IM 01C25A01-01E
Contents
1. Introduction
1.1 For Safe Use of Product...............................................3
1.2 Warranty.......................................................................5
2. Handling Cautions
2.1 Model and Specifications Check..................................7
2.2 Selecting the Installation Location...............................7
2.3 Pressure Connection...................................................7
2.4 Installation of an Explosion-Protected Instrument.......7
2.5 EMC Conformity Standards...................................... 31
2.6 Pressure Equipment Directive (PED)....................... 31
2.7 EU RoHS Directive.................................................... 32
2.8 Safety Requirement Standards................................. 33
3. Installation
3.1 Mounting................................................................... 34
3.2 Mounting the Diaphragm Seals.......................................34
3.3 Diaphragm Seals Installation Consideration............. 35
3.4 Mounting the Flushing Connection Ring................... 36
3.5 Affixing the Teflon Film.............................................. 37
3.6 Rotating Transmitter Section..................................... 38
3.7 Changing the Direction of Integral Indicator............. 38
4. Installing Impulse Piping
4.1 Impulse Piping Installation Precautions.................... 39
4.2 Impulse Piping Connection Examples...................... 42
4.3 Process Piping Installation Precautions (EJ115).42
5. Wiring
5.1 Wiring Precautions.................................................... 44
5.2 Connections of External Wiring to Terminal Box....... 44
5.3 Wiring........................................................................ 47
5.4 RTD Cable Connection (EJX910A/EJX930A).......... 49
5.5 Grounding................................................................. 51
5.6 Power Supply Voltage and Load Resistance............ 51
6. Operation
6.1 Preparation for Starting Operation............................ 52
6.2 Zero Point Adjustment............................................... 52
6.3 Local Parameter Setting........................................... 53
7. Errors and Countermeasures
IM 01C25A01-01E
14th Edition
<1. Introduction> 1
1. Introduction
This installation manual provides the basic guidelines Table 1.1 PDF Manual List and Applicable Style Code
for installation and wiring procedures of the DPharp EJX
[EJX series Hardware Manual]
series and EJA-E series transmitters with BRAIN and
HART protocols and is composed of the information Models Document No. Style
extracted from the product users’ manuals as listed in EJX110A S3
EJX120A S1
Table 1.1. It does not provide the information including IM 01C25B01-01E
EJX130A, EJX310A, EJX430A
wiring procedures of the transmitters with FOUNDATION S2
and EJX440A
Fieldbus, Profibus and Modbus protocols, product
EJX210A IM 01C25C01-01E S2
specific functional specifications and explanations, EJX510A and EJX530A S2
operation, maintenance and trouble-shooting. IM 01C25F01-01E
EJX610A and EJX630A S1
For EJXC40A Digital Remote Sensor, as this Installation EJX118A and EJX438A IM 01C25H01-01E S2
Manual does not cover the product, please refer to the EJX115A IM 01C25K01-01E S1
dedicated manual for EJXC40A. EJX910A S2
IM 01C25R01-01E
EJX930A S1
EJXC80A and EJXC50A IM 01C25W01-01EN —
WARNING EJXC40A IM 01C25W05-01EN —
To ensure correct and safe use of the instrument, [EJX series Communication Manual]
obtain the manuals and General Specifications sheets Models Document No. Style
applicable to designated models and specifications DPharp HART 5/HART 7
IM 01C25T01-06EN —
as listed Table 1.1 and 1.2, read them thoroughly and Communication Type
fully understand how to operate the instrument before DPharp FOUNDATION Fieldbus
IM 01C25T02-01E —
operating it. Communication Type
DPharp BRAIN Communication
IM 01C25T03-01E —
Type
Users’ manual for each product consists of a hardware DPharp PROFIBUS PA
IM 01C25T04-01EN —
manual describing installation, wiring, operation, and Communication Type
maintenance and a communication manual describing EJX910A and EJX930A HART
IM 01C25R02-01E —
information specific to each communication protocol type, Communication Type
including safety manual for safety instrumented system. EJX910A and EJX930A
IM 01C25R03-01E —
Fieldbus Communication Type
The specifications of each product including external
EJX910A and EJX930A Modbus
dimensions and detailed model and suffx codes are IM 01C25R05-01E —
Communication Type
described in General Specifications sheet(GS.)
[EJA-E series Hardware Manual]
These manuals and GSs can be downloaded from the
website of Yokogawa, and printed manuals can also be Models Document No. Style
purchased from the Yokogawa representatives. EJA110E, EJA120E
EJA130E, EJA310E, EJA430E IM 01C25B01-01E S1,S2
Website address: and EJA440E
https://www.yokogawa.com/solutions/products-platforms/field-instruments/ EJA210E IM 01C25C01-01E S1,S2
EJA510E and EJA530E IM 01C25F01-01E S1,S2
EJA118E and EJA438E IM 01C25H01-01E S1,S2
EJA115E IM 01C25K01-01E S1,S2
EJAC80E and EJAC50E IM 01C25W01-01EN —
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may
also be used to alert against unsafe practices.
IM 01C25A01-01E
<1. Introduction> 3
(b) Wiring
IMPORTANT
Indicates that operating the hardware or software in WARNING
this manner may damage it or lead to system failure.
• The instrument must be installed by an expert
engineer or a skilled personnel. The procedures
described about WIRING are not permitted for
NOTE operators.
• Please confirm that voltages between the power
Draws attention to information essential for
supply and the instrument before connecting the
understanding the operation and features.
power cables and that the cables are not powered
before connecting.
Direct current
Caution
WARNING
This symbol indicates that the operator must
refer to an explanation in the user’s manual • Wait 5 min. after power is turned off, before
in order to avoid the risk of injury or death of opening the covers.
personnel or damage to the instrument. • Do not open the cover in wet weather or humid
environment. If the cover is opened, stated
1.1 For Safe Use of Product enclosure protection is not applicable.
IM 01C25A01-01E
<1. Introduction> 4
(f) Modification
WARNING
• Yokogawa will not be liable for malfunctions or
damage resulting from any modification made to
this instrument by the customer.
产品中有害物质或元素的名称及含量
有害物质
型号 部件名称 铅 汞 镉 六价铬 多溴联苯 多溴二苯醚
(Pb) (Hg) (Cd) (Cr(VI)) (PBB) (PBDE)
壳体 × ○ ○ ○ ○ ○
EJX/EJA-E 膜盒组件 × ○ ○ ○ ○ ○
Series
差压/压力变送器 基板组件 × ○ ○ ○ ○ ○
电源连接线 × ○ ○ ○ ○ ○
○:表示该部件的所有均质材料中的有害物质的含量均在 GB/T26572 标准中所规定的限量以下。
环保使用期限:
注)该年数为“环保使用期限”,并非产品的质量保证期。
IM 01C25A01-01E
<1. Introduction> 5
1.2 Warranty
• The warranty shall cover the period noted on the
quotation presented to the purchaser at the time of
purchase. Problems occurred during the warranty
period shall basically be repaired free of charge.
• In case of problems, the customer should contact the
Yokogawa representative from which the instrument
was purchased, or the nearest Yokogawa office.
• If a problem arises with this instrument, please inform
us of the nature of the problem and the circumstances
under which it developed, including the model
specification and serial number. Any diagrams,
data and other information you can include in your
communication will also be helpful.
• Responsible party for repair cost for the problems
shall be determined by Yokogawa based on our
investigation.
• The Purchaser shall bear the responsibility for
repair costs, even during the warranty period, if the
malfunction is due to:
- Improper and/or inadequate maintenance by the
purchaser.
- Failure or damage due to improper handling, use
or storage which is out of design conditions.
- Use of the product in question in a location
not conforming to the standards specified by
Yokogawa, or due to improper maintenance of the
installation location.
- Failure or damage due to modification or repair
by any party except Yokogawa or an approved
representative of Yokogawa.
- Malfunction or damage from improper relocation of
the product in question after delivery.
- Reason of force majeure such as fires,
earthquakes, storms/floods, thunder/lightening,
or other natural disasters, or disturbances, riots,
warfare, or radioactive contamination.
Trademarks:
• ‘DPharp’, ‘EJX’, ‘EJA’, ‘FieldMate’ and ‘BRAIN
TERMINAL’ are registered trademarks of Yokogawa
Electric Corporation. Company names and product
names used in this material are registered trademarks
or trademarks of their respective owners.
• In this manual, trademarks or registered trademarks
are not marked with ™ or ®.
IM 01C25A01-01E
<2. Handling Cautions> 6
2. Handling Cautions
When the transmitter is delivered, visually check them 1
to make sure that no damage occurred during shipment. B
2
1 D
Also check that all transmitter mounting hardware shown 3
EJX910A 2 G
in Figure 2.1 is included. If the transmitter was ordered - - J 4
EJX930A 3
B
without the mounting bracket or without the process 4 K
C
connector, the transmitter mounting hardware is not M
D
included. 1
2
Table 2.1 Applicable Model Code for Mounting EJ210 - -
3
Hardware 4
Applicable EJ510
Suffix code Part name Qty EJ530 F
model - -
EJX610A L
EJ110 Process connector bolt 4
EJX630A
EJ120 Process Process connector 2
EJ130 connections EJ118 B
EJX910A 1,2,3 and 4 Process connector - -
2 EJ438 J
EJX930A gasket
IM 01C25A01-01E
<2. Handling Cautions> 7
2.1 Model and Specifications 2.3 Pressure Connection
Check
The model name and specifications are indicated on the WARNING
name plate attached to the case.
• Never loosen the process connector bolts when an
instrument is installed in a process. The device is
under pressure, and a loss of seal can result in a
sudden and uncontrolled release of process fluid.
• When draining toxic process fluids that have
condensed inside the pressure detector, take
appropriate steps to prevent the contact of such
fluids with the skin or eyes and the inhalation of
vapors from these fluids.
IM 01C25A01-01E
<2. Handling Cautions> 8
Note 2. Installation
WARNING Installation should be in accordance with Control
Drawing IFM022-A12.
The range setting switch must not be used in a Note 3. Specific conditions of use:
hazardous area. Precautions shall be taken to minimize the risk from
electrostatic discharge of painted parts.
When the enclosure of the Pressure Transmitters is
IMPORTANT made of aluminum alloy, if it is mounted in Zone 0, it
shall be installed such that, even in the event of rare
For combined approval types incidents, an ignition source due to impact and/or
Once a device of multiple approval type is installed, friction sparks is excluded.
it should not be re-installed using any other approval
Note 4. Maintenance and Repair
types. Apply a permanent mark in the check box of
Only personnel authorized by Yokogawa Electric
the selected approval type on the certification label on
Corporation can repair the equipment.
the transmitter to distinguish it from unused approval
types.
Model: EJX Series Date: October 22, 2003
Control Drawing
2.4.1 FM Approval
Suppl
y
Note 1. EJX/EJA-E Series pressure transmitters with
optional code /FS1 are applicable for use in
hazardous locations.
• Applicable Standard:
FM 3600:2011 Class I, II, Division 2
Groups A, B, C, D, F, G
Class III, Division 1
FM 3610:2010 Class I, Zone 2, Group IIC
General
Purpose
FM 3611:2004 EJX Series
Pressure T ransmitter Equipment
FM 3810:2005 Suppl
y
ANSI/ISA-60079-0-2009
ANSI/ISA-60079-11-2009 (Refer to Note 4)
ANSI/ISA-61010-1-2004
NEMA 250:1991
• Rating
Intrinsically Safe for
Class I, II, III Division 1,
Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4 Rev.2: July 16, 2019 Doc. No.: IFM022-A12 P.1
IM 01C25A01-01E
<2. Handling Cautions> 9
Model: EJX Series Date: October 22, 2003 • Ambient temperature:
Specific conditions of use:
- Precautions shall be taken to minimize the risk from electrostatic discharge of
–55 to 60 °C (Certificate date issued: February,
-
painted parts.
