Title:
Classification report for the determination of the fire resistance of a set of Nº 9/LE 895
penetration seals according to EN 13501-2:2007+A1:2009 Fire
classification of construction products and building elements. Part 2:
Classification using data from fire resistance tests, excluding ventilation
services (equivalent to UNE EN 13501-2:2009+A1:2010).

Tested material:
17 penetration seals based on collars reference “AF Collar”, “AF
Collar C” and “AF Multicollar” for plastic pipes, everything supplied
by AF Systems.
Test done in horizontal configuration.

File number: 16/10899-210 Part 2

Solicitor:
AF SYSTEMS Srl
Via Jenner 41-43, 26837
Mulazzano (LO)

Report Date:
25 July 2016

Tested on:
28 January 2016

The reproduction of this document is only authorised if it is made in its totality.


Electronically signed reports in digital format are considered original documents, as well as its
electronic copies. Their printing has no legal validity.
This document consists of 5 pages.

LGAI Technological Center S.A. Inscrita en el registro Mercantil de Barcelona, Tomo 35.803, Folio1, Hoja Nº B-266.627 Inscripción 1ª C.I.F. : A-63207492

Page 1
1.- INTRODUCTION
This Fire Resistance classification report defines the classification for a set of
penetration seals for plastic pipes supplied by AF Systems.

2.- DETAILS OF CLASSIFIED ELEMENT

2.1.- Type of function


Tested elements are defined as penetration seals for plastic pipes. Its function is to
withstand the integrity and thermal insulation criteria given in clause 5 of EN 13501-
2:2007+A1:2009 standard.

2.2.- Description
The complete description of the tested elements can be consulted in the test report
(see clause 3 of this classification report).

3.- TEST REPORT

This classification report is based on the following test report:


File nº: 16/10899-210 Part 1
Issued with date: 25 of July of 2016
Test carried out on: 28 of January of 2016

4.- TEST RESULTS

4.1.- Test standard:


EN 1366-3: 2009 “Fire resistance tests for service installations. Part 3: Penetration
seals” (equivalent to UNE EN 1366-3: 2011).

4.2.- Exposure conditions

Time/temperature curve T = 345 log10 (8t + 1) + 20 (acc EN 1363-1:2012)


Applied load No load applied
Support conditions Aerated concrete slab of 150 mm in thickness and
500 kg/m3.

File number: 16/10899-210 Part 2 Page 2


4.3.- Result table.

System Integrity criteria Thermal insulation


System 1 (AF Collar 315 + It was maintained the entire It was maintained the entire
HDPE pipe 315 x 9 mm) test, 181 minutes. test, 181 minutes.
System 2 (AF Collar 250 + It was maintained the entire It was maintained the entire
HDPE pipe 250 x 7.7 mm + test, 181 minutes. test, 181 minutes.
AF Panel)
System 3 (AF Collar 250 + It was maintained the entire It was maintained the entire
PVC pipe 250 x 6.2 mm + test, 181 minutes. test, 181 minutes.
AF Panel)
System 4 (AF Multicollar 110 It was maintained the entire It was maintained the entire
+ PVC pipe 110 x 3.2 mm) test, 181 minutes. test, 181 minutes.
System 5 (AF Multicollar 160 It was maintained the entire It was maintained the entire
+ PVC pipe 160 x 3.2 mm) test, 181 minutes. test, 181 minutes.
System 6 (AF Multicollar 160 It was maintained the entire It was maintained the entire
+ HDPE pipe 160 x 6.2 mm) test, 181 minutes. test, 181 minutes.
System 7 (AF Multicollar 160 It was maintained the entire It was maintained the entire
+ PP pipe 160 x 3.9 mm) test, 181 minutes. test, 181 minutes.
System 8 (AF Multicollar 110 It was maintained the entire It was maintained the entire
+ HDPE pipe 110 x 4.2 mm) test, 181 minutes. test, 181 minutes.
System 9 (AF Collar 160 + It was maintained the entire It was maintained the entire
PP pipe 160 x 3.9 mm + AF test, 181 minutes. test, 181 minutes.
Panel)
System 10 (AF Collar 110 + It failed at minute 162, when It failed at minute 162,
PP pipe 110 x 2.7 mm + AF cotton pad ignites when integrity criterion fails.
Panel)
System 11 (AF Multicollar It was maintained the entire It was maintained the entire
110 + PP pipe 110 x 2.7 test, 181 minutes. test, 181 minutes.
mm)
System 12 (AF Collar C 160 It was maintained the entire It was maintained the entire
+ HDPE pipe 160 x 6.2 mm) test, 181 minutes. test, 181 minutes.
System 13 (AF Collar 160 + It was maintained the entire It was maintained the entire
PVC pipe 160 x 3.2 mm + test, 181 minutes. test, 181 minutes.
AF Panel)
System 14 (AF Collar 110 + It failed at minute 155, when It failed at minute 155,
PVC pipe 110 x 3.2 mm + sustained flames appear. integrity criteria fails.
AF Panel)
System 15 (AF Collar C 160 It was maintained the entire It was maintained the entire
+ PP pipe 160 x 3.9 mm) test, 181 minutes. test, 181 minutes.
System 16 (AF Collar 160 + It was maintained the entire It was maintained the entire
HDPE pie 160 x 6.2 mm + test, 181 minutes. test, 181 minutes.
AF Panel)
System 17 (AF Collar 110 + It was maintained the entire It was maintained the entire
HDPE pipe 110 x 4.2 mm + test, 181 minutes. test, 181 minutes.
AF Panel )

