Professional Documents
Culture Documents
NOTE
The purpose of the stack and breeching is to A round breeching is preferred over a square or
conduct the products of combustion safely to the rectangular breeching and stack.
atmosphere. In addition a well designed stack
will provide sufficient draft to overcome friction
losses in the breeching and stack. Insulating the breeching will help to minimize
flue gas condensation which may result in
Considerations excessive corrosion. In addition the higher
resultant stack temperature will aid in increasing
On individual units, a direct vertical connection the available draft.
off the flue gas outlet of the boiler (it is preferable
to support the stack/breeching independent from STACKS
the boiler) or a horizontal offset connection may
be utilized. Construction AND Installation of the Stack
See Figure 1. shall be in conformance with national, regional
and local codes and standards and/or
In the case of multiple boilers, it is always better appropriate legislation.
to utilize a separate stack for each boiler. If this is
not practical, See Figure 2 for a Typical Multiple The following types of chimneys are suitable for
Boiler Installation with Common Breeching. use with boilers as supplied by Boilersmith Ltd.
A rain cap or hood should be used at the top of the For single boiler installations the Suggested
stack to minimize the entrance of rain or snow. Minimum Breeching Size and Boiler Outlet
See Figure 4. Diameters for Boilersmith Ltd. boilers is shown in
Chart 2. It is generally recommended that the
The top of every chimney shall be at least 3 ft stack size selected be larger than the breeching
above the highest point at which it comes in diameter and should not be selected smaller than
contact with the roof, and 2 ft above a roof surface the flue gas outlet supplied with the boiler.
or structure with a horizontal distance of 10 ft
from the chimney. See Figure 5.
EQUIVALENT DIAMETERS OF BREECHING
FOR MULTIPLE BOILER INSTALLATIONS
Required Equivalent Diameter of Breeching
Diameter to maintain approximately the same
(inches) flue gas velocity for one to five
boilers (in inches)
6 8 10 12 14
8 12 14 16 18
9 13 16 18 20
10 14 18 20 22
12 16 20 24 26
13 18 22 26 30
14 20 24 28 32
16 22 28 32 36
18 26 32 36 40
20 28 34 40 44
22 32 38 44 50
24 34 42 48 54
26 36 44 52 58
28 40 48 56 62
30 42 52 60 68
32 45 56 64 72
CHART 1
< 20 6 8
25- 30 8 8
30 8 10
40- 45 10 10
50- 60 10 12
65- 80 12 12
90-125 14 14
135-155 16 18
160-200 18 24
215-255 20 24
275-300 22 30
315-350 24 30
360 26 30
380-400 26 36
420-450 28 36
500-515 30 42
550-600 32 42
CHART 2