When the enclosure of the Pressure Transmitters is made of aluminum alloy, if it is
2020 or later)
mounted in Zone 0, it must be installed such that, even in the event of rare
incidents, an ignition source due to impact and/or friction sparks is excluded. –40 to 60 °C (Certificate date issued: October,
Entity Parameters [Groups: A, B, C, D, E, F and G] 2019)
Vmax: 30 V
Imax: 200 mA
Pmax: 1 W
• Enclosure: Type 4X
Ci: 6 nF
Li: 0 µH • Electrical Connection:
Entity Parameters [Groups: C, D, E, F and G]
Vmax: 30 V 1/2 NPT female, M20 female
Imax: 225 mA
Pmax: 1 W
Ci: 6 nF
Li: 0 µH
Note 2. Installation
Notes:
Installation should be in accordance with Control
1. Installation must be in accordance with the National Electric Code (NFPA70),
ANSI/ISA-RP12.06.01, and relevant local codes. Drawing IFM024-A12.
2. The Associated Apparatus must be FM -approved.
3. The following conditions must be satisfied.
Voc (or Uo) ≤ Vmax Note 3. Specific conditions of use:
Isc (or Io) ≤ Imax
Po ≤ Pmax
Ca (or Co) ≥ Ci + Ccable
Precautions shall be taken to minimize the risk from
La (or Lo) ≥ Li + Lcable
4. In case Nonincendive Field Wiring Concept is used for the interconnection, electrostatic discharge of painted parts.
FM-approved Associated Nonincendive Field Wiring Apparatus, which meets the
above conditions, must be used as the General Purpose Equipment. When the enclosure of the Pressure Transmitters is
5. The General Purpose Equipment connected to the Associated Apparatus must not
use or generate a voltage more than Um of the Associated Apparatus.
6. The control drawing of the Associated Apparatus must be followe d when installing
made of aluminum alloy, if it is mounted in Zone 0, it
the equipment.
7. Dust-tight conduit seals must be used when installed in Class II or Class III
shall be installed such that, even in the event of rare
environments.
8. WARNING –ELECTROSTATIC CHARGE MAY CAUSE AN EXPLOSION HAZARD. incidents, an ignition source due to impact and/or
AVOID ANY ACTIONS THAT CAUSE THE GENERATION OF ELECTROSTATIC
CHARGE, SUCH AS RUBBING WITH A DRY CLOTH ON COATING FACE OF THE friction sparks is excluded.
PRODUCT.
9. WARNING – SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC
SAFETY AND SUITABILITY FOR HAZARDOUS LOCATION Note 4. Maintenance and Repair
Only personnel authorized by Yokogawa Electric
Corporation can repair the equipment.
Rev.3: July 16, 2019 Doc. No.: IFM022-A12 P.2 Model: EJX-F Series Date: January 27, 2005
FM 3610 Groups A, B, C, D, E, F, G
Class I, Zone 0, Group IIC
FM 3611
FM 3810
ANSI/ISA-60079-0-2009
ANSI/ISA-60079-11-2009
ANSI/ISA-60079-27-2006
ANSI/UL 121201 Associated Apparatus
(Safety Barrier)
ANSI/ISA-61010-1
NEMA 250
• Rating
Intrinsically Safe with Entity/FISCO for
Class I, II, III Division 1, Rev.1: July 16, 2019 Doc. No.: IFM024-A12 P.1
Groups A, B, C, D, E, F, G T4 IFM024
Yokogawa Electric Corporation
IM 01C25A01-01E
<2. Handling Cautions> 10
Model: EJX-F Series Date: January 27, 2005 Model: EJX-F Series Date: January 27, 2005
Rev.4: July 16, 2019 Doc. No.: IFM024-A12 P.2 Rev.1: July 16, 2019 Doc. No.: IFM024-A12 P.3
Model: EJX-F Series Date: May 9, 2006 Model: EJX-F Series Date: January 27, 2005
Rev.1: July 16, 2019 Doc. No.: IFM024-A12 P.2-1 Rev.5: July 16, 2019 Doc. No.: IFM024-A12 P.4-1
IM 01C25A01-01E
<2. Handling Cautions> 11
Model: EJX-F Series Date: August 19, 2005 Note 2. Installation
FNICO Rules Installation should be in accordance with Control
The FNICO Concept allows the interconnection of nonincendive field wiring apparatus to associated
nonincendive field wiring apparatus not specifically examined in such combination. The criterion for
Drawing IFM026-A12.
such interconnection is that the voltage (Vmax), the current (Imax) and the power (Pmax), which
nonincendive field wiring apparatus can receive and remain nonincendive, must be equal or greater
than the voltage (Uo, Voc or Vt), the current (Io, Isc or It) and the power (Po) which can be provided by Note 3. Specific conditions of use:
the associated nonincendive field wiring apparatus (supply unit). In addition the maximum
unprotected residual capacitance (Ci) and inductance (Li) of each apparatus (other than terminators)
connected to the Fieldbus must be less than or equal to 5 nF and 20 μH respectively.
Precautions shall be taken to minimize the risk from
In each N.I. Fieldbus segment only one active source, normally the associated nonincendive field
wiring apparatus, is allowed to provide the necessary power for the Fieldbus system. The allowed electrostatic discharge of painted parts.
voltage (Uo, Voc or Vt) of the associated nonincendive field wiring apparatus used to supply the bus
cable must be limited to the range 14 V d.c. to 17.5 V d.c. All other equipment connected to the bus When the enclosure of the Pressure Transmitters is
cable has to be passive, meaning that the apparatus is not allowed to provide energy to the system,
except a leakage current of 50 μA for each connected device. Separately powered equipment needs
galvanic isolation to ensure the nonincendive field wiring Fieldbus circuit remains passive.
made of aluminum alloy, if it is mounted in Zone 0, it
The cable used to interconnect the devices needs to comply with the following parameters:
Loop resistance R': 15....150 Ω/km
shall be installed such that, even in the event of rare
Inductance per unit length L': 0.4....1 mH/km
Capacitance per unit length C': 45....200 nF/km C' = C' line/line + 0.5 C' line/screen, if both lines are incidents, an ignition source due to impact and/or
floating or C' = C' line/line + C'line/screen, if the screen is connected to one line.
Length of spur cable: max. 60 m
Length of trunk cable: max. 1 km in IIC and 5 km in IIB
friction sparks is excluded.
Length of splice: max = 1 m
Terminators
At the end of each trunk cable an FM Approved line terminator with the following parameters is
suitable: Model: EJX910A-F Series Date: September 9, 2005
R = 90...100 Ω
C = 0 ....2.2 μF Control drawing (intrinsic safety)
Multivariable
Tr an smitter Sensor circuit
Intrinsically Safe
Apparatus
or
Simple Apparatus
Note 1.
• Applicable Standard:
FM 3600:2011
FM 3610:2010 Rev.1: July 16, 2019 Doc. No.: IFM026-A12 P.1
FM 3611:2004 IFM026
Yokogawa Electric Corporation
FM 3810:2005
ANSI/ISA-60079-0-2009
ANSI/ISA-60079-11-2009
ANSI/ISA-60079-27-2006
ANSI/ISA-61010-1-2004
NEMA 250:1991
• Rating
Intrinsically Safe with Entity/FISCO for Class I, II, III
Division 1 Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4
Nonincendive field wiring/FNICO for Class I, II
Division 2 Groups A, B, C, D, F, G T4
Class III Division 1 T4
Class I, Zone 2 Group IIC T4
• Ambient temperature: –40 to 60°C
• Enclosure: Type 4X
• Electrical Connection: 1/2 NPT female, M20
female
IM 01C25A01-01E
<2. Handling Cautions> 12
Model: EJX910A-F Series Date: September 9, 2005 Model: EJX910A-F Series Date: May 22, 2006
Supply circuit:
Multivariable
Entity parameters [Groups: A, B, C, D, E, F, G, and IIC] Tr an smitter Sensor circuit
Ui: 24 V
Ii: 250 mA
Pi: 1.2 W
Ci: 3.52 nF
Li: 0 µH Certified Equipment
FISCO parameters (1) [Groups: A, B, C, D, E, F, G, and IIC] or
Ui: 17.5 V Simple Apparatus
Ii: 380 mA
Pi: 5.32 W
Ci: 3.52 nF
Li: 0 µH
FISCO parameters (2) [Groups: C, D, E, F, G, and IIB]
Ui: 17.5 V
Ii: 460 mA
Pi: 5.32 W
Ci: 3.52 nF
Li: 0 µH Class I, II, Division 2
Groups A, B, C, D, F, G
Sensor circuit:
Class III, Division 1
Entity parameters [Groups: A, B, C, D, E, F, G, and IIC]
Uo: 6.51 V Class I, Zone 2, Group IIC
Io: 4 mA
Po: 6 mW
Co: 34 µF
Lo: 500 mH
Rev.2: July 16, 2019 Doc. No.: IFM026-A12 P.2 Rev.1: July 16, 2019 Doc. No.: IFM026-A12 P.3-1
Model: EJX910A-F Series Date: September 9, 2005 Model: EJX910A-F Series Date: May 22, 2006
IM 01C25A01-01E
<2. Handling Cautions> 13
Model: EJX910A-F Series Date: May 22, 2006 Note 2. Wiring
FNICO Rules
• All wiring shall comply with National Electrical
The FNICO Concept allows the interconnection of nonincendive field wiring apparatus to associated
nonincendive field wiring apparatus not specifically examined in such combination. The criterion for Code ANSI/NFPA70 and Local Electrical Codes.
such interconnection is that the voltage (Vmax), the current (Imax) and the power (Pmax), which
nonincendive field wiring apparatus can receive and remain nonincendive, must be equal or greater • When installed in Division 1, “FACTORY SEALED,
than the voltage (Uo, Voc or Vt), the current (Io, Isc or It) and the power (Po) which can be provided by
the associated nonincendive field wiring apparatus (supply unit). In addition the maximum
unprotected residual capacitance (Ci) and inductance (Li) of each apparatus (other than terminators)
CONDUIT SEAL NOT REQUIRED.”
connected to the Fieldbus must be less than or equal to 5 nF and 20 μH respectively.
In each N.I. Fieldbus segment only one active source, normally the associated nonincendive field • Wiring connection for output signal code Q (Low
wiring apparatus, is allowed to provide the necessary power for the Fieldbus system. The allowed
voltage (Uo, Voc or Vt) of the associated nonincendive field wiring apparatus used to supply the bus Power type) shall follow the diagram below.
cable must be limited to the range 14 V d.c. to 17.5 V d.c. All other equipment connected to the bus
cable has to be passive, meaning that the apparatus is not allowed to provide energy to the system,
except a leakage current of 50 μA for each connected device. Separately powered equipment needs Pressure Transmitters
galvanic isolation to ensure the nonincendive field wiring Fieldbus circuit remains passive.
The cable used to interconnect the devices needs to comply with the following parameters:
Loop resistance R': 15....150 Ω/km SUPPLY +
Inductance per unit length L': 0.4....1 mH/km
Voltmeter
Capacitance per unit length C': 45....200 nF/km C' = C' line/line + 0.5 C' line/screen, if both lines are
floating or C' = C' line/line + C'line/screen, if the screen is connected to one line.
A Power Supply
Length of spur cable: max. 60 m
Length of trunk cable: max. 1 km in IIC and 5 km in IIB
Length of splice: max = 1 m
+ +
Terminators
At the end of each trunk cable an FM Approved line terminator with the following parameters is
suitable: – –
R = 90...100 Ω
C = 0 ....2.2 μF
SUPPLY –
Three-Wire Connection
Pressure Transmitters
SUPPLY +
Voltmeter
A Power Supply
+ +
– –
SUPPLY –
Rev.1: July 16, 2019 Doc. No.: IFM026-A12 P.3-3
Note 3. Operation
• Keep the “WARNING” nameplate attached to the
d. FM Explosionproof
transmitter.
Caution for FM explosionproof type. WARNING: OPEN CIRCUIT BEFORE
REMOVING COVER. FACTORY SEALED,
Note 1. EJX/EJA-E Series pressure transmitters with
CONDUIT SEAL NOT REQUIRED. INSTALL IN
optional code /FF1 or /V1F are applicable for
ACCORDANCE WITH THE USERS MANUAL IM
use in hazardous locations.
01C25.
• Applicable Standard: FM3600:2018,
• Take care not to generate mechanical sparking
FM3615:2018, FM3810:2018, NEMA 250:2003,
when accessing to the instrument and peripheral
ANSI/UL 61010-1:2012,
devices in a hazardous location.
ANSI/UL 61010-2-30:2012
• Explosionproof for Class I, Division 1, Groups B, C Note 4. Maintenance and Repair
and D. • The instrument modification or parts replacement
• Dust-ignitionproof for Class II/III, Division 1, by other than authorized representative of
Groups E, F and G. Yokogawa Electric Corporation is prohibited and
• Enclosure: Type 4X will void Factory Mutual Explosionproof Approval.
