Control Valve - Gas or Steam flow 25/08/2020

Calculation Control Valve

Project CV-101. Upgrading Meter system Fajar Wisesa.


Tag number CV-101 By FRM
Input data App AGL
Valve
Data : 6 in Globe : Quick Open. Ports : Two. Flow to : Between
Rated Cv : 550.8. Rated xT : .68. Style Fd : .7

Pipe sizes
Inlet : in. Outlet : in. Outlet pipe wall : .365 in

Fluid data
Gas mixture components Gas property factor: 1,2 dbA
4,55% Carbon Dioxide, 3,91% Nitrogen, 82,7% Methane, 3,44% Ethane, 3,17% Propane,
0,81% Butane-n, 0,71% Butane-Iso, 0,16% Pentane-n, 0,23% Pentane-Iso, 0,32% Hexane-n,
Maximum Normal Minimum Units
Percent of nominal flow 100 50 25
Gas flow 20 10 5 Msft3/d
Pressure drop 5 10 10 psi
Flow temperature 90 80 80 degF
Inlet pressure 300 150 150 psig
Cp/Cv Sp heat ratio 1.2669 1.2726 1.2699
Molecular weight 20.238 20.174 20.238
Density @ FTP 1.135 .58976 .59171 lb/ft3
Critical pressure 673.48 676.95 673.48 psia
Critical temperature 375.435 375.435 375.435 degR
Accoustic efficiency

Output data
Required Cv 297.9 149.3 74.77
Percent of valve lift 54 27 14
Noise level: dbA
Status Normal Normal Normal
Sonic minimum size 1.243 1.237 .8754 in
User saved volume units, data for all calculations, calculate size
Source - ANSI/ISA-75.01.01-2012 Flow Equations for sizing control valves
Accuracy - Within the limits of ANSI/ISA 75.01
InstruCalc Ver.9.0.3.

Notes
Preliminary Calculation