PVC Force Main Design

Technical Director
Example
by Craig Fisher, P.E. TABLE 1
pipe to burst must exceed 315 psi, where the
time to burst is calibrated to be in the 60 to
Pressure Ratings For PVC Pipe
70 second range.

T
h e l a s t t i m e a fo rc e SDR or DR PR, psi (MPa)
While this property of PVC pipe has tradi-
m a i n d e s i g n exam p l e tionally been incorporated for quality control
51 80 (0.55) and quality assurance purposes, it has only
wa s t h e su b j e c t o f a
recently been recognized for design purpos-
PVC Pipe News arti c l e was 41 100 (0.69) es. The latest edition of AWWA Manual
the summer of 1989. [1] M23, “PVC Pipe - Design and Installation,”
32.5 125 (0.86) allows the designer to capitalize on this PVC
Since then, the cyclic pipe property. [7] For non-recurring pressure
capabilities of PVC have 26 160 (1.10) surges, such as those resulting from a power
become better defined outage or fire fighting water flows, the
25 165 (1.14) designer is allowed to compare the potential
wit h a d d i t i o n a l stu d y. [2-3] pressures (including surge) against the STR
The News kept you 21 200 (1.38)
rather than the PR.
informed of these STRs for various DRs are listed in Table 2. The
de v e lo p m e n t s wi th seve ral 18 235 (1.62) STR is calculated using a safety factor of 2.0
against the pipe’s quick-burst requirement.
ar t ic les t h a t d esc ri b ed the
14 305 (2.11)
re s e a rc h a n d s u m m a r i z e d TABLE 2
t h e re s u l t s . [ 4 - 6] EQUATION 1 STR Values for PVC Pipe
SDR = DR = D0 ÷ tmin
This article demonstrates the use of the lat- SDR or DR STR, psi (MPa)
where:
est cyclic design chart for PVC in a force D0 = average outside diameter
main setting. Additionally, the concepts of 51 128 (0.88)
tmin = minimum wall thickness
Short Term Rating (STR) and Pressure Rating
(PR) are revisited. The values used in the S H O R T T E R M R AT I N G 41 160 (1.10)
design example come from an actual project
that was reviewed by one of our member An inherent property that PVC pipes have
32.5 203 (1.40)
companies. always offered is more pressure capacity as
the duration of the application of that pres-
26 256 (1.77)
P R E S S U R E R AT I N G sure is decreased. In fact, this is why the
quick-burst and sustained-pressure test val-
This is the design step that most engineers 25 264 (1.84)
ues used for quality control purposes far
are familiar with. The operating pressure is
exceed a PVC pipe’s Pressure Rating. An
compared to the PR of the pipe. The PRs for 21 320 (2.21)
SDR41 product, with a 100 psi Pressure
various dimension ratios of PVC pipe are list-
Rating, serves as an example. For the sus-
ed in Table 1. Mathematically, the Standard 18 376 (2.60)
tained-pressure test, an SDR41 must hold
Dimension Ratio (SDR) is the same as the
210 psi in excess of 1,000 hours. For the
Dimension Ratio (DR). Both are defined in
quick-burst test, the pressure causing the 14 488 (3.40)
Equation 1.

8 • W W W. U N I - B E L L . O R G P V C P I P E N E W S • W I N T E R 2 0 0 5
C Y C L I C C A PA C I T Y Stress Amplitude (psi)

3000

2000

1500

1000

700

500

300
200
150
100
The new research on the cyclic capabilities of

50
20
PVC pressure pipe [2-3] confirmed that pre- 3000
dicting the fatigue capabilities of PVC is much Vinson
USU
like that of any other material. It is a function
2500
of two variables: the average stress and the

Mean Stress (psi)


Positive/Negative Line
stress amplitude. The design chart developed
by the research is shown in Figure 1. 2000