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
32 V dc max. (FOUNDATION Fieldbus and
PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
9 to 30 V dc, 250 mW (RS485 Modbus
Communication Type)
• Output signal: 4 to 20 mA
15 mA (FOUNDATION Fieldbus and PROFIBUS PA
type)
1 to 5 V (Low Power type)
RS485 Modbus (RS485 Modbus Communication
Type)
IM 01C25A01-01E
<2. Handling Cautions> 14
e. FM Intrinsically Safe and Explosion Proof [For Division sytem]
Combination for HART/BRAIN Protocol • Intrinsically Safe for Class I, Division 1, Groups
Type A, B, C & D, Class II, Division 1, Groups E, F & G,
Class III, Division 1
EJX/EJA-E Series pressure transmitters with • Nonincendive for Class I, Division 2, Groups A, B,
optional code /FU1 or /V1U1 can be selected the C & D, Class II, Division 2, Groups F & G, Class III,
type of protection (FM Intrinsically Safe or FM Division 1
Explosionproof) for use in hazardous locations. • Enclosure: Type 4X
Note 1. For the installation of this transmitter, once a • Temp. Code: T4
particular type of protection is selected, any • Amb. Temp.: –50* to 60°C
* –15°C when /HE is specified.
other type of protection cannot be used. The
• Process Temperature: 120°C max.
installation must be in accordance with the
[For Zone system]
description about the type of protection in this
• Ex ia IIC T4, Ex nL IIC T4
instruction manual.
• Ambient Temperature: –50 to 60°C
Note 2. In order to avoid confusion, unnecessary • Max. Process Temp.: 120°C
marking is crossed out on the label other • Enclosure: IP66/IP67
than the selected type of protection when the
Note 2. Entity Parameters
transmitter is installed.
• Intrinsically safe ratings are as follows:
2.4.2 CSA Certification Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Input Current (Imax/Ii) = 200 mA
a. CSA Intrinsically Safe for HART/BRAIN Maximum Input Power (Pmax/Pi) = 0.9 W
Protocol Type (Except for EJX90A) Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
Caution for CSA Intrinsically safe and nonincendive
• Type "n" or Nonincendive ratings are as follows:
type. (Following contents refer to “DOC No. ICS013-
Maximum Input Voltage (Vmax/Ui) = 30 V
A13”)
Maximum Internal Capacitance (Ci) = 10 nF
Note 1. EJX/EJA-E Series pressure transmitters with Maximum Internal Inductance (Li) = 0 µH
optional code /CS1 are applicable for use in • Installation Requirements
hazardous locations. Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
Certificate: 1606623 Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
• Applicable Standard: Voc ≤ Vmax, Isc ≤ Imax,
C22.2 No.0 Ca ≥ Ci + Ccable, La ≥ Li + Lcable
C22.2 No.94 Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
C22.2 No.157 parameters of barrier.
C22.2 No.213
Note 3. Installation
C22.2 No.61010-1
• In any safety barreir used output current must
C22.2 No.61010-2-030
be limited by a resistor 'R' such that Io=Uo/R or
CAN/CSA C22.2 60079-0:07
Isc=Voc/R.
CAN/CSA E60079-11:02
• The safety barrier must be CSA certified.
CAN/CSA E60079-15:02
• Input voltage of the safety barrier must be less
CAN/CSA C22.2 No.60529
than 250 Vrms/Vdc.
ANSI/ISA-12.27.01
• Installation should be in accordance with Canadian
Electrical Code Part I and Local Electrical Code.
• Dust-tight conduit seal must be used when
installed in Class II and III environments.
IM 01C25A01-01E
<2. Handling Cautions> 15
• The instrument modification or parts replacement • CSA Intrinsically Safe Approval
by other than authorized representative of Class I, Division 1, Groups A, B, C, & D; Class II,
Yokogawa Electric Corporation and Yokogawa Division 1, Groups E, F & G; Class III; Ex ia IIC T4
Corporation of America is prohibited and will Ambient Temperature:
void Canadian Standards Intrinsically safe and –55* to 60 °C (Certificate date issued: February,
nonincendive Certification. 2020 or later)
[Intrinsically Safe] –40 to 60 °C (Certificate date issued: February,
Hazardous Location Nonhazardous Location 2016)
* –15°C when /HE is specified.
Group IIC, Zone 0
Type 4X, IP66/IP67
Class I, II, III, Division 1,
General • CSA Nonincendive Approval
Groups A, B, C, D, E, F, G
Purpose
Safety Barrier Class I, Division 2, Groups A, B, C, & D; Class II,
Pressure Transmitters Equipment
+ + +
Division 2, Groups F & G; Class III; Ex nL IIC T4
+
Ambient Temperature:
Supply – – – –
–55* to 60 °C (Certificate date issued: February,
2020 or later)
F0206.ai
–40 to 60 °C (Certificate date issued: February,
2016)
[Nonincendive] * –15°C when /HE is specified.
Hazardous Location Nonhazardous Location Type 4X, IP66/ IP67
Group IIC, Zone 2
Caution for CSA Intrinsically Safe Type.
Class I, II, Division 2, CSA Certified
Groups A, B, C, D, F, G
(Following Contents Refer to “DOC. No.
Equipment
Class III, Division 1. ([nL] or ICS018)
Pressure Transmitters nonincendive)
Installation Diagram for Intrinsically Safe
+ + (Division 1 Installation)
Supply – –
Not Use Terminator
Safety Barrier
F0207.ai
+ Pressure
– Transmitter
b. CSA Intrinsically Safe for Fieldbus Type
(Except for EJX90A) +
– Field Instruments
EJX/EJA-E Series pressure transmitters with optional
code /CS15 are applicable for use in hazardous
locations. +
– Field Instruments
• Certificate: 1689689
• Applicable standard:
C22.2 No.0 Hazardous Location
C22.2 No.94 Non-Hazardous Location
C22.2 No.157 Terminator
C22.2 No.213
+ –
C22.2 No.61010-1
Safety Barrier
C22.2 No.61010-2-030 + – F0229.ai
CAN/CSA C22.2 60079-0:07
CAN/CSA E60079-11:02
Note 1. The safety barrier must be CSA certified.
CAN/CSA E60079-15:02
CAN/CSA C22.2 No.60529 Note 2. Input voltage of the safety barrier must be less
ANSI/ISA-12.27.01 than 250Vrms/Vdc.
Note 3. Installation should be in accordance with
Canadian Electrical Code Part I and local
Electrical Code.
Note 4. Do not alter drawing without authorization from
CSA.
IM 01C25A01-01E
<2. Handling Cautions> 16
Electrical Data: Caution for CSA Non-incendive Type.
• Rating 1 (Entity) (Following contents refer to “DOC. No.
For Groups A, B, C, D, E, F, and G or Group IIC ICS018)
Ui (vmax) = 24 V dc Installation Diagram for Non-incendive or Type of
Ii (Imax) = 250 mA protection “n” (Division 2 Installation)
Pi (Pmax) = 1.2 W
Ci = 3.52 nF Terminator
Li = 0 μH
+
or –
SUPPLY
• Rating 2 (FISCO) Pressure
Transmitter
For Groups A, B, C, D, E, F, and G or Group IIC
Ui (vmax) = 17.5 V dc +
Transmitter
Ii (Imax) = 380 mA –
Pi (Pmax) = 5.32 W
Ci = 3.52 nF
Li = 0 μH +
Transmitter
or –
• Rating 3 (FISCO)
For Groups C, D, E, F, and G or Group IIB Hazardous location
Ui (vmax) = 17.5 V dc
Ii (Imax) = 460 mA Non-Hazardous location
Pi (Pmax) = 5.32 W Terminator
Ci = 3.52 nF
Li = 0 μH + –
Installation requirements; CSA Certified
Po ≤ Pi Uo ≤ Ui Io ≤ Ii, Equipment [nL]
+ –
Co ≥ Ci + Ccable Lo ≥ Li + Lcable
Vmax ≥ Voc Imax ≥ Isc F0230.ai
Ca ≥ Ci + Ccable La ≥ Li + Lcable
Uo, Io, Po, Co, Lo,Voc, Isc, Ca and La are parameters Note 1. Installation should be in accordance with
of barrier. Canadian Electrical Code Part I and local
Electrical Code.
Note 2. Dust-tight conduit seal must be used when
installed in class II and III environments.
Note 3. Do not alter drawing without authorization from
CSA.
Electrical Data:
• Rating (including FNICO)
Ui or Vmax = 32 V
Ci = 3.52 nF
Li = 0 μH
IM 01C25A01-01E
<2. Handling Cautions> 17
c. CSA Explosionproof Type Non-Hazardous Hazardous Locations Division 1
Locations
Caution for CSA explosionproof type.
Non-hazardous
Location Equipment 45 cm Max.
Note 1. EJX/EJA-E Series pressure transmitters with
optional code /CF1 or /V1F are applicable for
use in hazardous locations.
• Certificate: 2014354 42 V DC Max. Conduit
4 to 20 mA DC Sealing Fitting
• Applicable Standard: Signal
C22.2 No. 25 Transmitter
F0208.ai
C22.2 No. 30
CAN/CSA-C22.2 No. 94 Non-Hazardous Hazardous Locations Division 2
CAN/CSA-C22.2 No. 61010-1-12 Locations
CAN/CSA-C22.2 No. 61010-2-030-12 Non-hazardous
Location Equipment
CAN/CSA-C22.2 No. 60079-0:07
CAN/CSA-C22.2 No. 60079-1:07
CAN/CSA-C22.2 No. 60529
42 V DC Max.
ANSI/ISA-12.27.01 4 to 20 mA DC Sealing Fitting
• Explosion-proof for Class I, Groups B, C and D. Signal
Transmitter
• Dustignition-proof for Class II/III, Groups E, F and F0209.ai
G.
• Enclosure: Type 4X • All wiring shall comply with local installation
• Temperature Code: T6...T4 requirements and local electrical code.
• Ex d IIC T6...T4 • In hazardous locations, the cable entry devices
• Enclosure: IP66/IP67 shall be of a certified flameproof type, suitable for
• Maximum Process Temperature: 120°C (T4), the conditions of use and correctly installed.
100°C (T5), 85°C (T6) • Unused apertures shall be closed with suitable
• Ambient Temperature: –50* to 75°C (T4), flameproof certified blanking elements. (The plug
–50* to 80°C (T5), –50* to 75°C (T6) attached is flameproof certified.)
* –15°C when /HE is specified. • Wiring connection for output signal code Q (Low
• Supply Voltage: 42 V dc max. Power type) shall follow the diagram below.
32 V dc max. (FOUNDATION Fieldbus and
PROFIBUS PA type) Pressure Transmitters
9 to 28 V dc, 27 mW (Low Power type) SUPPLY +
9 to 30 V dc, 250 mW (RS485 Modbus Voltmeter
A Power Supply
Communication Type)
+ +
• Output Signal: 4 to 20 mA dc
15 mA (FOUNDATION Fieldbus and PROFIBUS PA – –
type)
SUPPLY –
1 to 5 V (Low Power type)
RS485 Modbus (RS485 Modbus Communication Three-Wire Connection
Type) Pressure Transmitters
Note 2. Wiring SUPPLY +
• All wiring shall comply with Canadian Electrical Voltmeter
A Power Supply
Code Part I and Local Electrical Codes.
+ +
• In hazardous location, wiring shall be in conduit as
shown in the figure. – –
• WARNING:
SUPPLY –
A SEAL SHALL BE INSTALLED WITHIN 45cm OF
THE ENCLOSURE. Four-Wire Connection
F0219.ai
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 45cm DU BOÎTIER.
• WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL NOT
REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2, AUCUN
JOINT N'EST REQUIS.
IM 01C25A01-01E
<2. Handling Cautions> 18
Note 3. Operation 2.4.3 ATEX Certification
• WARNING:
AFTER DE-ENERGIZING, DELAY 5 MINUTES (1) Technical Data
BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5 MINUTES a. ATEX Intrinsically Safe for HART/BRAIN
AVANT D'OUVRIR. Protocol Type (Except for EJX90A)
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65°C, USE Caution for ATEX Intrinsically safe type.