File number: 16/10899-210 Part 2 Page 3


5.- CLASSIFICATION

According to clause 7.5 of EN 13501-2:2007+A1:2009 standard, classification of the


tested elements is:

System Classification

System 1 (AF Collar 315 + HDPE pipe 315 x 9 mm) EI 180 U/C

System 2 (AF Collar 250 + HDPE pipe 250 x 7.7 mm + AF Panel) EI 180 U/C

System 3 (AF Collar 250 + PVC pipe 250 x 6.2 mm + AF Panel) EI 180 U/C

System 4 (AF Multicollar 110 + PVC pipe 110 x 3.2 mm) EI 180 U/U

System 5 (AF Multicollar 160 + PVC pipe 160 x 3.2 mm) EI 180 U/C

System 6 (AF Multicollar 160 + HDPE pipe 160 x 6.2 mm) EI 180 U/C

System 7 (AF Multicollar 160 + PP pipe 160 x 3.9 mm) EI 180 U/C

System 8 (AF Multicollar 110 + HDPE pipe 110 x 4.2 mm) EI 180 U/U

System 9 (AF Collar 160 + PP pipe 160 x 3.9 mm + AF Panel) EI 180 U/C

System 10 (AF Collar 110 + PP pipe 110 x 2.7 mm + AF Panel) EI 120 U/U

System 11 (AF Multicollar 110 + PP pipe 110 x 2.7 mm) EI 180 U/U

System 12 (AF Collar C 160 + HDPE pipe 160 x 6.2 mm) EI 180 U/U

System 13 (AF Collar 160 + PVC pipe 160 x 3.2 mm + AF Panel) EI 180 U/U

System 14 (AF Collar 110 + PVC pipe 110 x 3.2 mm + AF Panel) EI 120 U/U

System 15 (AF Collar C 160 + PP pipe 160 x 3.9 mm) EI 180 U/U

System 16 (AF Collar 160 + HDPE pie 160 x 6.2 mm + AF Panel) EI 180 U/C

System 17 (AF Collar 110 + HDPE pipe 110 x 4.2 mm + AF Panel ) EI 180 U/U

File number: 16/10899-210 Part 2 Page 4


6.- FIELD OF DIRECT APPLICATION (according to EN 1366-3:2009)

To be consulted in file number 16/10899-660 P2

The validity period is the one indicated in the product certification system.
This document is not neither a type approval nor a product certification.

Digitally Signed By
Albert Ger

Fire Laboratory Responsible Fire Resistance Responsible


LGAI Technological Center, S.A. LGAI Technological Center, S.A.

The results refer exclusively to the sample, product or material surrendered to the Laboratory, just as it is
informed in the section of received material and tested under the conditions indicated in the norms
mentioned in this document.

Quality Service Warranty


Applus+, guaranties that this work has been realized following the exigencies of our Quality and
Sustainable System, complying with honouring the contractual conditions and the legal standard.