10:

%I0.1 %Q0.0
"Stop" "Motor1"
R

%M0.1 %M0.4 %M2.3


"M_Stop" "Auto" "Motor2"
R

%M2.4
"Motor3"
R

%M0.1
"M_Stop"
RESET_BF
24