THE HEAT-RESISTING CABLES ≥ 90°C. Note 1. EJX/EJA-E Series pressure transmitters with
QUAND LA TEMPÉRATURE AMBIANTE ≥ 65°C, optional code /KS21 for potentially explosive
UTILISEZ DES CÂBLES RÉSISTANTES Á LA atmospheres.
CHALEUR ≥ 90°C. • No. DEKRA 11ATEX0228 X
• Take care not to generate mechanical sparking • Applicable Standard:
when accessing to the instrument and peripheral EN 60079-0:2012+A11:2013
devices in a hazardous location. EN 60079-11:2012
Note 4. Maintenance and Repair • Type of Protection and Marking code:
• The instrument modification or parts replacement Ex ia IIC T4 Ga
by other than authorized representative of Ex ia IIIC T85 ºC T100 ºC T120 ºC Db
Yokogawa Electric Corporation and Yokogawa • Group: II
Corporation of America is prohibited and will void • Category: 1G, 2D
Canadian Standards Explosionproof Certification. • Ambient Temperature for EPL Ga:
–50 to 60°C
d. CSA Intrinsically Safe and Explosion-proof • Ambient Temperature for EPL Db:
Combination for HART/BRAIN Protocol –30* to 60°C
Type (Except for EJX90A) * –15°C when /HE is specified.
• Process Temperature (Tp.): 120°C max.
EJX/EJA-E Series pressure transmitters with • Maximum Surface Temperature for EPL Db:
optional code /CU1 or /V1U1 can be selected the T85°C (Tp.: 80°C)
type of protection (CSA Intrinsically Safe or CSA T100°C (Tp.: 100°C)
Explosionproof) for use in hazardous locations. T120°C (Tp.: 120°C)
Note 1. For the installation of this transmitter, once a • Enclosure: IP66 / IP67
particular type of protection is selected, any To satisfy IP66 or IP67, apply waterproof glands to
other type of protection cannot be used. The the electrical connection port.
installation must be in accordance with the Note 2 Electrical Data
description about the type of protection in this • In type of explosion protection intrinsic safety Ex ia
instruction manual. IIC or Ex ia IIIC, only for connection to a certified
Note 2. For combined approval types, once a device of intrinsically safe circuit with following maximum
multiple approval type is installed, it should not values:
be re-installed using any other approval types. Ui = 30 V
Apply a permanent mark in the check box of the Ii = 200 mA
selected approval type on the certification label Pi = 0.9 W
on the transmitter to distinguish it from unused (Linear Source)
approval types. Maximum internal capacitance; Ci = 27.6 nF
Maximum internal inductance; Li = 0 µH
IM 01C25A01-01E
<2. Handling Cautions> 19
Note 3. Installation b. ATEX Intrinsically Safe for Fieldbus Type
• Refer to the control drawing. All wiring shall comply (Except for EJX90A)
with local installation requirements.
Caution for ATEX Intrinsically safe type.
[Control Drawing]
Note 1. EJX/EJA-E series pressure transmitters with
Hazardous Location Nonhazardous Location
optional code /KS26 for potentially explosive
Pressure Transmitters atmospheres:
+ + Certification Information:
Supply Safety Barrier *1
– –
WARNING
A modification of the equipment would no longer
F0210.ai comply with the construction described in the
*1: Any safety barriers must be a linear power source certificate documentation.
whose output current is resistively limited.
IM 01C25A01-01E
<2. Handling Cautions> 20
Enclosure: Note 6. Maintenance and Repair:
IP66/IP67 in accordance with only EN60529 • Only personnel authorized by Yokogawa Electric
Electrical Parameters: Corporation can repair the equipment.
Intrinsically safe ratings are as follows:
Note7. Control drawing
[Entity]
Ui = 24 V
Ii = 250 mA
Pi = 1.2 W
Ci = 3.52 nF
Li = 0 μH
[FISCO IIC]
Ui = 17.5 V
Ii = 380 mA
Pi = 5.32 W
Ci = 3.52 nF
Li = 0 μH
[FISCO IIB]
Ui = 17.5 V
Ii = 460 mA
Pi = 5.32 W
Ci = 3.52 nF
Li = 0 μH
Note 3. Installation:
• Refer to the control drawing IKE022-A12 P.1 and
P.2. (Note 7.)
• The type of threads is indicated at the cable entry,
using the following marking.
Screw Size Marking
ISO M20 × 1.5 female M
ANSI 1/2 NPT female A or N or W
F0239.ai
IM 01C25A01-01E
<2. Handling Cautions> 21
c. ATEX Intrinsically Safe for Fieldbus Type Note 4. Maintenance and Repair
for EJX90A • The instrument modification or parts replacement
by other than authorized representative of
Caution for ATEX Intrinsically safe type.
Yokogawa Electric Corporation is prohibited and
Note 1. EJX multivariable transmitter with optional will void DEKRA Intrinsically safe Certification.
code /KS26 are applicable for use in hazardous
Note 5. Special Conditions for Safe Use
locations:
• No. KEMA 06ATEX0278 X
• Applicable Standard: WARNING
EN 60079-0:2012+A11:2013
EN 60079-11:2012 • In the case where the enclosure of the Pressure
Transmitter is made of aluminium, if it is mounted
Note 2. Ratings
in an area where the use of category 1G apparatus
Type of Protection and Marking Code:
is required, it must be installed such, that even in
Ex ia IIC/IIB T4 Ga
the event of rare incidents, ignition sources due to
Ex ia IIIC T85°C T100°C T120°C Db
impact and friction sparks are excluded.
Group: II
• Electrostatic charge may cause an explosion
Category: 1G, 2D
hazard. Avoid any actions that cause the
Ambient Temperature for EPL Ga:
generation of electrostatic charge, such as rubbing
–40 to 60°C
with a dry cloth on coating face of the product.
Ambient Temperature for EPL Db:
• In the case where the enclosure of the Pressure
–30* to 60°C
* –15°C when /HE is specified.
Transmitter is made of aluminum, if it is mounted in
Maximum Process Temperature (Tp.): 120°C an area where the use of category 2D apparatus is
Maximum Surface Temperature for EPL Db. required, it shall be installed in such a way that the
T85°C (Tp.: 80°C) risk from electrostatic discharges and propagating
T100°C (Tp.: 100°C) brush discharges caused by rapid flow of dust is
T120°C (Tp.: 120°C) avoided.
Ambient Humidity: • To satisfy IP66 or IP67, apply waterproof glands to
0 to 100% (No condensation) the electrical connection port.
Degree of Protection of the Enclosure: • When the lightning protector option is specified,
IP66/IP67 the apparatus is not capable of withstanding the
Electrical Data 500V insulation test required by EN60079-11.
• When combined with Trapezoidal or Rectanglar This must be taken into account when installing
output characteristic FISCO model IIC barrier the apparatus.
[Supply circuit (terminals + and -)]
Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W,
Note 6. Installation instructions
Ci = 3.52 nF, Li = 0 µH
[Installation Diagram]
[Sensor circuit]
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W,
Co = 4.8 µF, Lo = 100 mH Terminator RTD
• When combined with Linear characteristic barrier Pt100.3wire
[Supply circuit (terminals + and -)] + Pressure
− SUPPLY Transmitter
Ui = 24 V, Ii = 250 mA, Pi = 1.2 W,
Ci = 3.52 nF, Li = 0 µH
+
[Sensor circuit] − Transmitter
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W,
Co = 4.8 µF, Lo = 100 mH
• When combined with Trapezoidal or Rectanglar + Transmitter
−
output characteristic FISCO model IIB barrier
[Supply circuit (terminals + and -)]
Hazardous Location
Ui = 17.5 V, Ii = 460 mA, Pi = 5.32 W,
Ci = 3.52 nF, Li = 0 µH Non-Hazardous Location
Terminator
[Sensor circuit]
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W,
+ −
Co = 4.8 µF, Lo = 100 mH Safety Barrier
Note 3. Installation + − F0232.ai
IM 01C25A01-01E
<2. Handling Cautions> 22
• In the rating 1(*1), the output current of the barrier d. ATEX Flameproof Type
must be limited by a resistor ‘Ra’ such that Io = Uo/
Caution for ATEX flameproof type.
Ra.
• In the rating 2(*2), the output of the barrier must be Note 1. EJX/EJA-E Series pressure transmitters with
the characteristics of the trapezoid or the rectangle optional code /KF22 or /V1F are applicable for
and this transmitter can be connected to Fieldbus use in hazardous locations.
equipment which are in according to the FISCO • No. KEMA 07ATEX0109 X
model. • Applicable Standard:
• The terminators may be built in by a barrier. EN IEC 60079-0
• More than one transmitter may be connected to EN 60079-1, EN 60079-31
the power supply line. • Type of Protection and Marking Code:
• The terminator and the safety barrier shall be Ex db IIC T6...T4 Gb, Ex tb IIIC T85°C Db
certified. • Group: II
Electrical data: • Category: 2G, 2D
Supply circuit • Enclosure: IP66 / IP67
Maximum Input Voltage Ui: 24 V • Temperature Class for gas-poof:
Maximum Input Current Ii: 250 mA T6, T5, and T4
*1: • Ambient Temperature for gas-proof:
Maximum Input Power Pi: 1.2 W
Rating 1 –50 to 75°C (T6), –50 to 80°C (T5), and
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH –50 to 75°C (T4)
or • Process Temperature (Tp.) for gas-proof:
Maximum Input Voltage Ui: 17.5 V –50 to 85°C (T6), –50 to 100°C (T5), and
Maximum Input Current Ii: 380 mA –50 to 120°C (T4)
Maximum Input Power Pi: 5.32 W • Maximum Surface Temperature for dust-proof:
Maximum Internal Capacitance Ci: 3.52 nF T85°C (Tamb.: –30* to 75°C, Tp.: –30* to 85°C)
* –15°C when /HE is specified.
Maximum Internal Inductance Li: 0 μH
*2:
or Note 2. Electrical Data
Rating 2
Maximum Input Voltage Ui: 17.5 V • Supply voltage: 42 V dc max.
Maximum Input Current Ii: 460 mA 32 V dc max. (FOUNDATION Fieldbus and
Maximum Input Power Pi: 5.32 W PROFIBUS PA type)
Maximum Internal Capacitance Ci: 3.52 nF 9 to 28 V dc, 27 mW (Low Power type)
Maximum Internal Inductance Li: 0 μH 9 to 30 V dc, 250 mW (RS485 Modbus
Communication Type)
Sensor circuit • Output signal: 4 to 20 mA
Maximum Output Voltage Uo: 7.63 V 15 mA (FOUNDATION Fieldbus and PROFIBUS PA
Maximum Output Current Io: 3.85 mA type)
Maximum Output Power Po: 0.008 W 1 to 5 V (Low Power type)
Maximum Internal Capacitance Co: 4.8 μF RS485 Modbus (RS485 Modbus Communication
Maximum Internal Inductance Lo: 100 mH Type)
Note3. For combined approval types Once a device of
• RTD sensor is prepared by the user. multiple approval type is installed, it should not
The sensor signal line must suited a test voltage of be re-installed using any other approval types.
500Vac. Apply a permanent mark in the check box of the
selected approval type on the ertification label
on the transmitter to distinguish it from unused
approval types.
IM 01C25A01-01E
<2. Handling Cautions> 23
Note 4. Installation Note 7. Specific Conditions of Use
• All wiring shall comply with local installation
requirement.
• In order to prevent the earthing conductor from
WARNING
loosening, the conductor must be secured to the
• Electrostatic charge may cause an explosion
terminal, tightening the screw with appropriate
hazard. Avoid any actions that cause the
torque. Care must be taken not to twist the
generation of electrostatic charge, such as rubbing
conductor.
with a dry cloth on coating face of the product.
• Cable glands, adapters and/or blanking elements
• In the case where the enclosure of the Pressure
with a suitable IP rating shall be of Ex d IIC/Ex tb
Transmitter is made of aluminium, if it is mounted
IIIC certified by ATEX and shall be installed so as
in an area where the use of category 2D apparatus
to maintain the specific degree of protection (IP
is required, it shall be installed in such a way
Code) of the equipment.
that the risk from electrostatic discharges and
• Wiring connection for output signal code Q (Low
propagating brush discharges caused by rapid
Power type) shall follow the diagram below.
flow of dust is avoided.