DESIGN STEPS 1500


Having reintroduced all the concepts, let’s review
Design
the design checks for our force main design 1000 Space
example. There are three of them. First, normal 2000 psi Limit
operating pressures (including routine surges)
500
are compared against the PR. The PR must meet
or exceed the cyclic pressures routinely generat-
ed during the force main’s operation. Second, 0
non-cyclic peak pressures are compared against 1.E+3 1.E+4 1.E+5 1.E+6 1.E+7 1.E+8 1.E+9
the STR. The STR must meet or exceed these Number of Cycles
occasional peak pressures generated by “infre- Figure 1.
quent” surge. Finally, the cyclic capability of the
PVC, as represented by the value C, must meet Routine pressures the force main experi- The water hammer resulting from an instanta-
or exceed the number of cycles expected, C’, ences are as follows: neous stoppage of flow serves as a conserva-
during the design life of the force main. tive estimate of the worst-case, non-recurring
Pop = Operating Pressure surge. It will be assumed this occurs while the
DESIGN REQUIREMENTS = 27 psi (Known) pump is operating at its normal duty point.
The pipe under consideration is a 14-inch, With that information, the worst-case peak
Pamp = Maximum Pressure Fluctuation
SDR 41, CSA B137.3 pipe, with an IPS diame- pressure may be determined as follows:
= 10 psi (Known)
ter regimen. As this is similar to the 14-inch
IPS option in AWWA C905-97, the C905 stan- Pmax = Maximum Routine Pressure Ps’ = Surge response to a 1 ft/sec
dard will be referenced in this example. The = Pop + Pamp instantaneous change in velocity
design flow is 2.65 ft3/sec. It is estimated that = 11.4 psi for SDR41(Table 5-6 AWWA
= 27 + 10
the variable speed pump will have 24 starts M23 [7])
= 37 psi
and 24 stops each day. Once the steady-state- Ps = Worst-case surge
operating flow has been achieved, the operat- Pmin = Minimum Routine Pressure
= Pop - Pamp = Dvmax Ps’
ing pressure is 27 psi. During start-up or shut-
= 27 - 10 = (2.78) (11.4)
down, the pressure fluctuations for the vari-
= 17 psi = 31.7 psi
able speed pump may be as large as 10 psi.
The force main discharges into a manhole at Hoop stresses from routine pressures may
Ppeak = Peak pressure from
atmospheric pressure at the upstream end. now be calculated. See pages 53 to 58 of unusual event
= Pop + Ps
From the AWWA C905 standard, the following AWWA M23 [7] for details:
= 27.0 + 31.7
dimensions may be looked-up or calculated: = 58.7 psi
savg = Average Hoop Stress
D0 = Average Outside Diameter = (Pop ÷ 2) (SDR -1 )
= 14.000 inches (Table 1 of C905) Calculating the number of cycles endured by
= (27 ÷ 2) (41 - 1) the force main over its design life is simple.
tmin = Minimum Wall Thickness = 540 psi
= 0.341 inches (Table 1 of C905) cycles/day = 24 starts + 24 stops
samp = Stress Amplitude = 48 cycles/day (Known)
tmin tol = Tolerance on the Minimum Wall = (Pamp ÷ 2) (SDR -1 )
= +0.048 inches (Table 1 of C905) cycles/year = (cycles/days) (365 days/year)
= (10 ÷ 2) (41 - 1)
= (48) (365)
Di = Inside Diameter = 200 psi
= 17,520 cycles/year
= D0 - 2tmin - tmin tol The fluid velocity while operating at the duty Design Life = 100 years (Known)
= 14.000 - 2(0.341) - 0.048 point is as follows:
= 13.270 inches C’ = Anticipated number of cycles during
Q = 2.65 ft3/sec (Known) force main’s design life
Ax = Cross Sectional Area
= (cycles/year) (design life)
= (p ÷ 4) (Di)2 v = Fluid Velocity
= (17,520) (100)
= (3.14 ÷ 4) (13.270)2 =Q÷A
= 1.752 x 106
= 138 in2 = 2.65 ft3/sec ÷ 0.960 ft2
= 0.960 ft2 = 2.78 ft/sec

