You are on page 1of 6

APPENDIX "B"

November 5, 2002 Page 1 of 6


BOILERSMITH LTD.
STACKS AND BREECHING

NOTE

The Stack and Breeching shall be installed in


conformance with national, regional and local The Breeching should be as short and straight as
codes and standards and/or appropriate possible without excessive bends to minimize
legislation. flow resistance.

The purpose of the stack and breeching is to A round breeching is preferred over a square or
conduct the products of combustion safely to the rectangular breeching and stack.
atmosphere. In addition a well designed stack
will provide sufficient draft to overcome friction
losses in the breeching and stack. Insulating the breeching will help to minimize
flue gas condensation which may result in
Considerations excessive corrosion. In addition the higher
resultant stack temperature will aid in increasing
On individual units, a direct vertical connection the available draft.
off the flue gas outlet of the boiler (it is preferable
to support the stack/breeching independent from STACKS
the boiler) or a horizontal offset connection may
be utilized. Construction AND Installation of the Stack
See Figure 1. shall be in conformance with national, regional
and local codes and standards and/or
In the case of multiple boilers, it is always better appropriate legislation.
to utilize a separate stack for each boiler. If this is
not practical, See Figure 2 for a Typical Multiple The following types of chimneys are suitable for
Boiler Installation with Common Breeching. use with boilers as supplied by Boilersmith Ltd.

BREECHING - Rectangular Brick Masonry


Chimneys
Installation AND Construction of the - Radial Brick Masonry Chimneys
Breeching shall be in conformance with - Reinforced Concrete Chimneys
national, regional and local codes and - Metal Chimneys
standards and/or appropriate legislation. - Factory-Built, Type A Chimneys
- Factory-Built Pressure Fired
Changes in breeching direction, shape and flow Chimneys
area must be accomplished separately and as
gradually as possible to eliminate turbulence Factory-Built, Type B, L or Class 1 BH for
which may adversely affect burner performance. NATURAL GAS FIRED APPLIANCES
See Figure 3. ONLY may be used if the flue gas temperature
is less than 500oF and a negative pressure exists
at the flue gas outlet vent of the boiler.
APPENDIX "B"

November 5, 2002 Page 2 of 6


BOILERSMITH LTD.
STACKS AND BREECHING

Installation of the Stack shall be in


conformance with national, regional and local
The walls of any chimney, gas vent or flue pipe codes and standards and/or appropriate
shall be constructed to be gas-, smoke- and flame- legislation.
tight.
The stack should be higher than nearby structures
A round stack is preferred over square stack. or geographical prominence since they could
create down drafts or eddy current.
Every chimney shall be capable of providing
sufficient draft to vent properly the appliances SIZING BREECHING AND STACK
that it serves.
A Breeching and stack should be sized on the
The cross-sectional area of the flue pipe shall not basis of maintaining a flue gas flow of 30 ft/sec or
be less than the area of the flue outlet of the less with the boiler operating at maximum
appliance, except that a tapered reduction in the capacity.
section of the flue adjacent to the chimney is
permitted provided adequate draft is maintained. In the case of a multiple boiler installation
utilizing a common stack and breeching, the
Insulating the stack will help to minimize flue gas breeching should be sized to maintain a constant
condensation which may result in excessive velocity of flow. The Equivalent Diameters of
corrosion. In addition the higher resultant stack Breeching for Multiple Boiler Installations to
temperature will aid in increasing the available maintain a constant velocity of flow are shown in
draft. Chart 1.

A rain cap or hood should be used at the top of the For single boiler installations the Suggested
stack to minimize the entrance of rain or snow. Minimum Breeching Size and Boiler Outlet
See Figure 4. Diameters for Boilersmith Ltd. boilers is shown in
Chart 2. It is generally recommended that the
The top of every chimney shall be at least 3 ft stack size selected be larger than the breeching
above the highest point at which it comes in diameter and should not be selected smaller than
contact with the roof, and 2 ft above a roof surface the flue gas outlet supplied with the boiler.
or structure with a horizontal distance of 10 ft
from the chimney. See Figure 5.
EQUIVALENT DIAMETERS OF BREECHING
FOR MULTIPLE BOILER INSTALLATIONS
Required Equivalent Diameter of Breeching
Diameter to maintain approximately the same
(inches) flue gas velocity for one to five
boilers (in inches)

one two three four five


Boiler Boilers Boilers Boilers Boilers

6 8 10 12 14
8 12 14 16 18
9 13 16 18 20
10 14 18 20 22
12 16 20 24 26
13 18 22 26 30
14 20 24 28 32
16 22 28 32 36
18 26 32 36 40
20 28 34 40 44
22 32 38 44 50
24 34 42 48 54
26 36 44 52 58
28 40 48 56 62
30 42 52 60 68
32 45 56 64 72

CHART 1

MINIMUM BREECHING DIAMETER


(inches O.D.)

BHP Minimum Breeching Boiler Outlet


Diameter Diameter

< 20 6 8
25- 30 8 8
30 8 10
40- 45 10 10
50- 60 10 12
65- 80 12 12
90-125 14 14
135-155 16 18
160-200 18 24
215-255 20 24
275-300 22 30
315-350 24 30
360 26 30
380-400 26 36
420-450 28 36
500-515 30 42
550-600 32 42

CHART 2

You might also like