Pressure Transmitters • The flame paths differ from the standard values
SUPPLY + in EN 60079-1. Repair of the equipment is only
Voltmeter allowed when done by the manufacturer or an
A Power Supply
+ +
authorised representative.
• The fasteners used to fasten the transmitter
– – enclosure onto the sensor capsule is special
fastener, and the property class of it is
SUPPLY –
A2-50(A4-50) or more.
Three-Wire Connection For transmitters with a membrane made of
Pressure Transmitters titanium, ignition hazard due to impact and friction
on the membranes shall be avoided.
SUPPLY +
Voltmeter • Maximum Surface Temperature for dust-proof:
A Power Supply T85°C (Tamb.: –30* to 75°C, Tp.: –30* to 85°C)
+ + * –15°C when /HE is specified.
– –
IM 01C25A01-01E
<2. Handling Cautions> 24
ATEX Intrinsically Safe Ex ic f. ATEX Intrinsically Safe Ex ic for Fieldbus
Type (Except for EJX90A)
Caution for ATEX intrinsically safe Ex ic
• Applicable Standard: Caution for ATEX Intrinsically safe Ex ic.
EN 60079-0:2012+A11:2013
Note 1. The transmitters with option code /KN26 for
EN 60079-11:2012
potentially explosive atmospheres
• Type of Protection and Marking Code:
Applicable Standard:
II 3G Ex ic IIC T4 Gc
EN IEC 60079-0, EN 60079-11
• Ambient Temperature: –30* to +60°C
* –15°C when /HE is specified. Note 2. Rating
• Ambient Humidity: Ex Marking:
0 to 100% (No condensation) II 3 G Ex ic IIC T4 Gc
• Maximum Process Temperature: 120°C Temperature specifications:
• IP Code: IP66 Ambient Process
• Ambient pollution degree: 2 Type of O-ring
temperature range temperature range
• Overvoltage category: I –30 to 60°C –30 to 120°C NBR
Fluoro-rubber
Note 1. Electrical Data –15 to 60°C –15 to 120°C
(FKM)
Ui = 30 V
Ci = 27.6 nF IP Code: IP66
Li = 0 µH Overvoltage Category: I
Electrical Parameters: See control drawing
Note 2. Installation
IKE047-A70 (Note 7.)
• All wiring shall comply with local installation
requirements. (refer to the control drawing) Note 3. Installation:
• Cable glands, adapters and/or blanking elements • See control drawing IKE047-A70. (Note 7.)
shall be of Ex “n”, Ex “e” or Ex “d” and shall be • The type of threads is indicated at the cable entry,
installed so as to maintain the specified degree of using the following marking.
protection (IP Code) of the transmitters.
Screw Size Marking
Note 3. Maintenance and Repair
ISO M20 × 1.5 female M
• The instrument modification or parts replacement
by other than authorized representative of ANSI 1/2 NPT female A or N or W
Yokogawa Electric Corporation is prohibited and F0239.ai
WARNING
• Electrostatic charge may cause an explosion
hazard. Avoid any actions that cause the
generation of electrostatic charge, such as rubbing
with a dry cloth on coating face of the product.
• When the lightning protector option is specified,
the apparatus is not capable of withstanding the
500V insulation test required by EN60079-11. This
must be taken into account when installing the
apparatus.
IM 01C25A01-01E
<2. Handling Cautions> 25
Note 7. Control drawing (3) Installation
WARNING
• All wiring shall comply with local installation
requirements and the local electrical code.
• There is no need for conduit seal in Division 1
and Division 2 hazardous locations because this
product is sealed at the factory.
(4) Operation
WARNING
• OPEN CIRCUIT BEFORE REMOVING COVER.
INSTALL IN ACCORDANCE WITH THIS USER’S
MANUAL
• Take care not to generate mechanical sparking
when access to the instrument and peripheral
devices in a hazardous location.
WARNING
(2) Electrical Connection
The instrument modification or parts replacement by
A mark indicating the electrical connection type is other than an authorized Representative of Yokogawa
stamped near the electrical connection port. These Electric Corporation is prohibited and will void the
marks are as followed. certification.
Screw Size Marking
ISO M20 × 1.5 female M
ANSI 1/2 NPT female N or W
F0214.ai
IM 01C25A01-01E
<2. Handling Cautions> 26
(6) Name Plate Tag plate for intrinsically safe Ex ic for Fieldbus
Ex ic IIC T4 Gc
Name plate IP66
Tamb -30(-15) TO 60°C
MAX. PROCESS TEMP. 120°C
Ui=32V, Ci=3.52nF, Li=0µH
WARNING
T6 T5 T4
[EJX90A]
PROCESS TEMP.(Tp.) -50 TO 85 100 120 °C
Tamb.
Ex tb IIIC T85°C Db
-50 TO 75 80 75 °C Tag plate for intrinsically safe Ex ia for Fieldbus
T85°C(Tamb.:-30(-15) TO 75°C, Tp.:-30(-15) TO 85°C)
No. KEMA 06ATEX0278 X
Ex ia IIC/IIB T4 Ga Ta: -40 to 60°C
Ex ia IIIC T85°C T100°C T120°C Db Ta: -30(-15) to 60°C
MAX PROCESS TEMP.(Tp.): 120°C
T85°C (Tp.: 80°C), T100°C (Tp.: 100°C), T120°C (Tp.: 120°C)
*3 D ENCLOSURE: IP66/IP67
Supply circuit
FISCO field device(IIC/IIB)
WARNING Entity Parameter Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0µH
Sensor circuit
Uo=7.63V, Io=3.85mA, Po=0.008W, Co=4.8uF, Lo=100mH
F0215-1.ai
WARNING
second block
POTENTIAL ELECTROSTATIC
CHARGING HAZARD
- SEE USER’S MANUAL NO. 91K819857 132 7
F0215-2.ai
*3 D
WARNING
*3 D
WARNING
F0215-3.ai
IM 01C25A01-01E
<2. Handling Cautions> 27
2.4.4 IECEx Certification Note 3. Installation
• In any safety barrier used output current must be
Model EJX Series pressure transmitters with optional
limited by a resistor ‘R’ such that Io=Uz/R.
code /SU21 can be selected the type of protection
• The safety barrier must be IECEx certified.
(IECEx Intrinsically Safe Ex ia, Ex ic or flameproof) for
• Input voltage of the safety barrier must be less
use in hazardous locations.
than 250 Vrms/Vdc.
EJX Series pressure transmitters with optional code
/SS26 can be selected the type of protection (IECEx • The instrument modification or parts replacement
intrinsically safe Ex ia or Ex ic) for use in hazardous by other than authorized representative of
locations. Yokogawa Electric Corporation is prohibited and
EJX Series pressure transmitters with will void IECEx certification.
optional code /SU2 can be selected the type of [Ex ia]
protection (IECEx Intrinsically Safe/type n or Hazardous Location Nonhazardous Location
flameproof) for use in hazardous locations. Group IIC, Zone 0
Note 1. For the installation of this transmitter, once a EJX/EJA-E Series IECEx certified
particular type of protection is selected, any Pressure Transmitters Safety Barrier
other type of protection cannot be used. The + +
installation must be in accordance with the Supply – –
description about the type of protection in this
instruction manual.
(*1)
Note 2. For combined approval types, once a device of
*1: When using non isolation barrier,
multiple approval type is installed, it should not connect (*1) to IS barrier system. F0236.ai
be re-installed using any other approval types.
Apply a permanent mark in the check box of the Note 4. Specific Condition of Use
selected approval type on the certification label
on the transmitter to distinguish it from unused
approval types.
WARNING
a. IECEx Intrinsically Safe Ex ia for HART/ • Electrostatic charge may cause an explosion
BRAIN Protocol Type (Except for EJX90A) hazard. Avoid any actions that cause the
generation of electrostatic charge, such as rubbing
Caution for IECEx Intrinsically safe Ex ia. with a dry cloth on coating face of the product.
Note 1. EJX/EJA-E series pressure transmitters with • When the enclosure of the pressure transmitter
optional code /SU21 are applicable for use in is made of aluminum, if it is mounted in an area
hazardous locations where the use of EPL Ga equipment is required, it
• No. IECEx DEK 11.0081X must be installed such, that, even in the event of
• Applicable Standard: IEC 60079-0:2011, rare incidents, ignition sources due to impact and
IEC 60079-11:2011 friction sparks are excluded.
• Ex ia IIC T4 Ga • Electrostatic charges on the coated parts of
• Ambient Temperature: –50 to 60°C Pressure Transmitter shall be avoided.
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
To satisfy IP66 or IP67, apply waterproof glands to b. IECEx Intrinsically Safe Ex ic for HART/
the electrical connection port. BRAIN Protocol Type (Except for EJX90A)
Note 2. Electrical Data Caution for IECEx Intrinsically safe Ex ic.
Maximum Input Voltage (Ui) = 30 V Note 1. EJX/EJA-E series pressure transmitters with
Maximum Input Current (Ii) = 200 mA optional code /SU21 are applicable for use in
Maximum Input Power (Pi) = 0.9 W (linear source) hazardous locations
Maximum Internal Capacitance (Ci) = 27.6 nF • No. IECEx DEK 13.0061X
Maximum Internal Inductance (Li) = 0 μH • Applicable Standard: IEC 60079-0:2011,
When the lightning protector option is specified, the IEC 60079-11:2011
apparatus is not capable of withstanding the 500V • Ex ic IIC T4 Gc
insulation test required by IEC60079-11. This must be • Ambient Temperature: –30* to 60°C
* -15 °C when /HE is specified.
taken into account when installing the apparatus.
• Max. Process Temp.: 120°C
• IP Code: IP66
• Overvoltage Category: I
IM 01C25A01-01E
<2. Handling Cautions> 28
Note 2. Electrical Data c. IECEx Intrinsically Safe Ex ia for Fieldbus
Maximum Input Voltage (Ui) = 30 V Type (Except for EJX90A)
Maximum Internal Capacitance (Ci) = 27.6 nF
Caution for IECEx Intrinsically safe Ex ia.
Maximum Internal Inductance (Li) = 0 μH
Note 1. EJX/EJA-E Series pressure transmitters with
Note 3. Installation
optional code /SS26 are applicable for use in
• The pressure transmitter is allowed to be installed
hazardous locations.
in “nL” systems, on condition that the output
Certification Information:
parameters of “nL” source (associated energy-
limited apparatus) are suitable to the above
mentioned input parameters of the pressure WARNING
transmitter and the cable parameters.
• Cable glands, adapters and/or blanking elements A modification of the equipment would no longer
shall be of Ex “n”, Ex “e” or Ex “d” and shall be comply with the construction described in the
installed so as to maintain the specified degree of certificate documentation.
protection of the equipment.
• The instrument modification or parts replacement Certificate Number:
by other than authorized representative of IECEx DEK 12.0016X
Yokogawa Electric Corporation is prohibited and
will void IECEx certification.
[Ex ic]
NOTE
Hazardous Location Nonhazardous Location
The symbol “X” placed after the certificate number
EJX/EJA-E Series Associated apparatus indicates that the equipment is subject to specific
Pressure Transmitters conditions of use.
+ +
• Applicable Standard
Supply
– – IEC 60079-0 :2011 (Certificate issue number:4)
IEC 60079-0 (Certificate issue number:5 or later)
F0237.ai IEC 60079-11:2011
IM 01C25A01-01E
<2. Handling Cautions> 29
Electrical Parameters: Note 6. Maintenance and Repair
Intrinsically safe ratings are as follows: • Only personnel authorized by Yokogawa Electric
[Entity] Corporation can repair the equipment.
Ui = 24 V
Note7. Control drawing
Ii = 250 mA
Pi = 1.2 W
Ci = 3.52 nF
Li = 0 μH
[FISCO IIC]
Ui = 17.5 V
Ii = 380 mA
Pi = 5.32 W
Ci = 3.52 nF
Li = 0 μH
[FISCO IIB]
Ui = 17.5 V
Ii = 460 mA
Pi = 5.32 W
Ci = 3.52 nF
Li = 0 μH
Note 3. Installation
• Refer to the control drawing IKE022-A12 P.1 and
P.2. (Note 7.)
• The type of threads is indicated at the cable entry,
using the following marking.
