1.3 Frequency 50 Hz
2. PERFORMANCE CURVES
2.4 Open and short circuit curves H.E.P. 33490 Issue No.1
2.5 Permitted duration of negative sequence current H.E.P. 1216 Issue No.9
2.9 Stator winding earth fault current versus time H.E.P. 12751 Issue No.2
2.11 Permitted duration of generator armature current H.E.P. 5987 Issue No.3
I.D.: GE_62_170T_11_5_0_9_FA1
1. The electrical details provided are calculated values. Unless
otherwise stated, all values are subject to tolerances as given Time : 13:25:06
in the relevant national standards.
Page: 1 of 7
ELECTRICAL DATA SHEET - CONTINUATION
BDAX 62-170ERT, 30.800 MW, 0.900 pf, 11.500 kV, 50.0 Hz
C) Sequence resistances:
I.D.: GE_62_170T_11_5_50_FA1
1. The electrical details provided are calculated values. Unless
otherwise stated, all values are subject to tolerances as given Time : 13:25:06
in the relevant national standards.
Page: 2 of 7
ELECTRICAL DATA SHEET - CONTINUATION
BDAX 62-170ERT, 30.800 MW, 0.900pf, 11.500 kV, 50.0 Hz
A) Direct Axis:
B) Quadrature Axis:
C) Miscellaneous:
I.D.: GE_62_170T_11_5_50_FA1
1. The electrical details provided are calculated values. Unless
otherwise stated, all values are subject to tolerances as given Time : 13:25:06
in the relevant national standards.
Page: 3 of 7
ELECTRICAL DATA SHEET - CONTINUATION
BDAX 62-170ERT, 30.800 MW, 0.900 pf, 11.500 kV, 50.0 Hz
7. INERTIA
2 2
7.1 Moment of inertia, WR 338 kg.m
8. EXCITATION
A) No load (cold):
8.7 Exciter field current at rated load and P.F 9.5 amps
I.D.: GE_62_170T_11_5_50_FA1
1. The electrical details provided are calculated values. Unless
otherwise stated, all values are subject to tolerances as given Time : 13:25:06
in the relevant national standards.
2. The rotor inertia value may vary slightly with generator / turbine Page: 4 of 7
Interface. In the event of conflict, the figure quoted on the rotor
Geometry drawing takes precedence.
ELECTRICAL DATA SHEET - CONTINUATION
BDAX 62-170ERT, 30.800 MW, 0.900 pf, 11.500 kV, 50.0 Hz
9.3 F.L. to N.L. steady state under full AVR control ± 0.5 %
These losses below are calculated values. The total loss and the resulting efficiencies are
guaranteed, subject to the tolerance specified in EN 60034-1.
Exciter loss(kW) 12 7
Efficiencies:
% load 100 75 50 25
I.D.: GE_62_170T_11_5_50_FA1
1. The electrical details provided are calculated values. Unless
otherwise stated, all values are subject to tolerances as given Time : 13:25:06
in the relevant national standards.
Page: 5 of 7
ELECTRICAL DATA SHEET - CONTINUATION
13. EXCITER
I.D.: GE_62_170T_11_5_50_FA1
1. The electrical details provided are calculated values. Unless
otherwise stated, all values are subject to tolerances as given Time : 13:25:06
in the relevant national standards.
Page: 6 of 7
ELECTRICAL DATA SHEET - CONTINUATION
BDAX 62-170ERT, 30.800 MW, 0.900 pf, 11.500 kV, 50.0 Hz
I.D.: GE_62_170T_11_5_50_FA1
1. The electrical details provided are calculated values. Unless
otherwise stated, all values are subject to tolerances as given Time : 13:25:06
in the relevant national standards.
Page: 7 of 7