Följande är en preliminär larmlista för att underlätta felsökning på fält.

De
1650-1 värden som står inom parantes är informationsmeddelande och inte per-
manenta larm, vissa av dessa resulterar i permanent larm om de återkom-
LARMLISTA F2120 mer. Vid larm från F2120 så visas systemets larmnummer i SMO eller VVM
men även ett unikt värde för F2120 inom parantes i larminformationen, det
visas i kolumn två i tabellen nedan.

Alarm number Alarm number Alarm text Description Possible cause


VVM/SMO F2120 permanent alarm
(info message) (info message)
(56) (205) Wrong serial Display unit have Wrong software in
number a non-valid serial outdoor unit, non-
number stored compatible outdoor
unit

156 (157) 80 (81) Low pressure in 5 repeated low Bad circulation in


cooling mode, BP8 pressure alarms in climate system
4hrs
(162) (69) High condenser out Normal in certain
operation modes,
bad flow, wrong
menu settings

(163) (65) High condenser in Normal in certain


operation modes,
bad flow, wrong
menu settings

224 182 Fan alarm 5 failed starts Fan blocked or not


connected, bad con-
nections
225 8 Mixed flow and Condensor in Flow and return
return sensor is warmer than pipes are mixed,
condenser out charge pump not
correctly installed
227 34 Sensor fault Sensor fault BT3 Bad connection
36 Sensor fault BT12 or short circuit in
38 Sensor fault BT14 sensor
40 Sensor fault BT15
42 Sensor fault BT16
44 Sensor fault BT17
46 Sensor fault BT28
48 Sensor fault BT81
50 Sensor fault BP8
52 Sensor fault BP9
54 Sensor fault BP11
56 Sensor fault BT84
228 2 Failed defrost Defrost could not System temperature
finish 10 times in a is to low and/or
row bad circulation,
high wind impact,
problem in
refrigerant circuit

NIBE Energy Systems Box 14, 285 21 Markaryd. www.nibe.se

1
Följande är en preliminär larmlista för att underlätta felsökning på fält. De
1650-1 värden som står inom parantes är informationsmeddelande och inte per-
manenta larm, vissa av dessa resulterar i permanent larm om de återkom-
LARMLISTA F2120 mer. Vid larm från F2120 så visas systemets larmnummer i SMO eller VVM
men även ett unikt värde för F2120 inom parantes i larminformationen, det
visas i kolumn två i tabellen nedan.

Alarm number Alarm number Alarm text Description Possible cause


VVM/SMO F2120 permanent alarm
(info message) (info message)
229 4 Short operation Compressor active Bad circulation or
times less than 5 minutes wrong settings in
3 times in a row VVM/SMO

230 78 Hot gas alarm 3 repeated alarms Low refrigerant


within 4hrs amount, defect
expansion valve,
defect compressor
232 76 Low evaporation 5 repeated alarms High wind impact,
temperature alarm within 4hrs defect evaporator
sensor, refrigeration
leak, defect
expansion valve
264 204 Communication 5 repeated alarms Inverter without
error towards within 4hrs. voltage, bad
inverter connection between
inverter and base
card
(271) (63) Low outdoor temp Outdoor temperatu-
heating re outside working
(87) Low outdoor temp envelope, defect
cooling outdoor sensor
(272) (61) High outdoor temp Outdoor temperatu-
heating re outside working
(85) High outdoor temp envelope, defect
cooling outdoor sensor
341 6 Safety defrost 10 Safety defrost in Bad airflow through
a row the evaporator,
high wind impact,
refrigeration issue
(342) (67) Low condenser in, Low system tempe-
cooling mode rature, bad circula-
tion, defect return
sensor
(343) (71) Low condenser out, Low system
cooling mode temperature, bad
circulation, defect
flow sensor
344 (345) 72 (73) Low pressure BP8 under working High wind impact,
limit, 5 repeated refrigeration issue,
alarms within 4hrs defect expansion
valve

NIBE Energy Systems Box 14, 285 21 Markaryd. www.nibe.se

2
Följande är en preliminär larmlista för att underlätta felsökning på fält. De
1650-1 värden som står inom parantes är informationsmeddelande och inte per-
manenta larm, vissa av dessa resulterar i permanent larm om de återkom-
LARMLISTA F2120 mer. Vid larm från F2120 så visas systemets larmnummer i SMO eller VVM
men även ett unikt värde för F2120 inom parantes i larminformationen, det
visas i kolumn två i tabellen nedan.