P V C P I P E N E W S • W I N T E R 2 0 0 5 W W W. U N I - B E L L . O R G • 9
3000 Stress Amplitude (psi) In this example, the first independent vari-

2000

1500

1000
able, savg, has a value of 540 psi. In Figure 2,

700

500

300
200
150
100
50
20
3000
that value is shown in green on the y-axis. A
Vinson green line extends right from that value until
USU it intersects the second independent vari-
2500
able, samp. In the example, samp has a value
Mean Stress (psi)

Positive/Negative Line
of 200 psi. At the intersection of the green
2000 line and the black line for the 200 psi stress
amplitude, the tail of a blue line is shown.
1500 The blue line is extended downward until it
hits the x-axis. The value for C in this exam-
Design ple is 4.2 x 107, which is read from the x-axis
1000 Space of the chart at the point of intersection of the
2000 psi Limit
arrowhead of the blue line and the x-axis.
540 500
REFLECTED
0 PRESSURE WAVES
1.E+3 1.E+4 1.E+5 1.E+6 1.E+7 1.E+8 1.E+9 In this example, no secondary or tertiary
4.2E+7 pressure waves are generated during a
Number of Cycles
Figure 2. pump start-up or shut-down because the
system is vented to the atmosphere. If the
DESIGN CHECKS design chart. Refer to Figure 2. First system were a closed system, and if surge
note that it is a semi-log chart. The x- pressures were able to be reflected, addi-
Is the operating pressure less than or equal tional analysis using Miner’s Rule would be
axis has a logarithmic scale. One of the
to the PR of the SDR41 selected? needed to determine the system’s cyclic
two independent variables, average
Pop ≤ PR? stress, serves as the chart’s y-axis. The life. Appendix A of Reference 3 discusses
second independent variable, stress the theory as does Reference 6.
27 psi ≤ 100 psi (From Table 1)
amplitude, is represented by the diago-
Yes. The first design check is passed. In this example, the cyclic life is recalculat-
nal black lines that overlay the chart.
ed with the following assumptions:
Each line represents a different stress
Is the peak pressure less than or equal to
amplitude. As one moves from left to • The system is closed and the surge
the STR of the SDR41 selected?
right across the chart, the stress ampli- pressure wave is reflected throughout
Ppeak ≤ STR? tudes represented by the black lines the system.
58.7 psi ≤ 160 psi (From Table 2) decrease. The x-axis is the dependent
variable, and it denotes the cyclic life of • The attenuation of the secondary and
Yes. The second design check is passed. the PVC pressure pipe. tertiary waves follows a dampened sinu-
soidal pattern as shown in Figure 3.
Is the cyclic capacity greater than the antic-
ipated number of cycles expected for the
force main over its design life?
C’ ≤ C?
1.752 x 106 ≤ 4.2 x 107 (From Figure 1)

Yes. The third and last design check is


passed.

The design is satisfactory.

What cyclic life would the force main have


under these operating conditions?
Cyclic Life = C ÷ Anticipated Number of
Cycles per Year
Cyclic Life = 4.2 x 107 ÷17,520 cycles/year
Cyclic Life = 2,397 years

CYCLIC CHECK
The manner by which the 4.2 x 107 value
for C was determined is further detailed Figure 3. Typical surge pattern, where the pressures decay in a dampened sinusoidal pattern.
for those not familiar with the cyclic

1 0 • W W W. U N I - B E L L . O R G P V C P I P E N E W S • W I N T E R 2 0 0 5
The first step is to represent the pressure pattern with the
equivalent number of primary pressure waves. References 3
and 6 show that the secondary and tertiary waves have the The How-To
fatigue equivalent of 0.55 primary waves. So, the number of
cycles per year must be increased by 55% to account for the Handbook of PVC Pipe
pressure pattern generated by reflected surge pressure 522 PAGES
waves.
Primary Cycles per Year = (1.55) (17,520)
Primary Cycles per Year = 27,156 cycles/year

Cyclic Life = C ÷ Anticipated Number of Primary Cycles per Year


Cyclic Life = 4.2 x 107 ÷ 27,156 cycles/year
Cyclic Life = 1,547 years

The design is again shown to be more than satisfactory from


a cyclic fatigue point-of-view.