Screw Size Marking
ISO M20 × 1.5 female M
ANSI 1/2 NPT female A or N or W
F0239.ai
IM 01C25A01-01E
<2. Handling Cautions> 30
d. IECEx Intrinsically Safe Ex ic for Fieldbus Note 4. Operation
Type (Except for EJX90A) • If the pressure transmitter is mounted in an area
where explosive atmospheres may be present,
Caution for IECEx Intrinsically safe Ex ic.
it must be installed in such a way that the risk
Note 1. EJX/EJA-E Series pressure transmitters with from electrostatic discharges and propagating
optional code /SS26 are applicable for use in brush discharges caused by rapid flow of dust are
hazardous locations. avoided.
Certification Information:
Note 5. Specific conditions of use
• See control drawing IIE020-A70 (Note 7.)
WARNING Note 6. Maintenance and Repair
• Only personnel authorized by Yokogawa Electric
A modification of the equipment would no longer Corporation can repair the equipment.
comply with the construction described in the
certificate documentation. Note 7. Control drawing
Certificate Number:
IECEx DEK 13.0064X
NOTE
The symbol “X” placed after the certificate number
indicates that the equipment is subject to specific
conditions of use.
Applicable Standard:
IEC 60079-0, IEC 60079-11
Note 2. Ratings
Ex Marking: Ex ic IIC T4 Gc
Temperature specifications:
Ambient Process
Type of O-ring
temperature range temperature range
–30 to 60°C –30 to 120°C NBR
Fluoro-rubber
–15 to 60°C –15 to 120°C
(FKM)
IP Code: IP66
Overvoltage Category: I
Electrical Parameters: See control drawing
IIE020-A70 (Note 7.)
Note 3. Installation
• See control drawing IIE020-A70. (Note 7.)
e. IECEx Flameproof Type
• The type of threads is indicated at the cable entry,
using the following marking. Caution for IECEx flameproof type.
IM 01C25A01-01E
<2. Handling Cautions> 31
• Supply Voltage: 42 V dc max. Note 4. Maintenance and Repair
32 V dc max. (FOUNDATION Fieldbus and • The instrument modification or parts replacement
PROFIBUS PA type) by other than authorized representative of
9 to 28 V dc, 27 mW (Low Power type) Yokogawa Electric Corporation is prohibited and
9 to 30 V dc, 250 mW (RS485 Modbus will void IECEx Certification.
Communication Type) • Electrical Connection
• Output Signal: 4 to 20 mA dc A mark indicating the electrical connection type is
15 mA (FOUNDATION Fieldbus and PROFIBUS PA stamped near the electrical connection port. These
type) marks are as followed.
1 to 5 V (Low Power type)
Screw Size Marking
RS485 Modbus (RS485 Modbus Communication
Type) ISO M20 × 1.5 female M
Three-Wire Connection
CAUTION
Pressure Transmitters
To meet EMC regulations, Yokogawa recommends
SUPPLY +
Voltmeter that customers run signal wiring through metal
A Power Supply conduits or use shielded twisted-pair cabling when
+ + installing EJX/EJA-E Series transmitters in a plant.
This equipment is a Class A product, and it is designed
– –
for use in the industrial environment. Please use this
SUPPLY – instrument in the industrial environment only.
Four-Wire Connection
F0221.ai
IM 01C25A01-01E
<2. Handling Cautions> 32
(2) Technical Data *1: PS is maximum pressure for vessel itself based on
Pressure Equipment Directive 2014/68/EU. Refer to
• Models without /PE3 General Specification for maximum working pressure of a
transmitter.
Article 4, Paragraph 3 of PED, denoted as Sound
*2: Referred to Table 1 covered by ANNEX II of EC Directive
Engineering Practice (SEP). on Pressure Equipment Directive 2014/68/EU.
• Models with /PE3
Module: H (3) Operation
Type of Equipment: Pressure Accessory-Vessel
Type of fluid: Liquid and Gas CAUTION
Group of fluid: 1 and 2
• The temperature and pressure of fluid should
Capsule PS*1 PS.V
Model
code (bar)
V(L)
(bar.L)
Category*2 be maintained at levels that are consistent with
normal operating conditions.
EJA110E M, H, V
160 0.01 1.6 • The ambient temperature should be maintained
EJ110 F, L at a level that is consistent with normal operating
Article 4,
EJX110A Paragraph 3 conditions.
(SEP) • Please take care to prevent water hammer and the
EJA110E M, H, V 250 0.01 2.5
with code like from inducing excessive pressures in pipes
/HG and valves. If phenomena are likely, install a safety
EJ110 valve or take some other appropriate measure to
with code / M, H, V 250 0.01 2.5 III
prevent pressure from exceeding PS.
PE3
Article 4,
• Take appropriate measures at the device or
EJ130 M, H 500 0.01 5.0 Paragraph 3 system level to protect transmitters if they are to be
(SEP) operated near an external heat source.
EJ130
with code / M, H 500 0.01 5.0 III
PE3
Article 4, 2.7 EU RoHS Directive
EJ310 L, M, A, B 160 0.01 1.6 Paragraph 3
(SEP) Applicable standard: EN 50581
Article 4, Applicable production sites are shown below.
EJ430 H, A, B 160 0.01 1.6 Paragraph 3 The condition of the RoHS compliant production sites
(SEP)
are as follows:
Article 4,
EJ440 C, D 500 0.1 5.0 Paragraph 3 Japan, USA, Germany, Bahrain, India
(SEP)
The production sites can be confirmed by the serial
EJ440
with code / C, D 500 0.1 5.0 III number shown in the frame of “NO.” in the name plate
PE3 of the product.
A, B, C 100 0.1 10 Article 4,
EJ510 Serial numbers (9 letters): AAnnnnnnn
Paragraph 3
EJX610A D 700 0.1 70 AA: Identification code of production site
(SEP)
EJ510, Japan: Use “91” USA: Use “U1”
EJX610A Germany: Use “D1” Bahrain: Use “BH”
D 700 0.1 70 III
with code / India: Use “Y1”
PE3
A, B, C 100 0.1 10 Article 4,
EJ530,
Paragraph 3
EJX630A D 700 0.1 70 (SEP)
EJ530,
EJX630A
D 700 0.1 70 III
with code /
PE3
L 160 0.01 1.6 Article 4,
EJX910A Paragraph 3
M, H 250 0.01 2.5 (SEP)
EJX910A
with code / M, H 250 0.01 2.5 III
PE3
Article 4,
EJX930A M, H 500 0.01 5.0 Paragraph 3
(SEP)
EJX930A
with code / M, H 500 0.01 5.0 III
PE3
IM 01C25A01-01E
<2. Handling Cautions> 33
2.8 Safety Requirement
Standards
Applicable standard: EN 61010-1, EN 61010-2-30,
C22.2 No.61010-1, C22.2 No.61010-2-030
IM 01C25A01-01E
<3. Installation> 34
3. Installation
Vertical pipe mounting Vertical pipe mounting
IMPORTANT (Process connector upside) (Process connector downside)
Figure 3.2 Transmitter Mounting flange or the screws at the joints between the
(Horizontal Impulse Piping Type) capillary tube and cover flanges. If the seal liquid
leaks, the transmitter cannot be used.
IM 01C25A01-01E
<3. Installation> 35
3.2.1 EJ210 3.3 Diaphragm Seals Installation
The transmitter is mounted on a process using its Consideration
high pressure side flange as shown in Figure 3.5. The
customer should prepare the mating flange, gasket, stud IMPORTANT
bolts and nuts.
• When measuring the liquid level of the tank, the
minimum liquid level (zero point) must be set to a
Gasket level at least 50 mm above the center of the high
pressure side diaphragm seal (see Figure 3.7).
• Correctly install the diaphragm seals on the high
and low pressure sides of the process, checking
the label on each seal.
• To avoid measuring error duets temperature
Stud bolt
difference between the two diaphragm seals,
Nut F0305.ai capillary tube must be bound together. The
Figure 3.5 EJ210 Mounting capillary tube must be securely fixed to the tank
wall to prevent movement by wind or vibration.
If the capillary tube is too long, loosely coil the
3.2.2 EJ118 and EJ438 extra tube portion (coil diameter of 300 mm or
Mount the diaphragm seals using the flanges as shown in more) and secure the coiled tube with a clamp.
Figure 3.6. The mating flange, gasket, bolts and nuts are
to be procured by the customer. Low
Flange
IMPORTANT pressure
Nut side
Bolt Diaphragm Install the sealed diaphragm
so that the shank positions
downward.
ød Minimum
High liquid level
Gasket
pressure
The product is side 50 mm minimum
shipped with these Correctly install the diaphragm
parts assembled. seals on the high and low pressure
sides of the process (The label on
each diaphragm seal is marked
HIGH or LOW). F0306.ai The transmitter should
be installed as low as
Figure 3.6 Mounting the Diaphragm Seals
possible below the
position where the high
pressure side
diaphragm seal is
installed.
F0307.ai
IM 01C25A01-01E
<3. Installation> 36
(P–P0) (–)
h= × 0.102 [mm]
ds
h≤0: Install the transmitter at least h (mm) below the Figure 3.8 Example of Installation to Tank
HP process connection (Caution on Installation)
h>0: Install the transmitter at most h (mm) above the
HP process connection
P: Pressure in the tank (Pa abs)
3.4 Mounting the Flushing
P0: Minimum working pressure limit of the transmitter (Pa
abs) See below table. Connection Ring
[For fill fluid code A, B, C, D, E]
Wetted parts Process connection size 3.4.1 Mounting to Pressure Detector
Capillary
material
length
code Section
code 2, 8 3 4,W
1 to 5m 6790 3190 The flushing connection ring is mounted to the pressure
SW
6 to 10m 10030 3520 detector section as shown in Figure 3.9.
1 to 5m 6790 3190
SE Pressure-detector section
6 to 10m 10030 3520
1 to 5m 3190
SY
6 to 10m 3520
1 to 5m 19150 6140 Ring
HW
6 to 10m 8290
1 to 5m 9620 3620
TW
6 to 10m 4210
1 to 5m 9540 4750 Spiral gasket
UW
6 to 10m 6050
Groove for
[For fill fluid code 1, 2, 4] installing Ring holder
spiral gasket
Wetted parts Process connection size
Capillary
material code View from pressure
length Vent/Drain plug
code 2, 8 3 4,W detector section
1 to 5m 2570 320
SW F0309.ai
6 to 10m 4680 530
1 to 5m 2570 320 Figure 3.9 Mounting to Pressure Detector Section
SE
6 to 10m 4680 530
1 to 5m 320 (1) Mount the ring holder on the ring and loosely tighten
SY
6 to 10m 530 the mounting screws.
1 to 5m 10220 2050
HW (2) Place the spiral gasket in the ring groove. With the
6 to 10m 3450
1 to 5m 4270 570 ring correctly aligned and flush with the face of the
TW
6 to 10m 960 pressure detector, securely tighten each ring holder’s
ds: Specific gravity of fill fluid (at 25°C). See below table. mounting screws.
(3) Position the ring so that the vent/drain plugs are
Fill fluid
A, 1, 4 B C, 2 D E aligned straight up and down.
code
ds: Specific 1.90 to
1.07 0.94 1.09 1.09
gravity 1.92
IM 01C25A01-01E
<3. Installation> 37
3.4.2 Mounting to Process Flange 3.5 Affixing the Teflon Film
Tighten the bolts to completely close the gap between the
ring and the pressure detector section. IMPORTANT
The mating flange, gasket, stud bolts and nuts are to
procured by the customer. The FEP Teflon option includes a teflon film and
fluorinated oil. Before mounting the transmitter to the
process flange, affix the teflon film as follows:
F0310.ai
Teflon film
Figure 3.10 Mounting to Process Flange PART No.
EJ210 F9347YD
2 inch EJ118
F9347YA
IMPORTANT EJ438
3 inch F9347XA
Fluorinated oil
• Confirm that there is no gap between the ring [PART No. : F9145YN]
and the process-detector section after they are Diaphragm
mounted on the process flange. A gap can lead to
a sudden, explosive release of process fluids. Gasket area
• When mounting or removing the ring, take care not F0311.ai
to tilt the pressure detector downward as the ring Figure 3.11 Affixing the Teflon Film
can slip off and cause injury.
• When re-mounting the ring, use the new spiral
gasket as shown in below table.