Alarm number Alarm number Alarm text Description Possible cause


VVM/SMO F2120 permanent alarm
(info message) (info message)
346 (347) 74 (75) High Pressure BP9 above working Bad circulation,
limit, 5 repeated defect expansion
alarms within 4hrs valve
400 (401) 207 Inverter alarm inverter initiation
error
209 Inverter not Wrong inverter
compatible model
211 Missing Wrong inverter
configuration file model
213 Configuration load
error
421 (420) 104 (103) Communication er- Communication Bad connection
ror between inver- error with AA2, 3
ter and bas card times repeated in
2hrs
425 (424) 108 (107) HP/LP switch alarm 2 repeated LP/HP Bad circulation, high
switch alarms within wind impact, defrost
2,5hrs problems, refrigera-
tion issue
429 (428) 112 (111) Inverter protection Temporary alarm Multiple
mode (MCE fault) message from inver- simultaneous other
ter 3 times in 2hrs alarms
431 (430) 114 (113) Over voltage Voltage to high to High voltage input
inverter 3 times in into F2120.
2hrs or continuous
for 1 hr
433 (432) 116 (115) Under voltage Voltage to low, Low or interrupted
under 180V, to voltage into F2120.
inverter 3 times in
2hrs or continuous
for 1 hr
435 (434) 118 (117) Phase loss One compressor At least one phase
phase has been missing into F2120
missing 3 times in
2hrs or continuous
for 1hr
437 (436) 120 (119) Over current Internal overcurrent High current into
protection tripped the inverter, external
(1x230V products) 3 short circuit
times in 2hrs

NIBE Energy Systems Box 14, 285 21 Markaryd. www.nibe.se

3
Följande är en preliminär larmlista för att underlätta felsökning på fält. De
1650-1 värden som står inom parantes är informationsmeddelande och inte per-
manenta larm, vissa av dessa resulterar i permanent larm om de återkom-
LARMLISTA F2120 mer. Vid larm från F2120 så visas systemets larmnummer i SMO eller VVM
men även ett unikt värde för F2120 inom parantes i larminformationen, det
visas i kolumn två i tabellen nedan.

Alarm number Alarm number Alarm text Description Possible cause


VVM/SMO F2120 permanent alarm
(info message) (info message)
439 (438) 122 (121) High inverter Inverter temporary Bad circulation, bad
temperature over max working heat transfer bet-
temperature 3 times ween inverter and
in 2hrs cooling plate
441 (440) 124 (123) Over current High current to the High current into
inverter 3 times in the inverter, external
2 hrs short circuit
443 (442) 126 (125) High inverter Inverter temporary Bad circulation, bad
temperature over max working heat transfer bet-
temperature 3 times ween inverter and
in 2hrs cooling plate
445 (444) 128 (127) Inverter protection Temporary inverter Disturbance in vol-
mode (Gate Kill) stop 3 times in 2 hrs tage to inverter, bad
connection, defect
EMC (TDI), defect
compressor
447 (446) 130 (129) Phase loss One compressor Disturbance in
compressor phase has been voltage to inverter,
missing 3 times in failed start trial of
2 hrs or continuous compressor
for 1hr
449 (448) 132 (131) Low compressor Compressorspeed Disturbance in
speed has been below the voltage to inverter,
operating window 3 failed start trial of
times in 2hrs compressor
453 (452) 136 (135) Over current Current from the Disturbance in
compressor inverter to the com- voltage to F2120.
pressor has been
too high, 3 times in
2hrs
455 (454) 138 (137) High power to the Power from the Disturbance in
compressor inverter to the com- voltage to F2120.
pressor has been
too high, 3 times in
2hrs
467 (466) 140 (139) Under voltage Incoming voltage Incoming voltage
too low too low to the
F2120 (1x230V
products).
501 (500) 184 (183) Failed compressor Wrong pressure Refrigeration issues,
start difference between defect pressure
BP8 and BP9 at sensors
start-up

NIBE Energy Systems Box 14, 285 21 Markaryd. www.nibe.se

4
Följande är en preliminär larmlista för att underlätta felsökning på fält. De
1650-1 värden som står inom parantes är informationsmeddelande och inte per-
manenta larm, vissa av dessa resulterar i permanent larm om de återkom-
LARMLISTA F2120 mer. Vid larm från F2120 så visas systemets larmnummer i SMO eller VVM
men även ett unikt värde för F2120 inom parantes i larminformationen, det
visas i kolumn två i tabellen nedan.

Alarm number Alarm number Alarm text Description Possible cause


VVM/SMO F2120 permanent alarm
(info message) (info message)
503 (502) 186 (185) Low compressor Compressor been Low voltage,
speed running below its compressor limits
operating window 3 active
times in 2hrs