CLOSING
The real engineering work was done before our member was
contacted to review this design. A pipe diameter and pump
had already been selected. Presumably, the combination The only complete reference for those who plan, design,
was the one most efficient for the flow desired and the align- install and operate PVC systems for municipal water mains,
ment’s topography. For that combination, operating pres- sanitary sewer and storm water drainage systems. If you are
sures and pressure fluctuations were provided. planning, or now operate a PVC pressure or non-pressure sys-
tem, this handbook is a must!
Admittedly, this is a straightforward design example. No iter-
ation was required. The PR, STR, and cyclic capability provid-
ed were more than adequate. When realistic design values Indicate preferred format:
are used, the results shown here are typical. The PVC prod- ❑ Hard-Bound ❑ CD-ROM
uct that the utility routinely uses is normally very robust for $48/each $20/each
the demands of the specific application. (Includes postage and handling for US and Canadian orders.)
References:
Payable in US Funds, Texas Residents add 8.25 percent sales tax.
1. Bauer, Dennis E., “PVC Force Main Design is Key to Long-Term
Performance,” Uni-Bell PVC Pipe News, Summer, 1989, Dallas, Texas, pp. Plus air mail charges:
10+. ❑ Mexico $16/bk ❑ All Other Countries $28/bk
2. Moser, Alma P., “Cyclic Life of PVC Pipe,” Utah State University, College
of Engineering, Logan, Utah, February 17, 2001.
Mail coupon with your check to:
Uni-Bell PVC Pipe Association
3. Jared D. Jeffrey et al, “Long-Term Cyclic Testing of PVC Pipe,” Utah State 2655 Villa Creek Drive, Suite 155
University, College of Engineering, Logan, Utah, February 26, 2004.
Dallas, Texas 75234
4. Dorsett, Matt, “New Tests and Analysis Serve to Improve Cyclic Design,”
PVC News, Spring 2001, Dallas, Texas, pp. 1+. PC Requirements for Electronic Version:
5. Fisher, Craig, “PVC Pressure Pipe Endures Over Ten Million Cycles,” PVC • I386, I486, Pentium or Pentium Pro processor-based personal com-
Pipe News, Spring 2004, Dallas, Texas, pp. 9+. puter
• Microsoft Windows 95 or Windows NT 3.51 or later
6. Fisher, Craig, “The Anatomy of a Force Main Pressure Wave,” PVC Pipe
News, Summer 2004, Dallas, Texas, pp. 6-8. • 8 MB of RAM (16 MB for Windows NT) available to Acrobat Reader
• 10 MB of available hard disk space
7. “Manual M23: PVC Pipe - Design and Installation,” American Water Works • CD-ROM drive
Association, Denver, Colorado, 2002.

8. “AWWA Standard for Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Name ____________________________________________________
Fittings, 14 in. Through 48 in. (350 mm through 1,200 mm) ANSI/AWWA Company __________________________________________________
C905,” American Water Works Association, Denver, CO, 1997. Address __________________________________________________
9. “CSA Standard B137.3, Rigid Polyvinyl Chloride (PVC) Pipe for Pressure City ______________________________________________________
Applications,” Canadian Standards Association, Etobicoke, Ontario. State/Province ______________________________________________
Zip/Postal Code ____________________________________________
Country____________________________________________________
Phone: ____________________________________________________
Fax: ______________________________________________________
E-mail: ____________________________________________________

P V C P I P E N E W S • W I N T E R 2 0 0 5 W W W. U N I - B E L L . O R G • 1 1