IM 01C25A01-01E
<3. Installation> 38
3.6 Rotating Transmitter Section 3.7 Changing the Direction of
The transmitter section can be rotated approximately Integral Indicator
360° and can be fixed at any angle within the above
range. (The direction of the rotation is depending on IMPORTANT
the configuration of the instrument.) Note that there is a
stopper which prevents the transmitter section from being Always turn OFF power, release pressure and
rotated more than 360°. remove a transmitter to non-hazardous area before
disassembling and reassmbling an indicator.
1) Remove the two setscrews that fasten the transmitter
section and capsule assembly, using the Allen
An integral indicator can be installed in the following
wrench.
three directions.
2) Rotate the transmitter section slowly and stop it at
designated position.
3) Tighten the two setscrews to a torque of 1.5 N·m.
WARNING
F0313.ai
In the case of the explosion-proof/flameproof type
transmitter, do not rotate the transmitter part in the Figure 3.13 Integral Indicator Direction
hazardous area while the transmitter is energized.
IMPORTANT
IMPORTANT The terminal box cover is locked by an Allen head
bolt (a shrouding bolt) on ATEX flameproof type
Do not rotate the transmitter section more than the transmitters. When the shrouding bolt is driven
above limit. clockwise by an Allen wrench, it is going in and cover
lock is released, and then the cover can be opened.
Vertical impulse piping type When a cover is closed it should be locked by a
shrouding bolt without fail. Tighten the shrouding bolt
Pressure-detector section to a torque of 0.7 N·m.
Stopper
1) Remove the cover.
2) While supporting the integral indicator with one hand,
loosen its two mounting screws.
3) Dismount the LCD board assembly from the CPU
assembly. When doing this, carefully pull the LCD
board assembly straight forward so as not to damage
Conduit connection
the connector pins between it and the CPU assembly.
Transmitter section 4) After rotating the LCD, align both the LCD board
assembly and CPU assembly connectors and engage
Horizontal impulse piping type them.
5) Insert and tighten the two mounting screws.
Transmitter section 6) Replace the cover.
CPU assembly
Integral 90°
Conduit connection indicator 90°
Zero-adjustment screw
IM 01C25A01-01E
<4. Installing Impulse Piping> 39
(1) Check the High and Low Pressure (4) Removing the Impulse Piping Connecting
Connections on the Transmitter (Figure 4.1) Port Dustproof Cap
Symbols “H” and “L” have been placed on the capsule The impulse piping connecting port on the transmitter
assembly to indicate high and low pressure side. With may be covered with a plastic cap to keep out dust. This
differential pressure transmitters, connect the high cap must be removed before connecting the line. (Be
pressure side impulse line to the “H” side, and the low careful not to damage the threads when removing this
pressure side impulse line to the “L” side. cap. Never insert a screwdriver or other tool between the
With gauge/absolute pressure transmitters, connect the cap and port threads to remove the cap.)
impulse line to the ‘H’ side.
(5) Connecting the Transmitter and 3-Valve
Differential Pressure Transmitter
Manifold (for differential pressure
“H” and “L” are shown transmitters)
Process
connection Process connection A 3-valve manifold consists of two stop valves to block
Process connector
process pressure and an equalizing valve to equalize
the pressures on the high and low pressure sides of the
Bolt F0401.ai transmitter. Such a manifold makes it easier to disconnect
Figure 4.1 “H” and “L” Symbols on a Capsule the transmitter from the impulse piping, and is convenient
Assembly when adjusting the transmitter zero point.
There are two 3-valve manifold typs: the pipe-mounting
(2) Changing the Process Connector Piping type and the direct-mounting type; care should be taken
Connections (for differential pressure with respect to the following points when connecting the
transmitters) manifold to the transmitter.
The impulse piping connection distances can be changed
between 51 mm, 54 mm and 57 mm by changing the
orientation of the process connectors.
This is convenient for aligning the impulse line with a
process connectors.
57 mm 54 mm 51 mm
F0402.ai
IM 01C25A01-01E
<4. Installing Impulse Piping> 40
Pipe-Mounting Type 3-Valve Manifold Direct-Mounting Type 3-Valve Manifold
1) Mount the 3-valve manifold on the transmitter. (When
Impulse piping mounting, use the two gaskets and the four bolts
Nipple
Vent plug
provided with the 3-valve manifold. Tighten the bolts
3-valve
(optional) manifold
evenly.)
Ball head 2) Mount the process connectors and gaskets on the top
Stop valve lock nut
of the 3-valve manifold (the side on which the impulse
(low pressure side)
piping will be connected.)
Pipe
Equalizing valve Pipes
Bolts Impulse
(balancing)
piping
Ball head Process Stop valve
lock nut connector 3-valve
Stop valve manifold
Gasket Equalizing
(high pressure side) Nipple valve
50 mm(2-inch) pipe Process
Process connector Stop valve
connector bolts
F0403.ai
IM 01C25A01-01E
<4. Installing Impulse Piping> 41
4.1.2 Routing the Impulse Piping (4) Temperature Difference Between Impulse
Piping (for differential pressure
(1) Process Pressure Tap Angles transmitters)
If condensate, gas, sediment or other extraneous If there is a temperature difference between the high
material in the process piping gets into the impulse and low impulse lines, the density difference of the fluids
piping, pressure measurement errors may result. To in the two lines will cause an error in the measurement
prevent such problems, the process pressure taps must pressure. When measuring flow, impulse lines must be
be angled as shown in Figure 4.5 according to the kind of routed together so that there is no temperature difference
fluid being measured. between them.
IM 01C25A01-01E
<4. Installing Impulse Piping> 42
4.2 Impulse Piping Connection Liquid Gas Steam
Tee
Figure 4.9 Manifold and Flow Direction Indication
Drain valve
Drain plug
Pipe (opened to atmosphere
at low pressure side) F0407.ai
NOTE
Process piping
• If the process fluid is a gas, then as a rule the F0410.ai
manifold must be located at the downside of the Figure 4.10 Process Piping Connection Examples
pressure-sensing assembly. (EJ115)
• If the process fluid is a liquid, then as a rule the
manifold must be located at the upside of the
pressure-sensing assembly.
IM 01C25A01-01E
<5. Wiring> 44
5. Wiring
5.2 Connections of External
NOTE
Wiring to Terminal Box
For FOUNDATION Fieldbus, PROFIBUS PA, and Mod
bus communication types, please refer to each ● Terminal Configuration
communication manual.
RTD cable connection*
IMPORTANT
Terminal 4 [B]*
• Lay wiring as far as possible from electrical noise
sources such as large capacity transformers,
motors, and power supplies. Terminal 1 Terminal 3 [A]
• Remove electrical connection dust cap before Terminal 2
wiring.
• All threaded parts must be treated with *For EJX9A only. F0527.ai
SUPPLY +
1
– Power supply and output terminals
2
Figure 5.1 Shrouding Bolt
CHECK +
3
External indicator (ammeter) terminals *1*2
– 2
Ground terminal
*1: When using an external indicator or check meter, the
internal resistance must be 10Ω or less.
*2: Not available for FOUNDATION Fieldbus communication
type.
F0528.ai
IM 01C25A01-01E
<5. Wiring> 45
5.2.1 Power Supply Wiring Connection 5.2.3 Status Output Connection
When option code /AL is specified, connect the external
IMPORTANT wiring as shown in Figure 5.7.
To configure and activate the process alarm function and
Connecting with the commercial AC power supply
status output, it is necessary to set some parameters.
will damage the device. Be sure to use the DC power
Refer to each communication manual for procedures.
supply in the predetermined range.
Transmitter
24V DC
terminal box Shielded cable
Connect the power supply wiring to the SUPPLY + and – +
Distributor
terminals. – 250Ω
■ 1 to 5 V output, HART
Connect the HART communicator or configuration tool to
the SUPPLY - and VOUT (+) terminals. (Use hooks.)
PC/FieldMate F0532.ai
IM 01C25A01-01E
<5. Wiring> 46
5.2.4 Connection Example for EJX910A and EJX930A
Table 5.1 The connection example for simultaneous analog and pulse and alarm, status output. (For HART protocol type)
Connection Description
Analog Output Transmitter Electrical Terminal
Distributor
In this case, + 24V DC
Communication is SUPPLY +
possible (up to a distance – 250Ω
of 2km when a CEV cable –
is used.) PULSE B* * Either B or +
Pulse Output Transmitter Electrical Terminal Use the Three-wire shielded cable.
Shielded Cable
In this case,
No communication is SUPPLY + E
possible.
–
* *1
PULSE B *2 R Electric counter
* Either B or +
When analog and pulse output are used, the length of communication line is subjected to wiring conditions. Refer to
Simultaneous example 1 to 3.
Distributor (or communication medium : ex. EP card)
Analog
For the shielded cables in this example of
-Pulse Output *3 Shielded Cable
24V DC
flowmeter installation, use two-wire separately
Example 1 SUPPLY + shielded cables.
In this case, Communica – *2 R 250Ω
-tion is possible(up to a * E(10.5 to 30V DC) This supply voltage requires a power sourse
distance of 2km when a
PULSE B Counting input with a maximum output current of no less than
CEV cable is used). * Either B or + Common E/R.
Electric counter *1 (or communication medium : ex. EP card)
Transmitter Electrical Terminal
For the shielded cables in this
Example 2 Recorder or
example of flowmeter installation,
In this case, Communica Shielded Cable other instrument
use two-wire separately shielded
-tion is possible (up to a 250Ω cables.
distance of 200m when a
SUPPLY + *2
E(16.4 to 30V DC)
This supply voltage requires a power
CEV cable is used) and R
= 1kΩ). – R
Counting input sourse with a maximum output current
PULSE * of no less than E/R+25mA.
B Common
The supply voltage requires output
* Either B or +
Electric counter *1 impedance no more than 1/1000 of R
Transmitter Electrical Terminal (load resistance).
Recorder or
other instrument
Example 3 250Ω
In this case, No communi
-cation is possible (when SUPPLY + E(16.4 to 30V DC) This supply voltage requires
R*2 a power sourse with a
shielded cable is not used). – Counting input maximum output current of
* no less than E/R+25mA.
PULSE B Common
* Either B or + Electric counter *1
Transmitter Electrical Terminal
IM 01C25A01-01E
<5. Wiring> 47
5.2.5 External Temperature Connection • Pulse output and Alarm, Status Output or
(for EJX910A and EJX930A) Simultaneous Analog-Pulse Output
Connect the RTD cable assembly to the Juck Terminal. (for EJX910A and EJX930A)
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
F0505.ai
instrument
Figure 5.8 External Temperature Connection
5.3 Wiring
Receiver
5.3.1 Loop Configuration instrument
F0506.ai
(3) Intrinsically Safe Type (for EJX910A and
Figure 5.9 Connection between Transmitter and EJX930A)
Distributor
• Analog Output
Hazardous Location Nonhazardous Location
Power
supply
Anaolg input
F0509.ai
IM 01C25A01-01E
<5. Wiring> 48
• Simultaneous Analog-Pulse Output • Four wire connection
Fasten the negative side wiring of both power supply
Hazardous Location Nonhazardous Location
and signal line to the SUPPLY - terminal.
Transmitter terminal box I/O module Hazardous Location Nonhazardous Location
Safety barrier
(Isolated type)
Transmitter terminal box
Distributor
Power (Power supply unit)
supply
Analog input
Power
supply
Receiver
Pulse input instrument
Safety barrier
(Isolated type)
F0510.ai F0530.ai
Figure 5.12 Connection between Transmitter, Figure 5.14 Connection between Transmitter,
barrier and receiver Distributor and Receiver
With three wire connection, the cable length may • Apply a non-hardening sealant to the terminal box
affect the measurement accuracy of the output signal. connection port and to the threads on the flexible
In either three-wire or four-wire connection, metal conduit for waterproofing.
recommended wiring distance is 200 m or less, and
the use of shielded cable is recommended.
Receiver
instrument
F0529.ai
IM 01C25A01-01E
<5. Wiring> 49
(2) Flameproof Type • RTD connection components: EJX multivariable
transmitter, two cable glands, and RTD cable.
Wire cables through a flameproof packing adapter, or use
Two cable glands are attached.
a flameproof metal conduit.
Electrical connection
Wiring cable through flameproof packing adapter.
• Apply a non-hardening sealant to the terminal box Cable gland
connection port and to the threads on the flameproof
packing adapter for waterproofing. RTD cable
with connector
Drain plug
F0512.ai
IM 01C25A01-01E
<5. Wiring> 50
Procedure (7) Rotate the running coupler another half turn to
securely tighten the seal on the RTD cable.
(1) Disassemble the cable gland: loosen the running
coupler to separate the backnut from the entry. (8) Use a protection conduit, if necessary.
(2) Remove the protection cap over the transmitter In this case, insert the cable through the conduit and
electrical connection and install the entry on the attach it to the Backnut.
electrical connection. Note that a non-hardening
sealant should be applied to the threads for a 1/2 NPT CAUTION
connection and a gasket should be used for an M20
connection. After the cable is secured as explained above, do not
tighten the running coupler any further; to do so could
damage the RTD connection.
Do not pull the cable or subject it to excessive
mechanical shock.
F0518.ai
(4) Insert the RTD cable and firmly plug its connector into
the connecting port in the transmitter's terminal box.
F0522.ai
Procedure
(1) Remove the protection cap protecting the RTD
electrical connection and insert the RTD cable.
F0519.ai
F0523.ai
CAUTION
Do not pull the cable or subject it to excessive
mechanical shock.
F0521.ai
IM 01C25A01-01E
<5. Wiring> 51
5.4.3 Cable Connection RTD Terminal Box 5.5 Grounding
Side
Grounding is always required for the proper operation of
EJX multivariable transmitter RTD I/F is for 3-wire Type transmitters. Follow the domestic electrical requirements
RTD, Pt100. as regulated in each country. For a transmitter with a
Heed the following when wiring an RTD of the 2- or 4-wire built-in lightning protector, grounding should satisfy
type. ground resistance of 10Ω or less.
Ground terminals are located on the inside and outside of
NOTE the terminal box. Either of these terminals may be used.
600
A B A B b Aa B b
F0524.ai
External E–10.5
R= Communication
Figure 5.18 The Method of Wiring for the RTD Side load 0.0244
applicable range
resistance BRAIN and HART
R (Ω)
Table 5.2 The Method of Wiring for the RTD Side
RTD Terminal
250
RTD Terminal A a B b
2-Wire White - Blue1 and Blue2 -
3-Wire White - Blue1 Blue2
4-Wire White open Blue1 Blue2
0 10.5 16.6 25.2 42
Power supply voltage E (V DC)
F0526.ai
IM 01C25A01-01E
<6. Operation> 52
6. Operation
NOTE Burnout direction switch
Burnout Direction H L H L
6.1 Preparation for Starting Switch Position
Self-diagnostic error
on the integral indicator
(Faulty transmitter) 6.2 Zero Point Adjustment
After completing preparations for operating the
F0601.ai
transmitter, adjust the zero point.
Verify and Change Transmitter Zero point adjustment can be done by turning the
transmitter’s zero-adjustment screw or by using the
Parameter Setting and Values
communicator. This section describes the procedure
The parameters related to the following items are set at for the zero-adjustment screw. For the zero-adjustment
factory as specified in order. via communication, procedure, please refer to each
• Calibration range communication manual.
• Integral indicator display
• Output mode IMPORTANT
• Software damping (optional)
Other parameters like following are shipped with the Do not turn off the power to the transmitter
default setting. immediately after performing a zero point adjustment.
• Low-cut Powering off within 30 seconds of performing this
• Process alarm setting procedure will return the zero point to its previous
• Static pressure range setting.
• Signal characterizer
• Write protection
To confirm or change the values, please refer to each 6.2.1 Adjusting Zero Point for Differential
communication manual. Pressure Transmitters
Before adjusting zero point, make sure that the equalizing
Output Status Setting at CPU Failure and valve is open.
Hardware Write Protection
Set the switches as shown in the figure below to set the
burn-out direction and write protection. The Burnout
switch is set to the H side for delivery (unless option code
/C1 or /C2 is specified in the order), and the hardware Zero-adjustment screw cover
write protection switch is set to E side except EJX910A F0603.ai
and EJX930A. The setting of the switches can be Figure 6.2 External Zero Adjustment Screw
confirmed via communication.
IM 01C25A01-01E
<6. Operation> 53
The zero-adjustment screw is located inside the cover. 6.3 Local Parameter Setting
Use a slotted screwdriver to turn the zero-adjustment
screw. Equalize the transmitter, then turn the screw
clockwise to increase the output or counterclockwise to WARNING
decrease the output. The zero point adjustment can be
made with a resolution of 0.01% of the setting range. The The local push button on the integral indicator must
degree of zero adjustments varies with the screw turning not be used in a hazardous area. When it is necessary
speed; turn the screw slowly to make a fine adjustment, to use the push button, operate it in a non- hazardous
quickly to make a rough adjustment. location.
[Example]
Integral indicator
The measuring range of 50 to 250 kPa; the actual
measured value of 130 kPa.
130–50
Actual measured value= x100=40.0%
250–50
(=10.4mA) Push-button
F0605.ai
Turn the screw to match the output signal to the actual Figure 6.4 Range –Setting Switch (push button)
measured value.
IM 01C25A01-01E
<6. Operation> 54
screw
Process
Measurement Zero adjustment
Display push
Activate LPS mode
push
***
1. Loop Test Select Output Current Run/Cancel
*
2. Tag Number Edit Tag number Save/Cancel the value
push *
3. Press Unit Select Press unit Save/Cancel the value
*
4. Press LRV Edit Press LRV Save/Cancel the value
push *
5. Press URV Edit Press URV Save/Cancel the value
*
6. Damping Time Edit Damping time Save/Cancel the value
push *
7. Output Mode Select Output mode Save/Cancel the value
*
8. Display Out1 Edit Display Out1 Save/Cancel the value
push
9. LRV-Apply Press Set LRV Save/Cancel the value
Process
Measurement
Display
F0606.ai
*: These parameter configurations are available with the software revision (SOFT REV)2.03 or later.
Software revision can be checked via a field communicator (HART/BRAIN) or DTM. Please refer to IM 01C25T01 for HART
parameter “Software rev” and IM 01C25T03 for BRAIN “SOFT REV.”
**: This paratmeter configuration is available with the softeware revision (SOFT REV) 3.01 or later.
***: This paratmeter configuration is available with the softeware revision (SOFT REV) 5.01 or later.
IM 01C25A01-01E
<7. Errors and Countermeasures> 55
The table below shows a summary of error messages for BRAIN and HART (protocol revision 5) protocols.
IM 01C25A01-01E
<7. Errors and Countermeasures> 56
Table 7.2 Alarm Message Summary (For EJX910A and EJX930A, HART protocol type)
Integral 4-20mA Output
Cause Countermeasure
indicator operation during error
AL. 01 Sensor problem. Outputs the signal (High or Low) set Replace capsule if the error recurs
CAP.ERR with burnout direction switch. after the transmitter is restarted.
Capsule temperature sensor problem. [status output: undefined] Replace capsule.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor problem. Replace amplifier.
AMP.ERR Amplifier EEPROM problem.
Amplifier problem.
A/D Converter problem.
AL. 03 External temperature sensor Check external temperature sensor.
ET.ERR disconnection.
— No device ID is found. Continues to operate and output. Replace amplifier.
AL. 10 Differential pressure is outside When PV is Pres Check input or replace capsule when
PRESS measurement range limit of capsule. Output AO upper limit or AO Lower necessary.
limit.
AL. 11 Static pressure exceeds limit. When PV is SP
ST. PRSS Output AO upper limit or AO Lower
limit.
AL. 12 Capsule temperature is outside range Continues to operate and output. Use heat insulation or make lagging
CAP.TMP (–50 to 130°C). to keep temperature within range.
AL. 13 Amplifier temperature is outside range
AMP.TMP (–50 to 95°C).
AL. 14 External temperature is outside range. When PV is ET
EXT. TMP Output AO upper limit or AO Lower
AL. 15 External temperature sensor resistance limit.
EXT. TMP is out specification.
AL. 16 PLS Pulse output is out specification. Continues to operate and output. Check settings and change them.
AL. 30 Differential pressure exceeds specified When PV is Pres. Check input and range setting, and
PRS.RNG range. Output AO upper limit or lower limit. change them as needed.
AL. 31 Static pressure exceeds specified When PV is SP
SP. RNG range. Output AO upper limit or lower limit.
AL. 32 Flow exceeds specified range. When PV is Flow
F. RNG Output AO upper limit or lower limit.
AL. 33 External temperature exceeds specified When PV is ET
ET. RNG range. Output AO upper limit or lower limit.
AL. 35 P.HI Input pressure exceeds specified Continues to operate and output. Check input.
AL. 36 P.LO threshold.
AL. 37 SP.HI Input static pressure exceeds specified
AL. 38 SP.LO threshold.
AL. 41 F.HI Input flow exceeds specified threshold.
AL. 42 F.LO
AL. 43 ET.HI Input external temperature exceeds
AL. 44 ET.LO specified threshold.
AL. 50 P. LRV Specified value is outside of setting Holds at the output value that existed Check settings and change them as
AL. 51 P. URV range. immediately before the error occurred. needed.
AL. 52 P. SPN
AL. 53 P. ADJ Continues to operate and output. Adjust settings and change them as
needed.
AL. 54 Holds at the output value that existed Check settings and change them as
SP. RNG immediately before the error occurred. needed.
AL. 55 Continues to operate and output. Adjust settings and change them as
SP. ADJ needed.
AL. 56 Holds at the output value that existed Check settings and change them as
ET. RNG immediately before the error occurred. needed.
AL. 57 Continues to operate and output. Adjust settings and change them as
ET. ADJ needed.
AL. 58 Holds at the output value that existed Check settings and change them as
FL. ADJ immediately before the error occurred. needed.
AL. 59 Specified value is outside of setting Normal calculation.
PLS.ADJ pulse output.
— Under Temperature Fix Mode. PV is ET Temp. Output Fix at 4mA. Leave from Temperature Fix Mode.
IM 01C25A01-01E
<7. Errors and Countermeasures> 57
Integral 4-20mA Output
Cause Countermeasure
indicator operation during error
AL. 79 Displayed value exceeds limit. Continues to operate and output. Check settings and change them as
OV. DISP needed.
AL.87 Flange temperature exceeds a preset It depends on the Diag Out Option Check the heater failure.
FLG. HI upper limit. setting.
AL.87 Flange temperature is below a preset Check the capsule temp. and
FLG. LO lower limit. Off: Continue to operate and output. Amplifier temp.
Burnout:Outputs AO upper limit or AO
lower limit. Adjust Flg Temp Coef.
Fall back:Outputs Diag Out Fixed Val.
AL.88 Differential pressure/pressure Continue to operate and output. Check process condition.
INVR.DP fluctuation does not reach the reference
level required to blockage detection so
that no blockage detection is carried
out.
AL.88 Low-pressure-side fluctuation does not
INVR.SL reach the reference fluctuation level
required to blockage detection.
AL.88 High-pressure-side fluctuation does not
INVR.SH reach the reference fluctuation level
required to blockage detection.
AL.88 BlkF can not be used for blockage
INVR.F detection for some reasons.
AL.89 Appointed the diagnosis range outside.
ILBD.OV
AL.89 B Blocking (both-side blockage) is It depends on the Diag Out Option Check process condition.
B BLK detected. setting.
AL.89 High-pressure-side blockage is
H BLK detected. Off: Continue to operate and output.
Burnout: Outputs AO upper limit or AO
AL.89 Low-pressure-side blockage is
lower limit.
L BLK detected.
Fall back: Outputs Diag Out Fixed Val.
AL.89 Pressure fluctuation amplitude of high-
H LRG pressure side is large.
AL.89 Pressure fluctuation amplitude of low-
L LRG pressure side is large.
AL.89 A Blocking (single-side blockage) is
A BLK detected.
AL. 90 SIM Under Simulation Mode for flow. Simulate input output. Check Simulation Mode.
AL. 91 F. SIM Under Simulation Mode for device Output the setting value of Simulate- Check Simulation Mode.
AL. 91 P. SIM variables. Value.
AL.91 SP. SIM
AL. 91
ET. SIM
AL. 91
TF. SIM
AL. 91
PCT. SIM
AL. 91
AO. SIM
IM 01C25A01-01E
58
Revision Information
Title : EJX and EJA-E Series
Differential Pressure and Pressure Transmitters Installation Manual
Manual No. : IM 01C25A01-01E
IM 01C25A01-01E
59
IM 01C25A01-01E